HL incident on 2025-07-02 — TX

Operator
Capturepoint Llc
Cause
Material Failure Of Pipe Or Weld
Commodity
Co2 (Carbon Dioxide)
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$21,000
Incident datetime
2025-07-02 00:00 UTC
Report number
Location
TX
Narrative
On june 2, 2025 at approximately 12:00 p.M. Cdt, a landowner notified austen pitts that there was a leak on the 4.5" texok CO2 pipeline row downstream of mlv8 at mp37.25. Mr. Pitts proceeded to the location to confirm the line failure at approximately 1:00 p.M. Cdt. The failed section of pipeline was isolated and the beaver county, oklahoma sherrif's office was notified of the plan to blowdown the failed section at 1:20 p.M. Cdt on 6/2/25. The planned blowdown was completed at 4:40 p.M. Cdt. Removed 13' of 4.5" pipe on 6/4/25 and welded in-place replacement section of pipe on 6/5/25. The line resumed operations on 6/12/25 at 5:00 p.M. Cdt. There were no injuries reported and no evacuations or public notification was necessary. Metallurgical engineering services, inc. (mes) performed a failure analysis which stated: "based on the comprehensive failure analysis conducted on the subject four-inch nominal pipe, the primary root cause of the failure was identified as weld defects within the circumferential girth weld, which were preferentially corroded from the inner diameter through the weld heat affected zone (haz) until the joint was compromised." based on their failure analysis, mes identified the primary root cause of the failure as, "...Weld defects within the girth weld haz, specifically undercuts, incomplete penetration due to poor alignment, and slag inclusions. These defects led to preferential corrosion attack, exacerbated by the presence of chalcogens, which resulted in the through hole failure. All relevant test outcomes supported these findings, confirming that the failure originated from weld-related issues rather than the base metal composition or mechanical properties."
Detailed record list
Report Received Date
2025-07-02 00:00:00
Iyear
2025
Report Number
20250163
Supplemental Number
41260
Report Type
Supplemental Final
Operator Id
Name
Capturepoint Llc
Operator Street Address
1101 Central Expressway, South Suite 150
Operator City Name
Allen
Operator State Abbreviation
TX
Operator Postal Code
75013
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Co2 (Carbon Dioxide)
Unintentional Release Bbls
34
Intentional Release Bbls
786
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Other
Accident Details
Landowner Reported
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Nrc Rpt Num
Ignite Ind
No
Upstream Action Taken
Valve Closure
Upstream Valve Type Ind
Manual
Downstream Action Taken
Valve Closure
Downstream Valve Type Ind
Manual
Num Pub Evacuated
0
Pipe Fac Name
Texok Co2
Segment Name
Texok Co2 (F2193)
Onshore State Abbreviation
Ok
Onshore Postal Code
73932
Onshore City Name
Not Within A Municipality
Onshore County Name
Beaver
Designated Location
Milepost
Designated Name
Mp37.25
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
96
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Weld, Including Heat-Affected Zone
Pipe Diameter
4.5
Pipe Wall Thickness
0.125
Pipe Smys
42000
Pipe Specification
Api5l X42
Pipe Seam Type
Erw - High Frequency
Pipe Manufacturer
Seah
Pipe Coating Type
Fusion Bonded Epoxy(Fbe)
Coating Applied Ind
No
Weld Subtype
Pipe Girth Weld
Different Girth Weld Ind
No
Installation Year
2015
Manufactured Year
2014
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
Yes
Vegetation Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
1200
Est Cost Prop Damage
21000
Est Cost Emergency
1000
Est Cost Environmental
0
Est Cost Other
1000
Est Cost Other Details
Working With Landowner To Determine Remediation Needed For Landowner's Property.
