Incident details
Operator, cause, commodity and consequences with raw source fields.
GTG incident on 2025-11-01 — TX
Operator
El Paso Natural Gas Co
Cause
Other Incident Cause
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$100
Incident datetime
2025-11-01 21:00
Report number
Location
TX
Narrative
At approximately 21:00 on 11/01/2025, williams station b plant initiated an esd due to a faulted processor on the safety plc. Due to mainline pressure venting for approximately 56 minutes, prior to technicians arriving on-site and manually closing valves, the result was a release of 3924 mcf of natural gas meeting regulatory reporting criteria. The esd system did not function as intended. It took one hour for technicians to reset the faulted safety plc and make station available to gas control. Preliminary indications were a battery charger failed. Further investigation concluded the primary cause of the esd was the fault on the safety plc processor. A contributing factor was both the suction and discharge valve power gas pilot valves were in the closed position not allowing the valves to close. No emergency responders were involved. No customers were affected. The arizona corporation commission made an announced visit to flagstaff area office and williams station on 11/3/2025 to investigate the event.
Detailed record list
Report Received Date
2025-11-26 00:00:00
Iyear
2025
Report Number
20250133
Supplemental Number
41631
Report Type
Original Final
Operator Id
4280
Name
El Paso Natural Gas Co
Operator Street Address
1001 Louisiana St, Ste 1000
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002-5089
Local Datetime
2025-11-01 21:00:00
Time Zone
Mountain
Daylight Savings Ind
Yes
Location Latitude
35.30608746
Location Longitude
-112.0602879
Nrc Rpt Num
1446880
Nrc Rpt Datetime
2025-11-01 21:45:00
Additional Nrc Report Numbers
1446923
Commodity Released Type
Natural Gas
Unintentional Release
3924
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2025-11-01 21:56:00
Restart Datetime
2025-11-01 21:56:00
Communication State Fed Ind
No
Ignite Ind
No
Num Pub Evacuated
0
Incident Identified Datetime
2025-11-01 21:00:00
On Site Datetime
2025-11-01 21:56:00
Confirmed Discovery Datetime
2025-11-01 21:00:00
On Off Shore
Onshore
Onshore State Abbreviation
Az
Onshore Postal Code
86001
Onshore City Name
Coconino
Onshore County Name
Coconino
Designated Location
Not Applicable
Pipe Fac Name
Williams Station
Segment Name
B Plant
Federal
No
Location Type
Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
System Part Involved
Onshore Compressor Station Equipment And Piping
Item Involved
Esd System, But Excluding Product Drain Lines And Tubing
Installation Year
Unknown
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Other
Release Type Details
Release Due To Esd Of Williams B Plant
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
682
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
13734
Est Cost Intentional Release
0
Est Cost Prop Damage
100
Est Cost Emergency
100
Est Cost Other
0
Gas Cost In Mcf
3.5
Prpty
13934
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
716
Gas Flow In Pipe In Mcf
102729
Mop Psig
845
Mop Cfr Section
192.619(A)(2)
Maop Established Date
1951-07-01 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Battery charger failure.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Incident Cause
Cause Details
Miscellaneous
Other Type
Miscellaneous
Misc Details
Failure Of Instrumentation / Logic / Loop
Preparer Name
R***** B***** I*
Preparer Email
R************@k***********.com
Preparer Telephone
7134202324
Authorizer Name
Z*** R*****
Authorizer Telephone
7134202609
Authorizer Email
Z**********@k***********.com
Narrative
At approximately 21:00 on 11/01/2025, williams station b plant initiated an esd due to a faulted processor on the safety plc. Due to mainline pressure venting for approximately 56 minutes, prior to technicians arriving on-site and manually closing valves, the result was a release of 3924 mcf of natural gas meeting regulatory reporting criteria. The esd system did not function as intended. It took one hour for technicians to reset the faulted safety plc and make station available to gas control. Preliminary indications were a battery charger failed. Further investigation concluded the primary cause of the esd was the fault on the safety plc processor. A contributing factor was both the suction and discharge valve power gas pilot valves were in the closed position not allowing the valves to close. No emergency responders were involved. No customers were affected. The arizona corporation commission made an announced visit to flagstaff area office and williams station on 11/3/2025 to investigate the event.
