Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2025-05-30 — OK
Operator
Oneok Ngl Pipeline, Llc
Cause
Equipment Failure
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$780
Incident datetime
2025-05-30 00:00 UTC
Report number
Location
OK
Narrative
At 4:25am on may 2, 2025, pipeline control received a call from a oneok plant operator indicating a release from a psv on the arbuckle ii prover. At 4:53am a oneok pipeline operator isolated the psv stopping the release. The cause of the psv failure is under investigation supplemental- investigation results indicate the psv released at 1,329 psi. It failed to re-seat due to damage to the stem and sealing surface of the psv and continued to release until manually isolated.
Detailed record list
Report Received Date
2025-05-30 00:00:00
Iyear
2025
Report Number
20250135
Supplemental Number
41093
Report Type
Supplemental Final
Operator Id
32109
Name
Oneok Ngl Pipeline, Llc
Operator Street Address
100 West Fifth Street
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74103
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
36.77511
Location Longitude
-97.76291
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls
306
Intentional Release Bbls
0
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
Able To Isolate The Prover And Manually Block In Psv 1/2 Inch Root Valve
Communication State Fed Ind
No
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Medford Arbuckle 2 Pump Station
Segment Name
Site 799
Onshore State Abbreviation
Ok
Onshore Postal Code
73759
Onshore City Name
Medford
Onshore County Name
Grant
Designated Location
Survey Station No.
Designated Name
0+00
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Relief Line And Relief Equipment
Installation Year
2025
Manufactured Year
2020
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Other
Leak Type Other
1/2 Inch Psv Failure
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
Usa Ecological Ind
Yes
Usa Ecological Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
9180
Est Cost Prop Damage
780
Est Cost Emergency
600
Est Cost Environmental
0
Est Cost Other
0
Prpty
10560
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
1329
Mop Psig
1480
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
2020-03-18 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest Schedule Ind
Yes
Invest No Control Room Ind
Yes
Invest Incorrect Action Ind
Yes
Employee Drug Test Ind
Yes
Contractor Drug Test Ind
No
Num Employees Tested
2
Num Employees Failed
0
Cause
Equipment Failure
Cause Details
Malfunction Of Control/relief Equipment
Eq Failure Type
Malfunction Of Control/relief Equipment
Relief Valve Ind
Yes
Eq Additional Other Ind
Yes
Eq Additional Other Details
Cause Of Psv Release Still Under Investigation
Preparer Name
G*** C*********
Preparer Email
G**************@o****.com
Preparer Telephone
9183818066
Prepared Date
2025-07-01 00:00:00
Local Contact Name
R*** M****
Local Contact Email
R*********@o****.com
Local Contact Telephone
5807410185
Authorizer Name
R*** M****
Authorizer Telephone
9183818066
Authorizer Title
Regulatory Compliance Manager
Authorizer Email
G**************@o****.com
Narrative
At 4:25am on may 2, 2025, pipeline control received a call from a oneok plant operator indicating a release from a psv on the arbuckle ii prover. At 4:53am a oneok pipeline operator isolated the psv stopping the release. The cause of the psv failure is under investigation supplemental- investigation results indicate the psv released at 1,329 psi. It failed to re-seat due to damage to the stem and sealing surface of the psv and continued to release until manually isolated.
