HL incident on 2025-08-15 — TX

Operator
Western Midstream Partners, Lp
Cause
Equipment Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$1,000
Incident datetime
2025-08-15 11:02
Report number
Location
TX
Narrative
On 8/15/2025 the python 54-1-37, a dbm oil services pipeline, sustained a small leak near a pig trap, releasing 1.23 bbls to ground. A half inch reducer union on a thermal expansion line loosened due to the stress induced from the height of the line. Technicians onsite were able to isolate the 1� valve on the thermal line, tighten the union and stop the leak. On september 22nd, the thermal expansion was remediated, lowering the vertical height of the line and replacing the half inch reducer union with a 1 inch, thereby reducing the vibration of the line and stress on the union. Dbm oil services llc is a subsidiary of western midstream.
Detailed record list
Report Received Date
2025-09-08 00:00:00
Iyear
2025
Report Number
20250210
Supplemental Number
41604
Report Type
Supplemental Final
Operator Id
Name
Western Midstream Partners, Lp
Operator Street Address
9950 Woodloch Forest Dr Suite 2800
Operator City Name
The Woodlands
Operator State Abbreviation
TX
Operator Postal Code
77380
Local Datetime
2025-08-15 11:02:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Crude Oil
Unintentional Release Bbls
1.23
Recovered Bbls
1.23
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2025-08-15 11:02:00
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
It Was A Small Discharge That Was Easily Isolated And Contained
Communication State Fed Ind
No
On Site Datetime
2025-08-15 11:02:00
Confirmed Discovery Datetime
2025-08-15 15:22:00
Nrc Rpt Datetime
2025-08-15 04:02:00
Nrc Rpt Num
Ignite Ind
No
Upstream Action Taken
Valve Closure
Upstream Valve Close Datetime
2025-08-15 11:02:00
Upstream Valve Type Ind
Manual
Downstream Action Taken
Operational Control
Downstream Oprtnl Cntrl Detail
Small Leak, Containment Was Not Needed
Notify Qualified Indiv Ind
No
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Dbm Oil Services Llc
Segment Name
Python 54-1-37-48 Oil Pl
Onshore State Abbreviation
Tx
Onshore Postal Code
79754
Onshore City Name
Not Within A Municipality
Onshore County Name
Loving
Designated Location
Milepost
Designated Name
66
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Scraper/pig Trap
Installation Year
2022
Manufactured Year
2022
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Connection Failure
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
0
Est Cost Prop Damage
1000
Est Cost Emergency
0
Est Cost Environmental
6500
Est Cost Other
0
Prpty
7500
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
250
Mop Psig
1440
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
2022-04-27 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
< 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Small leak
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Threaded Connection/coupling Failure
Eq Failure Type
Threaded Connection/coupling Failure
Other Stripped Ind
Threaded Pipe Collar
Additional Vibration Ind
Yes
Eqf Threaded Coupling Ind
Yes
Preparer Name
T***** A*****
Preparer Title
Dot Advisor
Preparer Email
T************@w***************.com
Preparer Telephone
713-842-0362
Prepared Date
2025-11-18 00:00:00
Local Contact Name
D*** A*******
Local Contact Email
D************@w***************.com
Local Contact Telephone
4328882720
Authorizer Name
T*** B****
Authorizer Telephone
7134197032
Authorizer Title
Dot Manager
Authorizer Email
T*********@w***************.com
Narrative
On 8/15/2025 the python 54-1-37, a dbm oil services pipeline, sustained a small leak near a pig trap, releasing 1.23 bbls to ground. A half inch reducer union on a thermal expansion line loosened due to the stress induced from the height of the line. Technicians onsite were able to isolate the 1� valve on the thermal line, tighten the union and stop the leak. On september 22nd, the thermal expansion was remediated, lowering the vertical height of the line and replacing the half inch reducer union with a 1 inch, thereby reducing the vibration of the line and stress on the union. Dbm oil services llc is a subsidiary of western midstream.