Prpty
24200
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
1175
Mop Psig
1677
Mop Cfr Section
Subpart E Pressure Test �195.406(A)(3)
Maop Established Date
2015-09-06 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Length Segment Isolated
44880
Internal Inspection Ind
No
Tight Mitered Ind
Yes
Operation Complications Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Pressure and temperature transmitters did not indicate a leak and the controllers did not see any changes in pressure or temperature to indicate a leak.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Material Failure Of Pipe Or Weld
Cause Details
Design-, Construction-, Installation-, Or Fabrication-Related
Field Exam Ind
Yes
Metallurgical Ind
Yes
Failure Type
Design-, Construction-, Installation-, Or Fabrication-Related
Other Factor
Yes
Other Factor Details
Significant Undercuts At The Toe Of Gw, Adjacent To Ds Side Of Weld Cap
Pwf Addl Misalignment Ind
Yes
Pwf Additional Other Ind
Yes
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
Yes
Hydrtst Most Rcnt Year
2015
Hydrtst Most Rcnt Pressure
2170
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Extrnl Cor Galvanic Ind
Yes
Pwf Installation Ind
Yes
Preparer Name
H***** U*****
Preparer Title
Regulatory Consultant
Preparer Email
H************@e*********.com
Preparer Telephone
9364476100
Prepared Date
2025-08-15 00:00:00
Local Contact Name
P*** A*******
Local Contact Email
P********@c******.com
Local Contact Telephone
5012695215
Authorizer Name
T***** C******
Authorizer Telephone
9187280133
Authorizer Title
Director
Authorizer Email
T*******@c**************.com
Narrative
On june 2, 2025 at approximately 12:00 p.M. Cdt, a landowner notified austen pitts that there was a leak on the 4.5" texok CO2 pipeline row downstream of mlv8 at mp37.25. Mr. Pitts proceeded to the location to confirm the line failure at approximately 1:00 p.M. Cdt. The failed section of pipeline was isolated and the beaver county, oklahoma sherrif's office was notified of the plan to blowdown the failed section at 1:20 p.M. Cdt on 6/2/25. The planned blowdown was completed at 4:40 p.M. Cdt. Removed 13' of 4.5" pipe on 6/4/25 and welded in-place replacement section of pipe on 6/5/25. The line resumed operations on 6/12/25 at 5:00 p.M. Cdt. There were no injuries reported and no evacuations or public notification was necessary. Metallurgical engineering services, inc. (mes) performed a failure analysis which stated: "based on the comprehensive failure analysis conducted on the subject four-inch nominal pipe, the primary root cause of the failure was identified as weld defects within the circumferential girth weld, which were preferentially corroded from the inner diameter through the weld heat affected zone (haz) until the joint was compromised." based on their failure analysis, mes identified the primary root cause of the failure as, "...Weld defects within the girth weld haz, specifically undercuts, incomplete penetration due to poor alignment, and slag inclusions. These defects led to preferential corrosion attack, exacerbated by the presence of chalcogens, which resulted in the through hole failure. All relevant test outcomes supported these findings, confirming that the failure originated from weld-related issues rather than the base metal composition or mechanical properties."
Report Received Date 2025-07-02 00:00:00
Iyear 2025
Report Number 20250163
Supplemental Number 41260
Report Type Supplemental Final
Operator Id 39754 PHMSA Enforcement
Name Capturepoint Llc
Operator Street Address 1101 Central Expressway, South Suite 150
Operator City Name Allen
Operator State Abbreviation TX
Operator Postal Code 75013
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 36.764489 Google Maps OpenStreetMap
Location Longitude -100.590862 Google Maps OpenStreetMap
Commodity Released Type Co2 (Carbon Dioxide)
Unintentional Release Bbls 34
Intentional Release Bbls 786
Recovered Bbls 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Other
Accident Details Landowner Reported
System Part Involved Onshore Pipeline, Including Valve Sites
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind Yes
Communication State Fed Ind Yes
Party Initiated Communication Operator
Nrc Rpt Num 1432910 NRC Report How to search
Ignite Ind No
Upstream Action Taken Valve Closure
Upstream Valve Type Ind Manual
Downstream Action Taken Valve Closure
Downstream Valve Type Ind Manual
Num Pub Evacuated 0
Pipe Fac Name Texok Co2
Segment Name Texok Co2 (F2193)
Onshore State Abbreviation Ok
Onshore Postal Code 73932
Onshore City Name Not Within A Municipality
Onshore County Name Beaver
Designated Location Milepost
Designated Name Mp37.25
Federal No
Location Type Pipeline Right-Of-Way
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover 96
Crossing No
Pipe Facility Type Interstate
Item Involved Weld, Including Heat-Affected Zone
Pipe Diameter 4.5
Pipe Wall Thickness 0.125
Pipe Smys 42000
Pipe Specification Api5l X42
Pipe Seam Type Erw - High Frequency
Pipe Manufacturer Seah
Pipe Coating Type Fusion Bonded Epoxy(Fbe)
Coating Applied Ind No
Weld Subtype Pipe Girth Weld
Different Girth Weld Ind No
Installation Year 2015
Manufactured Year 2014
Material Involved Carbon Steel
Release Type Leak
Leak Type Pinhole
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment No
Remediation Ind Yes
Vegetation Remed Ind Yes
Water Contam Ind No
Could Be Hca No
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 1200
Est Cost Prop Damage 21000
Est Cost Emergency 1000
Est Cost Environmental 0
Est Cost Other 1000
Est Cost Other Details Working With Landowner To Determine Remediation Needed For Landowner's Property.
