HL incident on 2025-08-03 — OK

Operator
Explorer Pipeline Co
Cause
Equipment Failure
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$75
Incident datetime
2025-08-03 01:15
Report number
Location
OK
Narrative
On september 3, 2025, explorer scada detected a vapor monitor alarm at 01:15. The pipeline was shut down and the station was isolated from the mainline pipeline. The appropriate notifications were made, and area personnel responded and identified a stainless still fitting associated with a pump seal flush system was cracked and had leaked. The release was totally contained on the property. Due to the location of the release around the pump and manifold, manual labor was necessary to excavate and remove equipment to access the impacted soil. Once it was confirmed the cost would exceed $50,000 on september 6, 2025, the national response center was notified. Explorer is working with the manufacturer of the fitting to determine the roof cause.
Detailed record list
Report Received Date
2025-09-02 00:00:00
Iyear
2025
Report Number
20250208
Supplemental Number
41330
Report Type
Original
Operator Id
Name
Explorer Pipeline Co
Operator Street Address
Po Box 2650
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74101
Local Datetime
2025-08-03 01:15:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Mixture Of Refined Products (Transmix Or Other Mixture)
Unintentional Release Bbls
5
Recovered Bbls
5
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Incident Identified Datetime
2025-08-03 01:15:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2025-08-03 01:18:00
Restart Datetime
2025-08-03 04:06:00
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2025-08-03 09:30:00
On Site Datetime
2025-08-03 03:15:00
Confirmed Discovery Datetime
2025-08-03 03:15:00
Nrc Rpt Datetime
2025-08-06 15:10:00
Nrc Rpt Num
Additional Nrc Report Numbers
1439248
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Qualified Indiv Notif Datetime
2025-08-03 01:57:00
Oil Spill Removal Org Ind
Yes
Osro Activated Datetime
2025-08-03 03:21:00
Osro Arrived On Site Dt
8/3/2025 9:31
Num Pub Evacuated
0
Pipe Fac Name
Springfield, Mo Pump Station
Segment Name
Springfield, Mo Pump Station
Onshore State Abbreviation
Mo
Onshore Postal Code
65707
Onshore City Name
Halfway
Onshore County Name
Polk
Designated Location
Milepost
Designated Name
191.94
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Tubing
Tubing Material
Stainless Steel
Tubing Type
Rigid
Installation Year
2025
Manufactured Year
Unknown
Material Involved
Material Other Than Carbon Steel
Material Details
Stainless Steel
Release Type
Leak
Leak Type
Crack
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
Usa Ecological Ind
Yes
Usa Ecological Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
630
Est Cost Prop Damage
75
Est Cost Emergency
125000
Est Cost Environmental
125000
Est Cost Other
0
Prpty
250705
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
690.8
Mop Psig
1260
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
2025-07-16 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Defective Or Loose Tubing Or Fitting
Eq Failure Type
Defective Or Loose Tubing Or Fitting
Eq Additional Other Ind
Yes
Eq Additional Other Details
Under Investigation With Manufacturer.
Preparer Name
K**** E* B****
Preparer Title
Manager Dot And Regulatory Compliance
Preparer Email
K*****@e***.com
Preparer Telephone
9184935104
Prepared Date
2025-09-02 00:00:00
Local Contact Name
J***** M*******
Local Contact Email
J********@e***.com
Local Contact Telephone
9185913266
Authorizer Name
L***** S******
Authorizer Telephone
9183595471
Authorizer Title
Vp Hsse
Authorizer Email
L*******@e***.com
Narrative
On september 3, 2025, explorer scada detected a vapor monitor alarm at 01:15. The pipeline was shut down and the station was isolated from the mainline pipeline. The appropriate notifications were made, and area personnel responded and identified a stainless still fitting associated with a pump seal flush system was cracked and had leaked. The release was totally contained on the property. Due to the location of the release around the pump and manifold, manual labor was necessary to excavate and remove equipment to access the impacted soil. Once it was confirmed the cost would exceed $50,000 on september 6, 2025, the national response center was notified. Explorer is working with the manufacturer of the fitting to determine the roof cause.
