GTG incident on 2025-08-24 — TX

Operator
Natural Gas Pipeline Co Of America (Kmi)
Cause
Equipment Failure
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$0
Incident datetime
2025-08-24 21:00
Report number
Location
TX
Narrative
On august 24, 2025 at 9:00 pm ngpl staff were performing routine checks before pigging operations and found a 2" vent valve on the compressor fuel supply line was open causing a continuous gas release. They quickly shut off the manual fuel supply valve to stop the leak. 9047 mcf of natural gas was released, there were no injuries or fire, and no emergency services were required. The investigation revealed that a power interruption to the station caused an air compressor to fail. The loss of air pressure caused a 2" vent valve on the compressor fuel supply line to fail-open as designed. The station was set to manual operations at the time which suppressed the alarm to gas control.
Detailed record list
Report Received Date
2025-09-23 00:00:00
Iyear
2025
Report Number
20250107
Supplemental Number
41595
Report Type
Supplemental Final
Operator Id
Name
Natural Gas Pipeline Co Of America (Kmi)
Operator Street Address
1001 Louisiana St, Ste 1000
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2025-08-24 21:00:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
-96.12831089
Nrc Rpt Num
Nrc Rpt Datetime
2025-08-24 21:59:00
Additional Nrc Report Numbers
1440882
Commodity Released Type
Natural Gas
Unintentional Release
9047
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Idle
Communication State Fed Ind
No
Ignite Ind
No
Num Pub Evacuated
0
Incident Identified Datetime
2025-08-24 21:00:00
On Site Datetime
2025-08-24 21:00:00
Confirmed Discovery Datetime
2025-08-24 21:00:00
On Off Shore
Onshore
Onshore State Abbreviation
Tx
Onshore Postal Code
77478
Onshore City Name
Wharton
Onshore County Name
Wharton
Designated Location
Survey Station No.
Designated Name
10329+48
Pipe Fac Name
Compressor Station 301
Segment Name
77488
Federal
No
Location Type
Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
System Part Involved
Onshore Compressor Station Equipment And Piping
Item Involved
Valve
Valve Type
Auxiliary Or Other Valve
Installation Year
2020
Manufactured Year
2020
Material Involved
Carbon Steel
Release Type
Other
Release Type Details
Power Interruption Caused An Air Compressor Failure Which Caused A Vent Valve To Fail Open.
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
660
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
43607
Est Cost Intentional Release
0
Est Cost Prop Damage
0
Est Cost Emergency
0
Est Cost Other
0
Gas Cost In Mcf
4.82
Prpty
43607
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
333
Gas Flow In Pipe In Mcf
0
Mop Psig
858
Mop Cfr Section
192.619(A)(2)
Maop Established Date
2018-10-05 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Incident investigation did not indicate any reason to suspect controller actions may have contributed.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Compressor Or Compressor-Related Equipment
Eq Failure Type
Compressor Or Compressor-Related Equipment
Other Compressor Ind
Appurtenance Failure
Additional Electricity Ind
Yes
Preparer Name
C****** P********
Preparer Title
Manager-Codes And Standards
Preparer Email
C****************@k***********.com
Preparer Telephone
1-713-420-2460
Local Contact Name
S*** K****
Local Contact Email
S*********@k***********.com
Local Contact Telephone
1-979-232-4249
Authorizer Name
Z*** R*****
Authorizer Title
Director - Engineering Codes And Standards
Authorizer Telephone
8329190774
Authorizer Email
Z**********@k***********.com
Narrative
On august 24, 2025 at 9:00 pm ngpl staff were performing routine checks before pigging operations and found a 2" vent valve on the compressor fuel supply line was open causing a continuous gas release. They quickly shut off the manual fuel supply valve to stop the leak. 9047 mcf of natural gas was released, there were no injuries or fire, and no emergency services were required. The investigation revealed that a power interruption to the station caused an air compressor to fail. The loss of air pressure caused a 2" vent valve on the compressor fuel supply line to fail-open as designed. The station was set to manual operations at the time which suppressed the alarm to gas control.
