Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2025-08-25 — OK
Operator
Magellan Pipeline Company, Lp
Cause
Equipment Failure
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$17,000
Incident datetime
2025-08-25 10:00
Report number
Location
OK
Narrative
At approximately 10:00 am a local operator attempted to start a tank mixer. The tank mixer failed to start, and operations began to investigate. The operator discovered the tank mixer bearing housing had failed causing a release. Local operations placed drip pans to collect any product that may continue to reach the ground. A vacuum truck was called to help with cleanup efforts and pump out enough product to a level where local technicians could lock in the tank mixer and stop the damaged seal from leaking any further. Technicians removed the leaking seal and replaced it with a new seal along with a new motor and gear box housing. The tank was then placed back into service.
Detailed record list
Report Received Date
2025-09-23 00:00:00
Iyear
2025
Report Number
20250228
Supplemental Number
41491
Report Type
Supplemental Final
Operator Id
22610
Name
Magellan Pipeline Company, Lp
Operator Street Address
100 West 5th Street
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74103
Local Datetime
2025-08-25 10:15:00
Time Zone
Central
Daylight Savings Ind
No
Location Latitude
29.796294
Location Longitude
-95.282123
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Gasoline (Non-Ethanol)
Unintentional Release Bbls
1
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2025-08-25 10:00:00
System Part Involved
Onshore Breakout Tank Or Storage Vessel, Including Attached Appurtenances
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
Use Of The Tank Stopped But Nothing More In The Terminal Was Affected.
Communication State Fed Ind
No
On Site Datetime
2025-08-25 10:08:00
Confirmed Discovery Datetime
2025-08-25 10:15:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Qualified Indiv Notif Datetime
2025-08-25 10:08:00
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
East Houston
Segment Name
Fac Id 357
Onshore State Abbreviation
Tx
Onshore Postal Code
77029
Onshore City Name
Houston
Onshore County Name
Harris
Designated Location
Milepost
Designated Name
0
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Tank, Including Attached Appurtenances
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Tank/vessel
Tank Vessel Subtype
Mixer
Tank Type
Atmospheric
Safe Fill Level
43
Safe Fill Level Exceeded Ind
No
Api Std Out Of Service Year
2008
Api Std In Service Year
2023
Installation Year
1998
Manufactured Year
1998
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Seal Or Packing
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
500
Est Cost Prop Damage
17000
Est Cost Emergency
940
Est Cost Environmental
665
Est Cost Other
0
Prpty
19105
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
13
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
No controllers actions had taken place prior to the release
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Non-Threaded Connection Failure
Eq Failure Type
Non-Threaded Connection Failure
Other Non Threaded Ind
Seal (Not Pump Seal) Or Packing
Failure Details
Tank Mixer Outboard Seal Failed Filling Bearing Housing With Product Which Caused The Bearing Housing To Fail Releasing Product.
Eq Additional Other Ind
Yes
Eq Additional Other Details
Bearing Housing Failed Following Seal Failure.
Preparer Name
G*** C*********
Preparer Title
Regulatory Compliance Specialist Ii
Preparer Email
G**************@o****.com
Preparer Telephone
9183818066
Prepared Date
2025-10-21 00:00:00
Authorizer Name
R*** M****
Authorizer Telephone
5807410185
Authorizer Title
Regulatory Compliance Manager
Authorizer Email
R*********@o****.com
Narrative
At approximately 10:00 am a local operator attempted to start a tank mixer. The tank mixer failed to start, and operations began to investigate. The operator discovered the tank mixer bearing housing had failed causing a release. Local operations placed drip pans to collect any product that may continue to reach the ground. A vacuum truck was called to help with cleanup efforts and pump out enough product to a level where local technicians could lock in the tank mixer and stop the damaged seal from leaking any further. Technicians removed the leaking seal and replaced it with a new seal along with a new motor and gear box housing. The tank was then placed back into service.
