Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2025-08-18 — PA
Operator
Buckeye Partners, Lp
Cause
Corrosion Failure
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$42,000
Incident datetime
2025-08-18 07:30
Report number
Location
PA
Narrative
On 8/18/2025 at approximately 07:30 eastern daylight savings time, local operator discovered product in a piping trench located just outside the perimeter of the tank field. The product appeared to be historical in nature. Osro was on site and cleaned up without further issue. Several hours later gasoline was discovered in the same location. At this time, the line was shut down and isolated. All internal notifications were made. Further investigation revealed the 8-inch diameter tank to tank circulation line was slowly leaking from a section of terminal pipe located approximately two feet into the tank dike area. All external notification were made, and nrc was contacted at this time. Osro was on site and all product and affected soil was recovered and removed. Approximately 100 barrels of gasoline has been recovered. All product was contained on operator property. There were no fires, injuries, and no product was released to any surface water. Cleanup is completed. The section of terminal piping has been idled and isolated with no plans of returning to service as this time. Note: buckeye acquired this facility in 2014 from hess. Buckeye does not have records prior to purchasing. Updates to this report will be submitted. 10/27/2025 update below: minor updates have been made. Section d. 3. Updated to 'yes' section d. 8c. Updated to $42,000 as previously reported, the section of pipe remains idled with no plans on placing back into service.
Detailed record list
Report Received Date
2025-09-15 00:00:00
Iyear
2025
Report Number
20250223
Supplemental Number
41518
Report Type
Supplemental Final
Operator Id
1845
Name
Buckeye Partners, Lp
Operator Street Address
The Buckeye Building 6161 Hamilton Boulevar
Operator City Name
Allentown
Operator State Abbreviation
PA
Operator Postal Code
18106
Local Datetime
2025-08-18 07:30:00
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Latitude
40.562155
Location Longitude
-74.245297
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Gasoline (Non-Ethanol)
Unintentional Release Bbls
100
Recovered Bbls
100
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2025-08-18 07:30:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2025-08-18 11:50:00
Still Shutdown Ind
Yes
Communication State Fed Ind
No
On Site Datetime
2025-08-18 07:30:00
Confirmed Discovery Datetime
2025-08-18 11:50:00
Nrc Rpt Datetime
2025-08-18 13:35:00
Nrc Rpt Num
1440201
Additional Nrc Report Numbers
1440416
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Qualified Indiv Notif Datetime
2025-08-18 07:30:00
Oil Spill Removal Org Ind
Yes
Osro Activated Datetime
2025-08-18 07:30:00
Osro Arrived On Site Dt
8/18/2025 7:30
Num Pub Evacuated
0
Pipe Fac Name
Port Reading Terminal
Segment Name
Terminal Piping
Onshore State Abbreviation
Nj
Onshore Postal Code
07064
Onshore City Name
Port Reading
Onshore County Name
Middlesex
Designated Location
Milepost
Designated Name
0
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Transition Area
Incident Area Subtype
Soil/air Interface
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Pipe
Pipe Type
Pipe Body
Puddle Weld Ind
No
Pipe Diameter
8
Pipe Wall Thickness
0.322
Pipe Smys
24000
Pipe Specification
Unknown
Pipe Seam Type
Other
Pipe Seam Details
Unknown
Pipe Manufacturer
Unknown
Pipe Coating Type
None
Coating Applied Ind
Unknown
Installation Year
Unknown
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
Yes
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
Commercially Nav Ind
Yes
Commercially Nav Yes No
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Usa Drinking Ind
Yes
Usa Drinking Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
0
Est Cost Prop Damage
42000
Est Cost Emergency
80000
Est Cost Environmental
160000
Est Cost Other
0
Prpty
282000
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
50
Mop Psig
275
Mop Cfr Section
Internal Design Pressure �195.406(A)(1)
Maop Established Date
2014-07-01 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