Report Received Date | 2025-05-30 00:00:00 |
---|---|
Iyear | 2025 |
Report Number | 20250135 |
Supplemental Number | 41093 |
Report Type | Supplemental Final |
Operator Id | 32109 PHMSA Enforcement |
Name | Oneok Ngl Pipeline, Llc |
Operator Street Address | 100 West Fifth Street |
Operator City Name | Tulsa |
Operator State Abbreviation | OK |
Operator Postal Code | 74103 |
Time Zone | Central |
Daylight Savings Ind | Yes |
Location Latitude | 36.77511 Google Maps OpenStreetMap |
Location Longitude | -97.76291 Google Maps OpenStreetMap |
Commodity Released Type | Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions |
Commodity Subtype | Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid) |
Unintentional Release Bbls | 306 |
Intentional Release Bbls | 0 |
Recovered Bbls | 0 |
Fatality Ind | No |
Fatal | 0 |
Injury Ind | No |
Injure | 0 |
Accident Identifier | Local Operating Personnel, Including Contractors |
Operator Type | Operator Employee |
System Part Involved | Onshore Pump/meter Station Equipment And Piping |
On Off Shore | Onshore |
Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
Shutdown Due Accident Ind | No |
Shutdown Explain | Able To Isolate The Prover And Manually Block In Psv 1/2 Inch Root Valve |
Communication State Fed Ind | No |
Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
Ignite Ind | No |
Num Pub Evacuated | 0 |
Pipe Fac Name | Medford Arbuckle 2 Pump Station |
Segment Name | Site 799 |
Onshore State Abbreviation | Ok |
Onshore Postal Code | 73759 |
Onshore City Name | Medford |
Onshore County Name | Grant |
Designated Location | Survey Station No. |
Designated Name | 0+00 |
Federal | No |
Location Type | Totally Contained On Operator-Controlled Property |
Incident Area Type | Aboveground |
Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
Crossing | No |
Pipe Facility Type | Interstate |
Item Involved | Relief Line And Relief Equipment |
Installation Year | 2025 |
Manufactured Year | 2020 |
Material Involved | Carbon Steel |
Release Type | Leak |
Leak Type | Other |
Leak Type Other | 1/2 Inch Psv Failure |
Wildlife Impact Ind | No |
Soil Contamination | No |
Long Term Assessment | No |
Remediation Ind | No |
Water Contam Ind | No |
Could Be Hca | Yes |
Commodity Reached Hca | Yes |
Usa Ecological Ind | Yes |
Usa Ecological Yes No | Yes |
Est Cost Oper Paid | 0 |
Est Cost Gas Released | 9180 |
Est Cost Prop Damage | 780 |
Est Cost Emergency | 600 |
Est Cost Environmental | 0 |
Est Cost Other | 0 |
Prpty | 10560 |
Num Persons Hosp Not Ovnght | 0 |
Num Injured Treated By Emt | 0 |
Num Resident Building Affctd | 0 |
Num Business Building Affctd | 0 |
Accident Psig | 1329 |
Mop Psig | 1480 |
Mop Cfr Section | Component Design Pressure �195.406(A)(2) View CFR 49 §192 |
Maop Established Date | 2020-03-18 00:00:00 |
Maop Reversal Flow Ind | No |
Accident Pressure | Pressure Did Not Exceed Mop |
Pressure Restriction Ind | No |
Pipeline Function | > 20% Smys Regulated Transmission |
Scada In Place Ind | Yes |
Scada Operating Ind | Yes |
Scada Functional Ind | Yes |
Scada Detection Ind | No |
Scada Conf Ind | No |
Cpm In Place Ind | Yes |
Cpm Operating Ind | Yes |
Cpm Functional Ind | Yes |
Cpm Detection Ind | No |
Cpm Conf Ind | No |
Investigation Status | Yes, specify investigation result(s): (select all that apply) |
Invest Schedule Ind | Yes |
Invest No Control Room Ind | Yes |
Invest Incorrect Action Ind | Yes |
Employee Drug Test Ind | Yes |
Contractor Drug Test Ind | No |
Num Employees Tested | 2 |
Num Employees Failed | 0 |
Cause | Equipment Failure |
Cause Details | Malfunction Of Control/relief Equipment |
Eq Failure Type | Malfunction Of Control/relief Equipment |
Relief Valve Ind | Yes |
Eq Additional Other Ind | Yes |
Eq Additional Other Details | Cause Of Psv Release Still Under Investigation |
Preparer Name | G*** C********* |
Preparer Email | G**************@o****.com |
Preparer Telephone | 9183818066 |
Prepared Date | 2025-07-01 00:00:00 |
Local Contact Name | R*** M**** |
Local Contact Email | R*********@o****.com |
Local Contact Telephone | 5807410185 |
Authorizer Name | R*** M**** |
Authorizer Telephone | 9183818066 |
Authorizer Title | Regulatory Compliance Manager |
Authorizer Email | G**************@o****.com |
Narrative | At 4:25am on may 2, 2025, pipeline control received a call from a oneok plant operator indicating a release from a psv on the arbuckle ii prover. At 4:53am a oneok pipeline operator isolated the psv stopping the release. The cause of the psv failure is under investigation supplemental- investigation results indicate the psv released at 1,329 psi. It failed to re-seat due to damage to the stem and sealing surface of the psv and continued to release until manually isolated. |