Incident details
Operator, cause, commodity and consequences with raw source fields.
GTG incident on 2025-09-12 — CO
Operator
Rockies Express Pipeline Llc
Cause
Equipment Failure
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$220
Incident datetime
2025-09-12 17:53
Report number
Location
CO
Narrative
At 16:31 on 9/12/2025 psv-5201, a discharge over-pressure relief valve on unit 5200 at seneca compressor station began to vent gas below the desired activation setpoint. This activation was due to a pipe nipple failure on the field test port. The scada system alerted occ and the mechanic on call for the station when it detected hi gas levels in the compressor building. The mechanic on call received the alarms and began driving to seneca station. While the mechanic was on the way the operations team asked occ to issue a remote stop command to the two units running at the station, unit 5100 and 5200. This command stopped the unit and commanded the suction and discharge valves closed, stopping the flow of gas to the psv. When the mechanic arrived on site, he discovered the broken pipe nipple and removed the assembly and replaced it with a plug. The unit was then checked and made available for service.
Detailed record list
Report Received Date
2025-10-10 00:00:00
Iyear
2025
Report Number
20250112
Supplemental Number
41450
Report Type
Original Final
Operator Id
32163
Name
Rockies Express Pipeline Llc
Operator Street Address
370 Van Gordon St
Operator City Name
Lakewood
Operator State Abbreviation
CO
Operator Postal Code
80228
Local Datetime
2025-09-12 16:39:00
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Latitude
39.92978
Location Longitude
-81.25021
Nrc Rpt Num
1442614
Nrc Rpt Datetime
2025-09-12 22:41:00
Additional Nrc Report Numbers
1442732
Commodity Released Type
Natural Gas
Unintentional Release
3100
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
Units Shutdown By Occ. Pipeline Continued Operation Bypassing Station..
Communication State Fed Ind
No
Ignite Ind
No
Num Pub Evacuated
0
Incident Identified Datetime
2025-09-12 17:53:00
On Site Datetime
2025-09-12 17:53:00
Confirmed Discovery Datetime
2025-09-12 22:10:00
On Off Shore
Onshore
Onshore State Abbreviation
Oh
Onshore Postal Code
43773
Onshore City Name
Quaker City
Onshore County Name
Noble
Designated Location
Not Applicable
Pipe Fac Name
Rockies Express Pipeline
Segment Name
Seneca Compressor Station
Federal
No
Location Type
Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Inside A Building
Crossing
No
Pipe Facility Type
Interstate
System Part Involved
Onshore Compressor Station Equipment And Piping
Item Involved
Compressor
Installation Year
2014
Manufactured Year
2014
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Crack
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
686
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
Yes
Mca Buildng Human Occupy Ind
Yes
Mca Paved Surface Freeway Ind
Yes
Est Cost Oper Paid
0
Est Cost Unintentional Release
5518
Est Cost Intentional Release
0
Est Cost Prop Damage
220
Est Cost Emergency
0
Est Cost Other
0
Gas Cost In Mcf
1.78
Prpty
5738
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
1260
Gas Flow In Pipe In Mcf
120000
Mop Psig
1480
Mop Cfr Section
192.619(A)(1)
Maop Established Date
2014-08-26 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Threaded Connection/coupling Failure
Eq Failure Type
Threaded Connection/coupling Failure
Other Stripped Ind
Pipe Nipple
Eq Additional Other Ind
Yes
Eq Additional Other Details
Improper Design
Preparer Name
S****** H*****
Preparer Title
Sr. Compliance Coordinator
Preparer Email
S*************@t********.com
Preparer Telephone
2814354951
Authorizer Name
D******* S*******
Authorizer Title
Director Phmsa Compliance
Authorizer Telephone
713-725-0147
Authorizer Email
D****************@t********.com
Narrative
At 16:31 on 9/12/2025 psv-5201, a discharge over-pressure relief valve on unit 5200 at seneca compressor station began to vent gas below the desired activation setpoint. This activation was due to a pipe nipple failure on the field test port. The scada system alerted occ and the mechanic on call for the station when it detected hi gas levels in the compressor building. The mechanic on call received the alarms and began driving to seneca station. While the mechanic was on the way the operations team asked occ to issue a remote stop command to the two units running at the station, unit 5100 and 5200. This command stopped the unit and commanded the suction and discharge valves closed, stopping the flow of gas to the psv. When the mechanic arrived on site, he discovered the broken pipe nipple and removed the assembly and replaced it with a plug. The unit was then checked and made available for service.
