GTG incident on 2025-10-14 — TX

Operator
Columbia Gas Transmission, Llc
Cause
Other Incident Cause
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$275,000
Incident datetime
2025-10-14 13:00
Report number
Location
TX
Narrative
Columbia gas transmission llc (columbia), a tc energy entity, operates and maintains forrest hills regulator station located in brooksville, kentucky. On tuesday october 14th, 2025, 3rd party nde technician (contractor), and a columbia m&r technician were hand prepping corroded surface areas of a 1-inch diameter fitting for evaluation. During hand preparation the fitting began leaking. Columbia's area operations manager was contacted and instructed the columbia m&r technician to evacuate the building and leave the doors open for venting. A columbia pipeline technician arrived on site to perform lel readings around the building. After assessing the event, confirming that no gas was being detected beyond the meter building, it was determined that potential impacts to residential life and property did not warrant residential evacuation at the time. The facility was manned around the clock with hourly instrumented leak sweeps from october14th to 19th. The leak was stable with corrective action including implementation of a pressure reduction to 320 psig. The leak source was identified at the side wall of the 1-inch diameter fitting. A root cause investigation is underway. The fitting has been repaired, and the facility was returned to service on october 19th, 2025.
Detailed record list
Report Received Date
2025-11-07 00:00:00
Iyear
2025
Report Number
20250124
Supplemental Number
41564
Report Type
Original
Operator Id
Name
Columbia Gas Transmission, Llc
Operator Street Address
700 Louisiana St. Suite 700
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2025-10-14 13:00:00
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Nrc Rpt Num
Nrc Rpt Datetime
2025-10-15 10:16:00
Additional Nrc Report Numbers
1445666
Commodity Released Type
Natural Gas
Unintentional Release
1435
Intentional Release
1
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
No Safety Concerns Were Identified That Warranted Facility Shut Down.
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2025-10-14 16:10:00
Ignite Ind
No
Num Pub Evacuated
0
Incident Identified Datetime
2025-10-14 13:00:00
On Site Datetime
2025-10-14 13:00:00
Confirmed Discovery Datetime
2025-10-15 10:00:00
On Off Shore
Onshore
Onshore State Abbreviation
Ky
Onshore Postal Code
41004
Onshore City Name
Brooksville
Onshore County Name
Bracken
Designated Location
Not Applicable
Pipe Fac Name
Forrest Hills Regulator Station
Segment Name
Rs-805844
Federal
No
Location Type
Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Inside A Building
Crossing
No
Pipe Facility Type
Interstate
System Part Involved
Onshore Regulator/metering Station Equipment And Piping
Item Involved
Regulator/control Valve
Installation Year
1969
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Class Location Type
Class 2 Location
Could Be Hca
No
Pir Radius
86
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
2454
Est Cost Intentional Release
2
Est Cost Prop Damage
275000
Est Cost Emergency
70000
Est Cost Other
0
Gas Cost In Mcf
1.71
Prpty
347456
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
430
Gas Flow In Pipe In Mcf
2300
Mop Psig
720
Mop Cfr Section
192.619(A)(1)
Maop Established Date
1969-09-22 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Contractor Working For The Operator
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
This was a manual regulator that is not controlled by gas control. The control room did not contribute to the release.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Incident Cause
Cause Details
Unknown
Other Type
Unknown
Unknown Subtype
Still Under Investigation, Cause Of Incident To Be Determined* (*supplemental Report Required)
Preparer Name
B***** H*****
Preparer Title
Compliance Specialist
Preparer Email
B*********@t*******.com
Preparer Telephone
304.539.9311
Authorizer Name
C*** B*****
Authorizer Title
Manager
Authorizer Telephone
304.541.2170
Authorizer Email
C**********@t*******.com
Narrative
Columbia gas transmission llc (columbia), a tc energy entity, operates and maintains forrest hills regulator station located in brooksville, kentucky. On tuesday october 14th, 2025, 3rd party nde technician (contractor), and a columbia m&r technician were hand prepping corroded surface areas of a 1-inch diameter fitting for evaluation. During hand preparation the fitting began leaking. Columbia's area operations manager was contacted and instructed the columbia m&r technician to evacuate the building and leave the doors open for venting. A columbia pipeline technician arrived on site to perform lel readings around the building. After assessing the event, confirming that no gas was being detected beyond the meter building, it was determined that potential impacts to residential life and property did not warrant residential evacuation at the time. The facility was manned around the clock with hourly instrumented leak sweeps from october14th to 19th. The leak was stable with corrective action including implementation of a pressure reduction to 320 psig. The leak source was identified at the side wall of the 1-inch diameter fitting. A root cause investigation is underway. The fitting has been repaired, and the facility was returned to service on october 19th, 2025.