| Report Received Date | 2025-09-23 00:00:00 |
|---|---|
| Iyear | 2025 |
| Report Number | 20250228 |
| Supplemental Number | 41491 |
| Report Type | Supplemental Final |
| Operator Id | 22610 PHMSA Enforcement |
| Name | Magellan Pipeline Company, Lp |
| Operator Street Address | 100 West 5th Street |
| Operator City Name | Tulsa |
| Operator State Abbreviation | OK |
| Operator Postal Code | 74103 |
| Local Datetime | 2025-08-25 10:15:00 |
| Time Zone | Central |
| Daylight Savings Ind | No |
| Location Latitude | 29.796294 Google Maps OpenStreetMap |
| Location Longitude | -95.282123 Google Maps OpenStreetMap |
| Commodity Released Type | Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions |
| Commodity Subtype | Gasoline (Non-Ethanol) |
| Unintentional Release Bbls | 1 |
| Recovered Bbls | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2025-08-25 10:00:00 |
| System Part Involved | Onshore Breakout Tank Or Storage Vessel, Including Attached Appurtenances |
| On Off Shore | Onshore |
| Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | Use Of The Tank Stopped But Nothing More In The Terminal Was Affected. |
| Communication State Fed Ind | No |
| On Site Datetime | 2025-08-25 10:08:00 |
| Confirmed Discovery Datetime | 2025-08-25 10:15:00 |
| Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
| Ignite Ind | No |
| Notify Qualified Indiv Ind | Yes |
| Qualified Indiv Notif Datetime | 2025-08-25 10:08:00 |
| Oil Spill Removal Org Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | East Houston |
| Segment Name | Fac Id 357 |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 77029 |
| Onshore City Name | Houston |
| Onshore County Name | Harris |
| Designated Location | Milepost |
| Designated Name | 0 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Tank, Including Attached Appurtenances |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Tank/vessel |
| Tank Vessel Subtype | Mixer |
| Tank Type | Atmospheric |
| Safe Fill Level | 43 |
| Safe Fill Level Exceeded Ind | No |
| Api Std Out Of Service Year | 2008 |
| Api Std In Service Year | 2023 |
| Installation Year | 1998 |
| Manufactured Year | 1998 |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Seal Or Packing |
| Wildlife Impact Ind | No |
| Soil Contamination | Yes |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | Yes |
| High Pop Ind | Yes |
| High Pop Yes No | Yes |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 500 |
| Est Cost Prop Damage | 17000 |
| Est Cost Emergency | 940 |
| Est Cost Environmental | 665 |
| Est Cost Other | 0 |
| Prpty | 19105 |
| Num Persons Hosp Not Ovnght | 0 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 0 |
| Num Business Building Affctd | 0 |
| Accident Psig | 13 |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | No |
| Cpm In Place Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | No controllers actions had taken place prior to the release |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Non-Threaded Connection Failure |
| Eq Failure Type | Non-Threaded Connection Failure |
| Other Non Threaded Ind | Seal (Not Pump Seal) Or Packing |
| Failure Details | Tank Mixer Outboard Seal Failed Filling Bearing Housing With Product Which Caused The Bearing Housing To Fail Releasing Product. |
| Eq Additional Other Ind | Yes |
| Eq Additional Other Details | Bearing Housing Failed Following Seal Failure. |
| Preparer Name | G*** C********* |
| Preparer Title | Regulatory Compliance Specialist Ii |
| Preparer Email | G**************@o****.com |
| Preparer Telephone | 9183818066 |
| Prepared Date | 2025-10-21 00:00:00 |
| Authorizer Name | R*** M**** |
| Authorizer Telephone | 5807410185 |
| Authorizer Title | Regulatory Compliance Manager |
| Authorizer Email | R*********@o****.com |
| Narrative | At approximately 10:00 am a local operator attempted to start a tank mixer. The tank mixer failed to start, and operations began to investigate. The operator discovered the tank mixer bearing housing had failed causing a release. Local operations placed drip pans to collect any product that may continue to reach the ground. A vacuum truck was called to help with cleanup efforts and pump out enough product to a level where local technicians could lock in the tank mixer and stop the damaged seal from leaking any further. Technicians removed the leaking seal and replaced it with a new seal along with a new motor and gear box housing. The tank was then placed back into service. |