Report Received Date 2025-09-02 00:00:00
Iyear 2025
Report Number 20250208
Supplemental Number 41330
Report Type Original
Operator Id 4805 PHMSA Enforcement
Name Explorer Pipeline Co
Operator Street Address Po Box 2650
Operator City Name Tulsa
Operator State Abbreviation OK
Operator Postal Code 74101
Local Datetime 2025-08-03 01:15:00
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 37.503016 Google Maps OpenStreetMap
Location Longitude -93.27968 Google Maps OpenStreetMap
Commodity Released Type Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype Mixture Of Refined Products (Transmix Or Other Mixture)
Unintentional Release Bbls 5
Recovered Bbls 5
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Incident Identified Datetime 2025-08-03 01:15:00
System Part Involved Onshore Pump/meter Station Equipment And Piping
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind Yes
Shutdown Datetime 2025-08-03 01:18:00
Restart Datetime 2025-08-03 04:06:00
Communication State Fed Ind Yes
Party Initiated Communication Operator
Initial Responder Com Datetime 2025-08-03 09:30:00
On Site Datetime 2025-08-03 03:15:00
Confirmed Discovery Datetime 2025-08-03 03:15:00
Nrc Rpt Datetime 2025-08-06 15:10:00
Nrc Rpt Num 1439072 NRC Report How to search
Additional Nrc Report Numbers 1439248
Ignite Ind No
Notify Qualified Indiv Ind Yes
Qualified Indiv Notif Datetime 2025-08-03 01:57:00
Oil Spill Removal Org Ind Yes
Osro Activated Datetime 2025-08-03 03:21:00
Osro Arrived On Site Dt 8/3/2025 9:31
Num Pub Evacuated 0
Pipe Fac Name Springfield, Mo Pump Station
Segment Name Springfield, Mo Pump Station
Onshore State Abbreviation Mo
Onshore Postal Code 65707
Onshore City Name Halfway
Onshore County Name Polk
Designated Location Milepost
Designated Name 191.94
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
Item Involved Tubing
Tubing Material Stainless Steel
Tubing Type Rigid
Installation Year 2025
Manufactured Year Unknown
Material Involved Material Other Than Carbon Steel
Material Details Stainless Steel
Release Type Leak
Leak Type Crack
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca Yes
Usa Ecological Ind Yes
Usa Ecological Yes No Yes
Est Cost Oper Paid 0
Est Cost Gas Released 630
Est Cost Prop Damage 75
Est Cost Emergency 125000
Est Cost Environmental 125000
Est Cost Other 0
Prpty 250705
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 690.8
Mop Psig 1260
Mop Cfr Section Component Design Pressure �195.406(A)(2) View CFR 49 §192
Maop Established Date 2025-07-16 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind Yes
Cpm In Place Ind Yes
Cpm Operating Ind Yes
Cpm Functional Ind Yes
Cpm Detection Ind No
Cpm Conf Ind No
Investigation Status Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind Yes
Invest No Controller Ind Yes
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Defective Or Loose Tubing Or Fitting
Eq Failure Type Defective Or Loose Tubing Or Fitting
Eq Additional Other Ind Yes
Eq Additional Other Details Under Investigation With Manufacturer.
Preparer Name K**** E* B****
Preparer Title Manager Dot And Regulatory Compliance
Preparer Email K*****@e***.com
Preparer Telephone 9184935104
Prepared Date 2025-09-02 00:00:00
Local Contact Name J***** M*******
Local Contact Email J********@e***.com
Local Contact Telephone 9185913266
Authorizer Name L***** S******
Authorizer Telephone 9183595471
Authorizer Title Vp Hsse
Authorizer Email L*******@e***.com
Narrative On september 3, 2025, explorer scada detected a vapor monitor alarm at 01:15. The pipeline was shut down and the station was isolated from the mainline pipeline. The appropriate notifications were made, and area personnel responded and identified a stainless still fitting associated with a pump seal flush system was cracked and had leaked. The release was totally contained on the property. Due to the location of the release around the pump and manifold, manual labor was necessary to excavate and remove equipment to access the impacted soil. Once it was confirmed the cost would exceed $50,000 on september 6, 2025, the national response center was notified. Explorer is working with the manufacturer of the fitting to determine the roof cause.