| Report Received Date | 2025-10-10 00:00:00 |
|---|---|
| Iyear | 2025 |
| Report Number | 20250112 |
| Supplemental Number | 41450 |
| Report Type | Original Final |
| Operator Id | 32163 PHMSA Enforcement |
| Name | Rockies Express Pipeline Llc |
| Operator Street Address | 370 Van Gordon St |
| Operator City Name | Lakewood |
| Operator State Abbreviation | CO |
| Operator Postal Code | 80228 |
| Local Datetime | 2025-09-12 16:39:00 |
| Time Zone | Eastern |
| Daylight Savings Ind | Yes |
| Location Latitude | 39.92978 Google Maps OpenStreetMap |
| Location Longitude | -81.25021 Google Maps OpenStreetMap |
| Nrc Rpt Num | 1442614 NRC Report How to search |
| Nrc Rpt Datetime | 2025-09-12 22:41:00 |
| Additional Nrc Report Numbers | 1442732 |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 3100 |
| Intentional Release | 0 |
| Accompanying Liquid | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Status When Identified | Normal Operation, Includes Pauses During Maintenance |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | Units Shutdown By Occ. Pipeline Continued Operation Bypassing Station.. |
| Communication State Fed Ind | No |
| Ignite Ind | No |
| Num Pub Evacuated | 0 |
| Incident Identified Datetime | 2025-09-12 17:53:00 |
| On Site Datetime | 2025-09-12 17:53:00 |
| Confirmed Discovery Datetime | 2025-09-12 22:10:00 |
| On Off Shore | Onshore |
| Onshore State Abbreviation | Oh |
| Onshore Postal Code | 43773 |
| Onshore City Name | Quaker City |
| Onshore County Name | Noble |
| Designated Location | Not Applicable |
| Pipe Fac Name | Rockies Express Pipeline |
| Segment Name | Seneca Compressor Station |
| Federal | No |
| Location Type | Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Inside A Building |
| Crossing | No |
| Pipe Facility Type | Interstate |
| System Part Involved | Onshore Compressor Station Equipment And Piping |
| Item Involved | Compressor |
| Installation Year | 2014 |
| Manufactured Year | 2014 |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Crack |
| Class Location Type | Class 1 Location |
| Could Be Hca | No |
| Pir Radius | 686 |
| Heat Damage Ind | No |
| Non Heat Damage Ind | No |
| Did Occur In Mca Ind | Yes |
| Mca Buildng Human Occupy Ind | Yes |
| Mca Paved Surface Freeway Ind | Yes |
| Est Cost Oper Paid | 0 |
| Est Cost Unintentional Release | 5518 |
| Est Cost Intentional Release | 0 |
| Est Cost Prop Damage | 220 |
| Est Cost Emergency | 0 |
| Est Cost Other | 0 |
| Gas Cost In Mcf | 1.78 |
| Prpty | 5738 |
| Num Persons Hosp Not Ovnght | 0 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 0 |
| Num Business Building Affctd | 0 |
| Wildlife Impact Ind | No |
| Accident Psig | 1260 |
| Gas Flow In Pipe In Mcf | 120000 |
| Mop Psig | 1480 |
| Mop Cfr Section | 192.619(A)(1) View CFR 49 §192 |
| Maop Established Date | 2014-08-26 00:00:00 |
| Maop Reversal Flow Ind | No |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Pressure Restriction Ind | No |
| Gas Required Odorized Ind | No |
| Pipeline Function | Transmission System |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | Yes |
| Scada Conf Ind | Yes |
| Accident Identifier | Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations) |
| Investigation Status | Yes, specify investigation result(s): (select all that apply) |
| Invest No Control Room Ind | Yes |
| Invest No Controller Ind | Yes |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Threaded Connection/coupling Failure |
| Eq Failure Type | Threaded Connection/coupling Failure |
| Other Stripped Ind | Pipe Nipple |
| Eq Additional Other Ind | Yes |
| Eq Additional Other Details | Improper Design |
| Preparer Name | S****** H***** |
| Preparer Title | Sr. Compliance Coordinator |
| Preparer Email | S*************@t********.com |
| Preparer Telephone | 2814354951 |
| Authorizer Name | D******* S******* |
| Authorizer Title | Director Phmsa Compliance |
| Authorizer Telephone | 713-725-0147 |
| Authorizer Email | D****************@t********.com |
| Narrative | At 16:31 on 9/12/2025 psv-5201, a discharge over-pressure relief valve on unit 5200 at seneca compressor station began to vent gas below the desired activation setpoint. This activation was due to a pipe nipple failure on the field test port. The scada system alerted occ and the mechanic on call for the station when it detected hi gas levels in the compressor building. The mechanic on call received the alarms and began driving to seneca station. While the mechanic was on the way the operations team asked occ to issue a remote stop command to the two units running at the station, unit 5100 and 5200. This command stopped the unit and commanded the suction and discharge valves closed, stopping the flow of gas to the psv. When the mechanic arrived on site, he discovered the broken pipe nipple and removed the assembly and replaced it with a plug. The unit was then checked and made available for service. |