GTG incident on 2025-09-12 — CO

Operator
Rockies Express Pipeline Llc
Cause
Equipment Failure
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$220
Incident datetime
2025-09-12 17:53
Report number
Location
CO
Narrative
At 16:31 on 9/12/2025 psv-5201, a discharge over-pressure relief valve on unit 5200 at seneca compressor station began to vent gas below the desired activation setpoint. This activation was due to a pipe nipple failure on the field test port. The scada system alerted occ and the mechanic on call for the station when it detected hi gas levels in the compressor building. The mechanic on call received the alarms and began driving to seneca station. While the mechanic was on the way the operations team asked occ to issue a remote stop command to the two units running at the station, unit 5100 and 5200. This command stopped the unit and commanded the suction and discharge valves closed, stopping the flow of gas to the psv. When the mechanic arrived on site, he discovered the broken pipe nipple and removed the assembly and replaced it with a plug. The unit was then checked and made available for service.
Detailed record list
Report Received Date
2025-10-10 00:00:00
Iyear
2025
Report Number
20250112
Supplemental Number
41450
Report Type
Original Final
Operator Id
Name
Rockies Express Pipeline Llc
Operator Street Address
370 Van Gordon St
Operator City Name
Lakewood
Operator State Abbreviation
CO
Operator Postal Code
80228
Local Datetime
2025-09-12 16:39:00
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Nrc Rpt Num
Nrc Rpt Datetime
2025-09-12 22:41:00
Additional Nrc Report Numbers
1442732
Commodity Released Type
Natural Gas
Unintentional Release
3100
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
Units Shutdown By Occ. Pipeline Continued Operation Bypassing Station..
Communication State Fed Ind
No
Ignite Ind
No
Num Pub Evacuated
0
Incident Identified Datetime
2025-09-12 17:53:00
On Site Datetime
2025-09-12 17:53:00
Confirmed Discovery Datetime
2025-09-12 22:10:00
On Off Shore
Onshore
Onshore State Abbreviation
Oh
Onshore Postal Code
43773
Onshore City Name
Quaker City
Onshore County Name
Noble
Designated Location
Not Applicable
Pipe Fac Name
Rockies Express Pipeline
Segment Name
Seneca Compressor Station
Federal
No
Location Type
Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Inside A Building
Crossing
No
Pipe Facility Type
Interstate
System Part Involved
Onshore Compressor Station Equipment And Piping
Item Involved
Compressor
Installation Year
2014
Manufactured Year
2014
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Crack
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
686
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
Yes
Mca Buildng Human Occupy Ind
Yes
Mca Paved Surface Freeway Ind
Yes
Est Cost Oper Paid
0
Est Cost Unintentional Release
5518
Est Cost Intentional Release
0
Est Cost Prop Damage
220
Est Cost Emergency
0
Est Cost Other
0
Gas Cost In Mcf
1.78
Prpty
5738
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
1260
Gas Flow In Pipe In Mcf
120000
Mop Psig
1480
Mop Cfr Section
192.619(A)(1)
Maop Established Date
2014-08-26 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Threaded Connection/coupling Failure
Eq Failure Type
Threaded Connection/coupling Failure
Other Stripped Ind
Pipe Nipple
Eq Additional Other Ind
Yes
Eq Additional Other Details
Improper Design
Preparer Name
S****** H*****
Preparer Title
Sr. Compliance Coordinator
Preparer Email
S*************@t********.com
Preparer Telephone
2814354951
Authorizer Name
D******* S*******
Authorizer Title
Director Phmsa Compliance
Authorizer Telephone
713-725-0147
Authorizer Email
D****************@t********.com
Narrative
At 16:31 on 9/12/2025 psv-5201, a discharge over-pressure relief valve on unit 5200 at seneca compressor station began to vent gas below the desired activation setpoint. This activation was due to a pipe nipple failure on the field test port. The scada system alerted occ and the mechanic on call for the station when it detected hi gas levels in the compressor building. The mechanic on call received the alarms and began driving to seneca station. While the mechanic was on the way the operations team asked occ to issue a remote stop command to the two units running at the station, unit 5100 and 5200. This command stopped the unit and commanded the suction and discharge valves closed, stopping the flow of gas to the psv. When the mechanic arrived on site, he discovered the broken pipe nipple and removed the assembly and replaced it with a plug. The unit was then checked and made available for service.