< 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
This section of terminal piping is outside of controller purview.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
External Corrosion
Internal External
External Corrosion
Visual Exam Results
Localized Pitting
Galvanic Corrosion Ind
Yes
Field Exam Basis Ind
Yes
Underground Location
Yes
Under Cathodic Protection Ind
Yes
Cathodic Pro Start Year
2014
Shielding Evident
No
Cathodic Survey Type
Yes
Cp Annual Survey Ind
Yes
Cp Annual Survey Year
2025
Prior Damage
N/a Bare/ineffectively Coated Pipe
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Preparer Name
D*** C*****
Preparer Title
Senior Specialist Dot Compliance
Preparer Email
D******@b******.com
Preparer Telephone
4847071426
Prepared Date
2025-10-29 00:00:00
Authorizer Name
R***** O****
Authorizer Telephone
610-904-4524
Authorizer Title
Director Dot Compliance
Authorizer Email
R*****@b******.com
Narrative
On 8/18/2025 at approximately 07:30 eastern daylight savings time, local operator discovered product in a piping trench located just outside the perimeter of the tank field. The product appeared to be historical in nature. Osro was on site and cleaned up without further issue. Several hours later gasoline was discovered in the same location. At this time, the line was shut down and isolated. All internal notifications were made. Further investigation revealed the 8-inch diameter tank to tank circulation line was slowly leaking from a section of terminal pipe located approximately two feet into the tank dike area. All external notification were made, and nrc was contacted at this time. Osro was on site and all product and affected soil was recovered and removed. Approximately 100 barrels of gasoline has been recovered. All product was contained on operator property. There were no fires, injuries, and no product was released to any surface water. Cleanup is completed. The section of terminal piping has been idled and isolated with no plans of returning to service as this time. Note: buckeye acquired this facility in 2014 from hess. Buckeye does not have records prior to purchasing. Updates to this report will be submitted. 10/27/2025 update below: minor updates have been made. Section d. 3. Updated to 'yes' section d. 8c. Updated to $42,000 as previously reported, the section of pipe remains idled with no plans on placing back into service.
| Report Received Date | 2025-09-15 00:00:00 |
|---|---|
| Iyear | 2025 |
| Report Number | 20250223 |
| Supplemental Number | 41518 |
| Report Type | Supplemental Final |
| Operator Id | 1845 PHMSA Enforcement |
| Name | Buckeye Partners, Lp |
| Operator Street Address | The Buckeye Building 6161 Hamilton Boulevar |
| Operator City Name | Allentown |
| Operator State Abbreviation | PA |
| Operator Postal Code | 18106 |
| Local Datetime | 2025-08-18 07:30:00 |
| Time Zone | Eastern |
| Daylight Savings Ind | Yes |
| Location Latitude | 40.562155 Google Maps OpenStreetMap |
| Location Longitude | -74.245297 Google Maps OpenStreetMap |
| Commodity Released Type | Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions |
| Commodity Subtype | Gasoline (Non-Ethanol) |
| Unintentional Release Bbls | 100 |
| Recovered Bbls | 100 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2025-08-18 07:30:00 |
| System Part Involved | Onshore Terminal/tank Farm Equipment And Piping |
| On Off Shore | Onshore |
| Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2025-08-18 11:50:00 |
| Still Shutdown Ind | Yes |
| Communication State Fed Ind | No |
| On Site Datetime | 2025-08-18 07:30:00 |
| Confirmed Discovery Datetime | 2025-08-18 11:50:00 |
| Nrc Rpt Datetime | 2025-08-18 13:35:00 |
| Nrc Rpt Num | 1440201 NRC Report How to search |
| Additional Nrc Report Numbers | 1440416 |
| Ignite Ind | No |
| Notify Qualified Indiv Ind | Yes |
| Qualified Indiv Notif Datetime | 2025-08-18 07:30:00 |
| Oil Spill Removal Org Ind | Yes |
| Osro Activated Datetime | 2025-08-18 07:30:00 |
| Osro Arrived On Site Dt | 8/18/2025 7:30 |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Port Reading Terminal |
| Segment Name | Terminal Piping |
| Onshore State Abbreviation | Nj |
| Onshore Postal Code | 07064 |
| Onshore City Name | Port Reading |
| Onshore County Name | Middlesex |
