HL incident on 2025-08-28 — TX
Operator
Et Crude Operating Llc
Cause
Equipment Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$250
Incident datetime
2025-08-28 00:00 UTC
Report number
Location
TX
Narrative
On 07/30/25 at approximately 22:37, a pipeline controller received a hi-hi pressure alarm on the maurepas 24-inch line at norco meter station. The line was immediately shut-in and a pipeline tech was dispatched to the site. Once on site, a crude oil release was confirmed coming from a braided stainless steel hose connected to drain from a thermal relief. Approximately 0.36 (15 gallons) barrels of crude oil was released. All free product was cleaned and contaminated soil and rocks were cleaned up. This braided stainless steel hose was replaced with a new hose and the pressure safety valve was checked for proper operation. The line was restarted at 02:28. An investigation determined the cause of the accident was due to equipment failure. The liner inside the braided stainless steel had cracked due to routine wear.
Detailed record list
Report Received Date
2025-08-28 00:00:00
Iyear
2025
Report Number
20250204
Supplemental Number
41316
Report Type
Original Final
Operator Id
31476
Name
Et Crude Operating Llc
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
30.018533
Location Longitude
-90.404579
Commodity Released Type
Crude Oil
Unintentional Release Bbls
0.36
Recovered Bbls
0.36
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Communication State Fed Ind
No
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Norco Meter Station
Segment Name
Maurepas 24-Inch
Onshore State Abbreviation
La
Onshore Postal Code
70079
Onshore City Name
Not Within A Municipality
Onshore County Name
St. Charles
Designated Location
Survey Station No.
Designated Name
0+00
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Relief Line And Relief Equipment
Installation Year
2018
Manufactured Year
Unknown
Material Involved
Material Other Than Carbon Steel
Material Details
Stainless Steel Braided Hose
Release Type
Leak
Leak Type
Crack
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
20
Est Cost Prop Damage
250
Est Cost Emergency
1704
Est Cost Environmental
1700
Est Cost Other
0
Prpty
3674
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
293
Mop Psig
285
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
2018-04-11 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Exceeded Mop, But Did Not Exceed 110% Of Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
A review of the accident determined that there were no control room actions that contributed to the event.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Other Equipment Failure
Eq Failure Type
Other Equipment Failure
Failure Details
Braided Stainless Steel Hose Failure
Eq Additional Other Ind
Yes
Eq Additional Other Details
Routine Wear Led To A Crack In The Internal Liner Of The Braided Hose.
Preparer Name
T*** N*******
Preparer Title
Director - Dot Compliance
Preparer Email
T************@e*************.com
Preparer Telephone
713-989-7126
Prepared Date
2025-08-28 00:00:00
Authorizer Name
T*** N*******
Authorizer Telephone
713-989-7126
Authorizer Title
Director - Dot Compliance
Authorizer Email
T************@e*************.com
Narrative
On 07/30/25 at approximately 22:37, a pipeline controller received a hi-hi pressure alarm on the maurepas 24-inch line at norco meter station. The line was immediately shut-in and a pipeline tech was dispatched to the site. Once on site, a crude oil release was confirmed coming from a braided stainless steel hose connected to drain from a thermal relief. Approximately 0.36 (15 gallons) barrels of crude oil was released. All free product was cleaned and contaminated soil and rocks were cleaned up. This braided stainless steel hose was replaced with a new hose and the pressure safety valve was checked for proper operation. The line was restarted at 02:28. An investigation determined the cause of the accident was due to equipment failure. The liner inside the braided stainless steel had cracked due to routine wear.