Prpty 24200
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 1175
Mop Psig 1677
Mop Cfr Section Subpart E Pressure Test �195.406(A)(3) View CFR 49 §192
Maop Established Date 2015-09-06 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Length Segment Isolated 44880
Internal Inspection Ind No
Tight Mitered Ind Yes
Operation Complications Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details Pressure and temperature transmitters did not indicate a leak and the controllers did not see any changes in pressure or temperature to indicate a leak.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Material Failure Of Pipe Or Weld
Cause Details Design-, Construction-, Installation-, Or Fabrication-Related
Field Exam Ind Yes
Metallurgical Ind Yes
Failure Type Design-, Construction-, Installation-, Or Fabrication-Related
Other Factor Yes
Other Factor Details Significant Undercuts At The Toe Of Gw, Adjacent To Ds Side Of Weld Cap
Pwf Addl Misalignment Ind Yes
Pwf Additional Other Ind Yes
Collected Data Ind No
Has Hydrtst Conduc Before Ind Yes
Hydrtst Most Rcnt Year 2015
Hydrtst Most Rcnt Pressure 2170
Direct Asmnt Conducted No
Non Destructive Exam Ind No
Extrnl Cor Galvanic Ind Yes
Pwf Installation Ind Yes
Preparer Name H***** U*****
Preparer Title Regulatory Consultant
Preparer Email H************@e*********.com
Preparer Telephone 9364476100
Prepared Date 2025-08-15 00:00:00
Local Contact Name P*** A*******
Local Contact Email P********@c******.com
Local Contact Telephone 5012695215
Authorizer Name T***** C******
Authorizer Telephone 9187280133
Authorizer Title Director
Authorizer Email T*******@c**************.com
Narrative On june 2, 2025 at approximately 12:00 p.M. Cdt, a landowner notified austen pitts that there was a leak on the 4.5" texok CO2 pipeline row downstream of mlv8 at mp37.25. Mr. Pitts proceeded to the location to confirm the line failure at approximately 1:00 p.M. Cdt. The failed section of pipeline was isolated and the beaver county, oklahoma sherrif's office was notified of the plan to blowdown the failed section at 1:20 p.M. Cdt on 6/2/25. The planned blowdown was completed at 4:40 p.M. Cdt. Removed 13' of 4.5" pipe on 6/4/25 and welded in-place replacement section of pipe on 6/5/25. The line resumed operations on 6/12/25 at 5:00 p.M. Cdt. There were no injuries reported and no evacuations or public notification was necessary. Metallurgical engineering services, inc. (mes) performed a failure analysis which stated: "based on the comprehensive failure analysis conducted on the subject four-inch nominal pipe, the primary root cause of the failure was identified as weld defects within the circumferential girth weld, which were preferentially corroded from the inner diameter through the weld heat affected zone (haz) until the joint was compromised." based on their failure analysis, mes identified the primary root cause of the failure as, "...Weld defects within the girth weld haz, specifically undercuts, incomplete penetration due to poor alignment, and slag inclusions. These defects led to preferential corrosion attack, exacerbated by the presence of chalcogens, which resulted in the through hole failure. All relevant test outcomes supported these findings, confirming that the failure originated from weld-related issues rather than the base metal composition or mechanical properties."