| Designated Location | Milepost |
| Designated Name | 0 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Transition Area |
| Incident Area Subtype | Soil/air Interface |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Pipe |
| Pipe Type | Pipe Body |
| Puddle Weld Ind | No |
| Pipe Diameter | 8 |
| Pipe Wall Thickness | 0.322 |
| Pipe Smys | 24000 |
| Pipe Specification | Unknown |
| Pipe Seam Type | Other |
| Pipe Seam Details | Unknown |
| Pipe Manufacturer | Unknown |
| Pipe Coating Type | None |
| Coating Applied Ind | Unknown |
| Installation Year | Unknown |
| Manufactured Year | Unknown |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Pinhole |
| Wildlife Impact Ind | No |
| Soil Contamination | Yes |
| Long Term Assessment | Yes |
| Remediation Ind | Yes |
| Soil Remed Ind | Yes |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | Yes |
| Commercially Nav Ind | Yes |
| Commercially Nav Yes No | Yes |
| High Pop Ind | Yes |
| High Pop Yes No | Yes |
| Usa Drinking Ind | Yes |
| Usa Drinking Yes No | Yes |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 0 |
| Est Cost Prop Damage | 42000 |
| Est Cost Emergency | 80000 |
| Est Cost Environmental | 160000 |
| Est Cost Other | 0 |
| Prpty | 282000 |
| Num Persons Hosp Not Ovnght | 0 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 0 |
| Num Business Building Affctd | 0 |
| Accident Psig | 50 |
| Mop Psig | 275 |
| Mop Cfr Section | Internal Design Pressure �195.406(A)(1) View CFR 49 §192 |
| Maop Established Date | 2014-07-01 00:00:00 |
| Maop Reversal Flow Ind | No |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | < 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | This section of terminal piping is outside of controller purview. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Corrosion Failure |
| Cause Details | External Corrosion |
| Internal External | External Corrosion |
| Visual Exam Results | Localized Pitting |
| Galvanic Corrosion Ind | Yes |
| Field Exam Basis Ind | Yes |
| Underground Location | Yes |
| Under Cathodic Protection Ind | Yes |
| Cathodic Pro Start Year | 2014 |
| Shielding Evident | No |
| Cathodic Survey Type | Yes |
| Cp Annual Survey Ind | Yes |
| Cp Annual Survey Year | 2025 |
| Prior Damage | N/a Bare/ineffectively Coated Pipe |
| Collected Data Ind | No |
| Has Hydrtst Conduc Before Ind | No |
| Direct Asmnt Conducted | No |
| Non Destructive Exam Ind | No |
| Preparer Name | D*** C***** |
| Preparer Title | Senior Specialist Dot Compliance |
| Preparer Email | D******@b******.com |
| Preparer Telephone | 4847071426 |
| Prepared Date | 2025-10-29 00:00:00 |
| Authorizer Name | R***** O**** |
| Authorizer Telephone | 610-904-4524 |
| Authorizer Title | Director Dot Compliance |
| Authorizer Email | R*****@b******.com |
| Narrative | On 8/18/2025 at approximately 07:30 eastern daylight savings time, local operator discovered product in a piping trench located just outside the perimeter of the tank field. The product appeared to be historical in nature. Osro was on site and cleaned up without further issue. Several hours later gasoline was discovered in the same location. At this time, the line was shut down and isolated. All internal notifications were made. Further investigation revealed the 8-inch diameter tank to tank circulation line was slowly leaking from a section of terminal pipe located approximately two feet into the tank dike area. All external notification were made, and nrc was contacted at this time. Osro was on site and all product and affected soil was recovered and removed. Approximately 100 barrels of gasoline has been recovered. All product was contained on operator property. There were no fires, injuries, and no product was released to any surface water. Cleanup is completed. The section of terminal piping has been idled and isolated with no plans of returning to service as this time. Note: buckeye acquired this facility in 2014 from hess. Buckeye does not have records prior to purchasing. Updates to this report will be submitted. 10/27/2025 update below: minor updates have been made. Section d. 3. Updated to 'yes' section d. 8c. Updated to $42,000 as previously reported, the section of pipe remains idled with no plans on placing back into service. |