Report Received Date 2025-10-10 00:00:00
Iyear 2025
Report Number 20250112
Supplemental Number 41450
Report Type Original Final
Operator Id 32163 PHMSA Enforcement
Name Rockies Express Pipeline Llc
Operator Street Address 370 Van Gordon St
Operator City Name Lakewood
Operator State Abbreviation CO
Operator Postal Code 80228
Local Datetime 2025-09-12 16:39:00
Time Zone Eastern
Daylight Savings Ind Yes
Location Latitude 39.92978 Google Maps OpenStreetMap
Location Longitude -81.25021 Google Maps OpenStreetMap
Nrc Rpt Num 1442614 NRC Report How to search
Nrc Rpt Datetime 2025-09-12 22:41:00
Additional Nrc Report Numbers 1442732
Commodity Released Type Natural Gas
Unintentional Release 3100
Intentional Release 0
Accompanying Liquid 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Status When Identified Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind No
Shutdown Explain Units Shutdown By Occ. Pipeline Continued Operation Bypassing Station..
Communication State Fed Ind No
Ignite Ind No
Num Pub Evacuated 0
Incident Identified Datetime 2025-09-12 17:53:00
On Site Datetime 2025-09-12 17:53:00
Confirmed Discovery Datetime 2025-09-12 22:10:00
On Off Shore Onshore
Onshore State Abbreviation Oh
Onshore Postal Code 43773
Onshore City Name Quaker City
Onshore County Name Noble
Designated Location Not Applicable
Pipe Fac Name Rockies Express Pipeline
Segment Name Seneca Compressor Station
Federal No
Location Type Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Inside A Building
Crossing No
Pipe Facility Type Interstate
System Part Involved Onshore Compressor Station Equipment And Piping
Item Involved Compressor
Installation Year 2014
Manufactured Year 2014
Material Involved Carbon Steel
Release Type Leak
Leak Type Crack
Class Location Type Class 1 Location
Could Be Hca No
Pir Radius 686
Heat Damage Ind No
Non Heat Damage Ind No
Did Occur In Mca Ind Yes
Mca Buildng Human Occupy Ind Yes
Mca Paved Surface Freeway Ind Yes
Est Cost Oper Paid 0
Est Cost Unintentional Release 5518
Est Cost Intentional Release 0
Est Cost Prop Damage 220
Est Cost Emergency 0
Est Cost Other 0
Gas Cost In Mcf 1.78
Prpty 5738
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Wildlife Impact Ind No
Accident Psig 1260
Gas Flow In Pipe In Mcf 120000
Mop Psig 1480
Mop Cfr Section 192.619(A)(1) View CFR 49 §192
Maop Established Date 2014-08-26 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Maop
Pressure Restriction Ind No
Gas Required Odorized Ind No
Pipeline Function Transmission System
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind Yes
Accident Identifier Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind Yes
Invest No Controller Ind Yes
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Threaded Connection/coupling Failure
Eq Failure Type Threaded Connection/coupling Failure
Other Stripped Ind Pipe Nipple
Eq Additional Other Ind Yes
Eq Additional Other Details Improper Design
Preparer Name S****** H*****
Preparer Title Sr. Compliance Coordinator
Preparer Email S*************@t********.com
Preparer Telephone 2814354951
Authorizer Name D******* S*******
Authorizer Title Director Phmsa Compliance
Authorizer Telephone 713-725-0147
Authorizer Email D****************@t********.com
Narrative At 16:31 on 9/12/2025 psv-5201, a discharge over-pressure relief valve on unit 5200 at seneca compressor station began to vent gas below the desired activation setpoint. This activation was due to a pipe nipple failure on the field test port. The scada system alerted occ and the mechanic on call for the station when it detected hi gas levels in the compressor building. The mechanic on call received the alarms and began driving to seneca station. While the mechanic was on the way the operations team asked occ to issue a remote stop command to the two units running at the station, unit 5100 and 5200. This command stopped the unit and commanded the suction and discharge valves closed, stopping the flow of gas to the psv. When the mechanic arrived on site, he discovered the broken pipe nipple and removed the assembly and replaced it with a plug. The unit was then checked and made available for service.