| Report Received Date | 2025-11-26 00:00:00 |
|---|---|
| Iyear | 2025 |
| Report Number | 20250133 |
| Supplemental Number | 41631 |
| Report Type | Original Final |
| Operator Id | 4280 PHMSA Enforcement |
| Name | El Paso Natural Gas Co |
| Operator Street Address | 1001 Louisiana St, Ste 1000 |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77002-5089 |
| Local Datetime | 2025-11-01 21:00:00 |
| Time Zone | Mountain |
| Daylight Savings Ind | Yes |
| Location Latitude | 35.30608746 Google Maps OpenStreetMap |
| Location Longitude | -112.0602879 Google Maps OpenStreetMap |
| Nrc Rpt Num | 1446880 NRC Report How to search |
| Nrc Rpt Datetime | 2025-11-01 21:45:00 |
| Additional Nrc Report Numbers | 1446923 |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 3924 |
| Intentional Release | 0 |
| Accompanying Liquid | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Status When Identified | Normal Operation, Includes Pauses During Maintenance |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2025-11-01 21:56:00 |
| Restart Datetime | 2025-11-01 21:56:00 |
| Communication State Fed Ind | No |
| Ignite Ind | No |
| Num Pub Evacuated | 0 |
| Incident Identified Datetime | 2025-11-01 21:00:00 |
| On Site Datetime | 2025-11-01 21:56:00 |
| Confirmed Discovery Datetime | 2025-11-01 21:00:00 |
| On Off Shore | Onshore |
| Onshore State Abbreviation | Az |
| Onshore Postal Code | 86001 |
| Onshore City Name | Coconino |
| Onshore County Name | Coconino |
| Designated Location | Not Applicable |
| Pipe Fac Name | Williams Station |
| Segment Name | B Plant |
| Federal | No |
| Location Type | Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Interstate |
| System Part Involved | Onshore Compressor Station Equipment And Piping |
| Item Involved | Esd System, But Excluding Product Drain Lines And Tubing |
| Installation Year | Unknown |
| Manufactured Year | Unknown |
| Material Involved | Carbon Steel |
| Release Type | Other |
| Release Type Details | Release Due To Esd Of Williams B Plant |
| Class Location Type | Class 1 Location |
| Could Be Hca | No |
| Pir Radius | 682 |
| Heat Damage Ind | No |
| Non Heat Damage Ind | No |
| Did Occur In Mca Ind | No |
| Est Cost Oper Paid | 0 |
| Est Cost Unintentional Release | 13734 |
| Est Cost Intentional Release | 0 |
| Est Cost Prop Damage | 100 |
| Est Cost Emergency | 100 |
| Est Cost Other | 0 |
| Gas Cost In Mcf | 3.5 |
| Prpty | 13934 |
| Num Persons Hosp Not Ovnght | 0 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 0 |
| Num Business Building Affctd | 0 |
| Wildlife Impact Ind | No |
| Accident Psig | 716 |
| Gas Flow In Pipe In Mcf | 102729 |
| Mop Psig | 845 |
| Mop Cfr Section | 192.619(A)(2) View CFR 49 §192 |
| Maop Established Date | 1951-07-01 00:00:00 |
| Maop Reversal Flow Ind | No |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Pressure Restriction Ind | No |
| Gas Required Odorized Ind | No |
| Pipeline Function | Transmission System |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | Yes |
| Scada Conf Ind | Yes |
| Accident Identifier | Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations) |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Battery charger failure. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Other Incident Cause |
| Cause Details | Miscellaneous |
| Other Type | Miscellaneous |
| Misc Details | Failure Of Instrumentation / Logic / Loop |
| Preparer Name | R***** B***** I* |
| Preparer Email | R************@k***********.com |
| Preparer Telephone | 7134202324 |
| Authorizer Name | Z*** R***** |
| Authorizer Telephone | 7134202609 |
| Authorizer Email | Z**********@k***********.com |
| Narrative | At approximately 21:00 on 11/01/2025, williams station b plant initiated an esd due to a faulted processor on the safety plc. Due to mainline pressure venting for approximately 56 minutes, prior to technicians arriving on-site and manually closing valves, the result was a release of 3924 mcf of natural gas meeting regulatory reporting criteria. The esd system did not function as intended. It took one hour for technicians to reset the faulted safety plc and make station available to gas control. Preliminary indications were a battery charger failed. Further investigation concluded the primary cause of the esd was the fault on the safety plc processor. A contributing factor was both the suction and discharge valve power gas pilot valves were in the closed position not allowing the valves to close. No emergency responders were involved. No customers were affected. The arizona corporation commission made an announced visit to flagstaff area office and williams station on 11/3/2025 to investigate the event. |