Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2025-06-26 — OK
Operator
Magellan Pipeline Company, Lp
Cause
Incorrect Operation
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$322
Incident datetime
2025-06-26 00:00 UTC
Report number
Location
OK
Narrative
On 6/4/25 a local operator was making valve line ups and smelled diesel fuel and noticed a sheen on top of a puddle of water due to recent rains located underneath a manifold. All operations were suspended, and investigation began. It was determined that the bleeder valve was not closed when the valve was last opened on 6/2/25. Sump alarms were received initially on 6/2/25 and local personnel were able to identify the open valve and were able to shut it but were unable to identify any sheen due to constant rain for the next 48 hours. Operations found that when the pump was operating the product traveled down the bleeder valve line to the sump line. The pressure from the product began to back up to the sump line due to the high flow. The product then back fed up each drain line into the sight glasses finding a weak gasket on the sight glass causing a release. To ensure this was in fact the cause of the release local personnel recreated the scenario to find the leak. The broken sight glass was removed and replaced with a new one.
Detailed record list
Report Received Date
2025-06-26 00:00:00
Iyear
2025
Report Number
20250156
Supplemental Number
41185
Report Type
Supplemental Final
Operator Id
22610
Name
Magellan Pipeline Company, Lp
Operator Street Address
100 West 5th Street
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74103
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
39.140135
Location Longitude
-94.601424
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Diesel, Fuel Oil, Kerosene, Jet Fuel
Unintentional Release Bbls
0.75
Recovered Bbls
0.75
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Oil Spill Removal Org Ind
Yes
Osro Arrived On Site Dt
6/4/2025 12:45
Num Pub Evacuated
0
Pipe Fac Name
Kansas City
Segment Name
Fac Id 200
Onshore State Abbreviation
Ks
Onshore Postal Code
66115
Onshore City Name
Kansas City
Onshore County Name
Wyandotte
Designated Location
Milepost
Designated Name
0
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Drain Lines
Installation Year
1931
Manufactured Year
2012
Material Involved
Material Other Than Carbon Steel
Material Details
Sight Glass Gasket
Release Type
Leak
Leak Type
Other
Leak Type Other
Sight Glass Gasket
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
Yes
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
120
Est Cost Prop Damage
322
Est Cost Emergency
10000
Est Cost Environmental
10000
Est Cost Other
0
Prpty
20442
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
130
Mop Psig
275
Mop Cfr Section
Other
Mop Cfr Section Details
Ansi Class
Maop Established Date
1931-01-01 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
No controllers actions had taken place prior to the release
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Incorrect Operation
Cause Details
Valve Left Or Placed In Wrong Position, But Not Resulting In A Tank, Vessel, Or Sump/separator Overflow Or Facility Overpressure
Operation Type
Valve Left Or Placed In Wrong Position, But Not Resulting In A Tank, Vessel, Or Sump/separator Overflow Or Facility Overpressure
Related Failure Follow Ind
Yes
Category Type
Normal Operating Conditions
Operator Qualification Ind
Yes
Qualified Individuals
Yes, They Were Qualified For The Task(S)
Preparer Name
G*** C*********
Preparer Title
Regulatory Compliance Specialist Ii
Preparer Email
G**************@o****.com
Preparer Telephone
9183818066
Prepared Date
2025-07-29 00:00:00
Authorizer Name
R*** M****
Authorizer Telephone
5807410185
Authorizer Title
Regulatory Compliance Manager
Authorizer Email
R*********@o****.com
Narrative
On 6/4/25 a local operator was making valve line ups and smelled diesel fuel and noticed a sheen on top of a puddle of water due to recent rains located underneath a manifold. All operations were suspended, and investigation began. It was determined that the bleeder valve was not closed when the valve was last opened on 6/2/25. Sump alarms were received initially on 6/2/25 and local personnel were able to identify the open valve and were able to shut it but were unable to identify any sheen due to constant rain for the next 48 hours. Operations found that when the pump was operating the product traveled down the bleeder valve line to the sump line. The pressure from the product began to back up to the sump line due to the high flow. The product then back fed up each drain line into the sight glasses finding a weak gasket on the sight glass causing a release. To ensure this was in fact the cause of the release local personnel recreated the scenario to find the leak. The broken sight glass was removed and replaced with a new one.