Report Received Date 2025-11-07 00:00:00
Iyear 2025
Report Number 20250124
Supplemental Number 41564
Report Type Original
Operator Id 2616 PHMSA Enforcement
Name Columbia Gas Transmission, Llc
Operator Street Address 700 Louisiana St. Suite 700
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2025-10-14 13:00:00
Time Zone Eastern
Daylight Savings Ind Yes
Location Latitude 38.69243 Google Maps OpenStreetMap
Location Longitude -84.17288 Google Maps OpenStreetMap
Nrc Rpt Num 1445511 NRC Report How to search
Nrc Rpt Datetime 2025-10-15 10:16:00
Additional Nrc Report Numbers 1445666
Commodity Released Type Natural Gas
Unintentional Release 1435
Intentional Release 1
Accompanying Liquid 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Status When Identified Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind No
Shutdown Explain No Safety Concerns Were Identified That Warranted Facility Shut Down.
Communication State Fed Ind Yes
Party Initiated Communication Operator
Initial Responder Com Datetime 2025-10-14 16:10:00
Ignite Ind No
Num Pub Evacuated 0
Incident Identified Datetime 2025-10-14 13:00:00
On Site Datetime 2025-10-14 13:00:00
Confirmed Discovery Datetime 2025-10-15 10:00:00
On Off Shore Onshore
Onshore State Abbreviation Ky
Onshore Postal Code 41004
Onshore City Name Brooksville
Onshore County Name Bracken
Designated Location Not Applicable
Pipe Fac Name Forrest Hills Regulator Station
Segment Name Rs-805844
Federal No
Location Type Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Inside A Building
Crossing No
Pipe Facility Type Interstate
System Part Involved Onshore Regulator/metering Station Equipment And Piping
Item Involved Regulator/control Valve
Installation Year 1969
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Leak
Leak Type Pinhole
Class Location Type Class 2 Location
Could Be Hca No
Pir Radius 86
Heat Damage Ind No
Non Heat Damage Ind No
Did Occur In Mca Ind No
Est Cost Oper Paid 0
Est Cost Unintentional Release 2454
Est Cost Intentional Release 2
Est Cost Prop Damage 275000
Est Cost Emergency 70000
Est Cost Other 0
Gas Cost In Mcf 1.71
Prpty 347456
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Wildlife Impact Ind No
Accident Psig 430
Gas Flow In Pipe In Mcf 2300
Mop Psig 720
Mop Cfr Section 192.619(A)(1) View CFR 49 §192
Maop Established Date 1969-09-22 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Maop
Pressure Restriction Ind No
Gas Required Odorized Ind No
Pipeline Function Transmission System
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Contractor Working For The Operator
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details This was a manual regulator that is not controlled by gas control. The control room did not contribute to the release.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Other Incident Cause
Cause Details Unknown
Other Type Unknown
Unknown Subtype Still Under Investigation, Cause Of Incident To Be Determined* (*supplemental Report Required)
Preparer Name B***** H*****
Preparer Title Compliance Specialist
Preparer Email B*********@t*******.com
Preparer Telephone 304.539.9311
Authorizer Name C*** B*****
Authorizer Title Manager
Authorizer Telephone 304.541.2170
Authorizer Email C**********@t*******.com
Narrative Columbia gas transmission llc (columbia), a tc energy entity, operates and maintains forrest hills regulator station located in brooksville, kentucky. On tuesday october 14th, 2025, 3rd party nde technician (contractor), and a columbia m&r technician were hand prepping corroded surface areas of a 1-inch diameter fitting for evaluation. During hand preparation the fitting began leaking. Columbia's area operations manager was contacted and instructed the columbia m&r technician to evacuate the building and leave the doors open for venting. A columbia pipeline technician arrived on site to perform lel readings around the building. After assessing the event, confirming that no gas was being detected beyond the meter building, it was determined that potential impacts to residential life and property did not warrant residential evacuation at the time. The facility was manned around the clock with hourly instrumented leak sweeps from october14th to 19th. The leak was stable with corrective action including implementation of a pressure reduction to 320 psig. The leak source was identified at the side wall of the 1-inch diameter fitting. A root cause investigation is underway. The fitting has been repaired, and the facility was returned to service on october 19th, 2025.

All rights reserved. Copyright © by ClearPHMSA