Report Received Date 2025-09-08 00:00:00
Iyear 2025
Report Number 20250210
Supplemental Number 41604
Report Type Supplemental Final
Operator Id 473 PHMSA Enforcement
Name Western Midstream Partners, Lp
Operator Street Address 9950 Woodloch Forest Dr Suite 2800
Operator City Name The Woodlands
Operator State Abbreviation TX
Operator Postal Code 77380
Local Datetime 2025-08-15 11:02:00
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 31.914252 Google Maps OpenStreetMap
Location Longitude -103.606527 Google Maps OpenStreetMap
Commodity Released Type Crude Oil
Unintentional Release Bbls 1.23
Recovered Bbls 1.23
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Incident Identified Datetime 2025-08-15 11:02:00
System Part Involved Onshore Pipeline, Including Valve Sites
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind No
Shutdown Explain It Was A Small Discharge That Was Easily Isolated And Contained
Communication State Fed Ind No
On Site Datetime 2025-08-15 11:02:00
Confirmed Discovery Datetime 2025-08-15 15:22:00
Nrc Rpt Datetime 2025-08-15 04:02:00
Nrc Rpt Num 1440116 NRC Report How to search
Ignite Ind No
Upstream Action Taken Valve Closure
Upstream Valve Close Datetime 2025-08-15 11:02:00
Upstream Valve Type Ind Manual
Downstream Action Taken Operational Control
Downstream Oprtnl Cntrl Detail Small Leak, Containment Was Not Needed
Notify Qualified Indiv Ind No
Oil Spill Removal Org Ind No
Num Pub Evacuated 0
Pipe Fac Name Dbm Oil Services Llc
Segment Name Python 54-1-37-48 Oil Pl
Onshore State Abbreviation Tx
Onshore Postal Code 79754
Onshore City Name Not Within A Municipality
Onshore County Name Loving
Designated Location Milepost
Designated Name 66
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Intrastate
Item Involved Scraper/pig Trap
Installation Year 2022
Manufactured Year 2022
Material Involved Carbon Steel
Release Type Leak
Leak Type Connection Failure
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment No
Remediation Ind Yes
Soil Remed Ind Yes
Water Contam Ind No
Could Be Hca No
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 0
Est Cost Prop Damage 1000
Est Cost Emergency 0
Est Cost Environmental 6500
Est Cost Other 0
Prpty 7500
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 250
Mop Psig 1440
Mop Cfr Section Component Design Pressure �195.406(A)(2) View CFR 49 §192
Maop Established Date 2022-04-27 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Internal Inspection Ind Yes
Operation Complications Ind No
Pipeline Function < 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details Small leak
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Threaded Connection/coupling Failure
Eq Failure Type Threaded Connection/coupling Failure
Other Stripped Ind Threaded Pipe Collar
Additional Vibration Ind Yes
Eqf Threaded Coupling Ind Yes
Preparer Name T***** A*****
Preparer Title Dot Advisor
Preparer Email T************@w***************.com
Preparer Telephone 713-842-0362
Prepared Date 2025-11-18 00:00:00
Local Contact Name D*** A*******
Local Contact Email D************@w***************.com
Local Contact Telephone 4328882720
Authorizer Name T*** B****
Authorizer Telephone 7134197032
Authorizer Title Dot Manager
Authorizer Email T*********@w***************.com
Narrative On 8/15/2025 the python 54-1-37, a dbm oil services pipeline, sustained a small leak near a pig trap, releasing 1.23 bbls to ground. A half inch reducer union on a thermal expansion line loosened due to the stress induced from the height of the line. Technicians onsite were able to isolate the 1� valve on the thermal line, tighten the union and stop the leak. On september 22nd, the thermal expansion was remediated, lowering the vertical height of the line and replacing the half inch reducer union with a 1 inch, thereby reducing the vibration of the line and stress on the union. Dbm oil services llc is a subsidiary of western midstream.

All rights reserved. Copyright © by ClearPHMSA