Report Received Date | 2025-06-26 00:00:00 |
---|---|
Iyear | 2025 |
Report Number | 20250156 |
Supplemental Number | 41185 |
Report Type | Supplemental Final |
Operator Id | 22610 PHMSA Enforcement |
Name | Magellan Pipeline Company, Lp |
Operator Street Address | 100 West 5th Street |
Operator City Name | Tulsa |
Operator State Abbreviation | OK |
Operator Postal Code | 74103 |
Time Zone | Central |
Daylight Savings Ind | Yes |
Location Latitude | 39.140135 Google Maps OpenStreetMap |
Location Longitude | -94.601424 Google Maps OpenStreetMap |
Commodity Released Type | Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions |
Commodity Subtype | Diesel, Fuel Oil, Kerosene, Jet Fuel |
Unintentional Release Bbls | 0.75 |
Recovered Bbls | 0.75 |
Fatality Ind | No |
Fatal | 0 |
Injury Ind | No |
Injure | 0 |
Accident Identifier | Local Operating Personnel, Including Contractors |
Operator Type | Operator Employee |
System Part Involved | Onshore Pump/meter Station Equipment And Piping |
On Off Shore | Onshore |
Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
Shutdown Due Accident Ind | Yes |
Communication State Fed Ind | Yes |
Party Initiated Communication | Operator |
Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
Ignite Ind | No |
Notify Qualified Indiv Ind | Yes |
Oil Spill Removal Org Ind | Yes |
Osro Arrived On Site Dt | 6/4/2025 12:45 |
Num Pub Evacuated | 0 |
Pipe Fac Name | Kansas City |
Segment Name | Fac Id 200 |
Onshore State Abbreviation | Ks |
Onshore Postal Code | 66115 |
Onshore City Name | Kansas City |
Onshore County Name | Wyandotte |
Designated Location | Milepost |
Designated Name | 0 |
Federal | No |
Location Type | Totally Contained On Operator-Controlled Property |
Incident Area Type | Aboveground |
Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
Crossing | No |
Pipe Facility Type | Interstate |
Item Involved | Drain Lines |
Installation Year | 1931 |
Manufactured Year | 2012 |
Material Involved | Material Other Than Carbon Steel |
Material Details | Sight Glass Gasket |
Release Type | Leak |
Leak Type | Other |
Leak Type Other | Sight Glass Gasket |
Wildlife Impact Ind | No |
Soil Contamination | Yes |
Long Term Assessment | Yes |
Remediation Ind | Yes |
Soil Remed Ind | Yes |
Water Contam Ind | No |
Could Be Hca | Yes |
Commodity Reached Hca | Yes |
High Pop Ind | Yes |
High Pop Yes No | Yes |
Est Cost Oper Paid | 0 |
Est Cost Gas Released | 120 |
Est Cost Prop Damage | 322 |
Est Cost Emergency | 10000 |
Est Cost Environmental | 10000 |
Est Cost Other | 0 |
Prpty | 20442 |
Num Persons Hosp Not Ovnght | 0 |
Num Injured Treated By Emt | 0 |
Num Resident Building Affctd | 0 |
Num Business Building Affctd | 0 |
Accident Psig | 130 |
Mop Psig | 275 |
Mop Cfr Section | Other View CFR 49 §192 |
Mop Cfr Section Details | Ansi Class |
Maop Established Date | 1931-01-01 00:00:00 |
Maop Reversal Flow Ind | No |
Accident Pressure | Pressure Did Not Exceed Mop |
Pressure Restriction Ind | No |
Pipeline Function | > 20% Smys Regulated Transmission |
Scada In Place Ind | Yes |
Scada Operating Ind | Yes |
Scada Functional Ind | Yes |
Scada Detection Ind | No |
Scada Conf Ind | No |
Cpm In Place Ind | Yes |
Cpm Operating Ind | Yes |
Cpm Functional Ind | Yes |
Cpm Detection Ind | No |
Cpm Conf Ind | No |
Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
Investigation Status Details | No controllers actions had taken place prior to the release |
Employee Drug Test Ind | No |
Contractor Drug Test Ind | No |
Cause | Incorrect Operation |
Cause Details | Valve Left Or Placed In Wrong Position, But Not Resulting In A Tank, Vessel, Or Sump/separator Overflow Or Facility Overpressure |
Operation Type | Valve Left Or Placed In Wrong Position, But Not Resulting In A Tank, Vessel, Or Sump/separator Overflow Or Facility Overpressure |
Related Failure Follow Ind | Yes |
Category Type | Normal Operating Conditions |
Operator Qualification Ind | Yes |
Qualified Individuals | Yes, They Were Qualified For The Task(S) |
Preparer Name | G*** C********* |
Preparer Title | Regulatory Compliance Specialist Ii |
Preparer Email | G**************@o****.com |
Preparer Telephone | 9183818066 |
Prepared Date | 2025-07-29 00:00:00 |
Authorizer Name | R*** M**** |
Authorizer Telephone | 5807410185 |
Authorizer Title | Regulatory Compliance Manager |
Authorizer Email | R*********@o****.com |
Narrative | On 6/4/25 a local operator was making valve line ups and smelled diesel fuel and noticed a sheen on top of a puddle of water due to recent rains located underneath a manifold. All operations were suspended, and investigation began. It was determined that the bleeder valve was not closed when the valve was last opened on 6/2/25. Sump alarms were received initially on 6/2/25 and local personnel were able to identify the open valve and were able to shut it but were unable to identify any sheen due to constant rain for the next 48 hours. Operations found that when the pump was operating the product traveled down the bleeder valve line to the sump line. The pressure from the product began to back up to the sump line due to the high flow. The product then back fed up each drain line into the sight glasses finding a weak gasket on the sight glass causing a release. To ensure this was in fact the cause of the release local personnel recreated the scenario to find the leak. The broken sight glass was removed and replaced with a new one. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company
All rights reserved. Copyright © by ClearPHMSA