Report Received Date 2025-09-23 00:00:00
Iyear 2025
Report Number 20250107
Supplemental Number 41595
Report Type Supplemental Final
Operator Id 13120 PHMSA Enforcement
Name Natural Gas Pipeline Co Of America (Kmi)
Operator Street Address 1001 Louisiana St, Ste 1000
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2025-08-24 21:00:00
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 29.40649226 Google Maps OpenStreetMap
Location Longitude -96.12831089 Google Maps OpenStreetMap
Nrc Rpt Num 1440731 NRC Report How to search
Nrc Rpt Datetime 2025-08-24 21:59:00
Additional Nrc Report Numbers 1440882
Commodity Released Type Natural Gas
Unintentional Release 9047
Intentional Release 0
Accompanying Liquid 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Status When Identified Idle
Communication State Fed Ind No
Ignite Ind No
Num Pub Evacuated 0
Incident Identified Datetime 2025-08-24 21:00:00
On Site Datetime 2025-08-24 21:00:00
Confirmed Discovery Datetime 2025-08-24 21:00:00
On Off Shore Onshore
Onshore State Abbreviation Tx
Onshore Postal Code 77478
Onshore City Name Wharton
Onshore County Name Wharton
Designated Location Survey Station No.
Designated Name 10329+48
Pipe Fac Name Compressor Station 301
Segment Name 77488
Federal No
Location Type Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
System Part Involved Onshore Compressor Station Equipment And Piping
Item Involved Valve
Valve Type Auxiliary Or Other Valve
Installation Year 2020
Manufactured Year 2020
Material Involved Carbon Steel
Release Type Other
Release Type Details Power Interruption Caused An Air Compressor Failure Which Caused A Vent Valve To Fail Open.
Class Location Type Class 1 Location
Could Be Hca No
Pir Radius 660
Heat Damage Ind No
Non Heat Damage Ind No
Did Occur In Mca Ind No
Est Cost Oper Paid 0
Est Cost Unintentional Release 43607
Est Cost Intentional Release 0
Est Cost Prop Damage 0
Est Cost Emergency 0
Est Cost Other 0
Gas Cost In Mcf 4.82
Prpty 43607
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Wildlife Impact Ind No
Accident Psig 333
Gas Flow In Pipe In Mcf 0
Mop Psig 858
Mop Cfr Section 192.619(A)(2) View CFR 49 §192
Maop Established Date 2018-10-05 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Maop
Pressure Restriction Ind No
Gas Required Odorized Ind No
Pipeline Function Transmission System
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details Incident investigation did not indicate any reason to suspect controller actions may have contributed.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Compressor Or Compressor-Related Equipment
Eq Failure Type Compressor Or Compressor-Related Equipment
Other Compressor Ind Appurtenance Failure
Additional Electricity Ind Yes
Preparer Name C****** P********
Preparer Title Manager-Codes And Standards
Preparer Email C****************@k***********.com
Preparer Telephone 1-713-420-2460
Local Contact Name S*** K****
Local Contact Email S*********@k***********.com
Local Contact Telephone 1-979-232-4249
Authorizer Name Z*** R*****
Authorizer Title Director - Engineering Codes And Standards
Authorizer Telephone 8329190774
Authorizer Email Z**********@k***********.com
Narrative On august 24, 2025 at 9:00 pm ngpl staff were performing routine checks before pigging operations and found a 2" vent valve on the compressor fuel supply line was open causing a continuous gas release. They quickly shut off the manual fuel supply valve to stop the leak. 9047 mcf of natural gas was released, there were no injuries or fire, and no emergency services were required. The investigation revealed that a power interruption to the station caused an air compressor to fail. The loss of air pressure caused a 2" vent valve on the compressor fuel supply line to fail-open as designed. The station was set to manual operations at the time which suppressed the alarm to gas control.

All rights reserved. Copyright © by ClearPHMSA