Report Received Date | 2025-08-28 00:00:00 |
---|---|
Iyear | 2025 |
Report Number | 20250204 |
Supplemental Number | 41316 |
Report Type | Original Final |
Operator Id | 31476 PHMSA Enforcement |
Name | Et Crude Operating Llc |
Operator Street Address | 1300 Main Street |
Operator City Name | Houston |
Operator State Abbreviation | TX |
Operator Postal Code | 77002 |
Time Zone | Central |
Daylight Savings Ind | Yes |
Location Latitude | 30.018533 Google Maps OpenStreetMap |
Location Longitude | -90.404579 Google Maps OpenStreetMap |
Commodity Released Type | Crude Oil |
Unintentional Release Bbls | 0.36 |
Recovered Bbls | 0.36 |
Fatality Ind | No |
Fatal | 0 |
Injury Ind | No |
Injure | 0 |
Accident Identifier | Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations) |
System Part Involved | Onshore Pump/meter Station Equipment And Piping |
On Off Shore | Onshore |
Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
Shutdown Due Accident Ind | Yes |
Communication State Fed Ind | No |
Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
Ignite Ind | No |
Notify Qualified Indiv Ind | Yes |
Oil Spill Removal Org Ind | No |
Num Pub Evacuated | 0 |
Pipe Fac Name | Norco Meter Station |
Segment Name | Maurepas 24-Inch |
Onshore State Abbreviation | La |
Onshore Postal Code | 70079 |
Onshore City Name | Not Within A Municipality |
Onshore County Name | St. Charles |
Designated Location | Survey Station No. |
Designated Name | 0+00 |
Federal | No |
Location Type | Totally Contained On Operator-Controlled Property |
Incident Area Type | Aboveground |
Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
Crossing | No |
Pipe Facility Type | Intrastate |
Item Involved | Relief Line And Relief Equipment |
Installation Year | 2018 |
Manufactured Year | Unknown |
Material Involved | Material Other Than Carbon Steel |
Material Details | Stainless Steel Braided Hose |
Release Type | Leak |
Leak Type | Crack |
Wildlife Impact Ind | No |
Soil Contamination | Yes |
Long Term Assessment | No |
Remediation Ind | Yes |
Soil Remed Ind | Yes |
Water Contam Ind | No |
Could Be Hca | Yes |
Commodity Reached Hca | Yes |
High Pop Ind | Yes |
High Pop Yes No | Yes |
Est Cost Oper Paid | 0 |
Est Cost Gas Released | 20 |
Est Cost Prop Damage | 250 |
Est Cost Emergency | 1704 |
Est Cost Environmental | 1700 |
Est Cost Other | 0 |
Prpty | 3674 |
Num Persons Hosp Not Ovnght | 0 |
Num Injured Treated By Emt | 0 |
Num Resident Building Affctd | 0 |
Num Business Building Affctd | 0 |
Accident Psig | 293 |
Mop Psig | 285 |
Mop Cfr Section | Component Design Pressure �195.406(A)(2) View CFR 49 §192 |
Maop Established Date | 2018-04-11 00:00:00 |
Maop Reversal Flow Ind | No |
Accident Pressure | Pressure Exceeded Mop, But Did Not Exceed 110% Of Mop |
Pressure Restriction Ind | No |
Pipeline Function | > 20% Smys Regulated Transmission |
Scada In Place Ind | Yes |
Scada Operating Ind | Yes |
Scada Functional Ind | Yes |
Scada Detection Ind | Yes |
Scada Conf Ind | Yes |
Cpm In Place Ind | No |
Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
Investigation Status Details | A review of the accident determined that there were no control room actions that contributed to the event. |
Employee Drug Test Ind | No |
Contractor Drug Test Ind | No |
Cause | Equipment Failure |
Cause Details | Other Equipment Failure |
Eq Failure Type | Other Equipment Failure |
Failure Details | Braided Stainless Steel Hose Failure |
Eq Additional Other Ind | Yes |
Eq Additional Other Details | Routine Wear Led To A Crack In The Internal Liner Of The Braided Hose. |
Preparer Name | T*** N******* |
Preparer Title | Director - Dot Compliance |
Preparer Email | T************@e*************.com |
Preparer Telephone | 713-989-7126 |
Prepared Date | 2025-08-28 00:00:00 |
Authorizer Name | T*** N******* |
Authorizer Telephone | 713-989-7126 |
Authorizer Title | Director - Dot Compliance |
Authorizer Email | T************@e*************.com |
Narrative | On 07/30/25 at approximately 22:37, a pipeline controller received a hi-hi pressure alarm on the maurepas 24-inch line at norco meter station. The line was immediately shut-in and a pipeline tech was dispatched to the site. Once on site, a crude oil release was confirmed coming from a braided stainless steel hose connected to drain from a thermal relief. Approximately 0.36 (15 gallons) barrels of crude oil was released. All free product was cleaned and contaminated soil and rocks were cleaned up. This braided stainless steel hose was replaced with a new hose and the pressure safety valve was checked for proper operation. The line was restarted at 02:28. An investigation determined the cause of the accident was due to equipment failure. The liner inside the braided stainless steel had cracked due to routine wear. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company
All rights reserved. Copyright © by ClearPHMSA