HL incident on 2025-04-23 — TX
Operator
Enterprise Crude Pipeline Llc
Cause
Corrosion Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$60,000
Incident datetime
2025-04-23 00:00 UTC
Report number
Location
TX
Narrative
On 3/24/202 at 5:14 pm cst enterprise pipeline operator discovered a crude oil release on bypass pipeline at sealy station. The leak was immediately isolated. Approximately 0.48 barrels of crude oil was released. Upon further investigation, it was determined that internal corrosion from microbiological growth caused the crude oil release. The bypass line has been repaired and put back into service.
Detailed record list
Report Received Date
2025-04-23 00:00:00
Iyear
2025
Report Number
20250102
Supplemental Number
40841
Report Type
Supplemental Final
Operator Id
30829
Name
Enterprise Crude Pipeline Llc
Operator Street Address
1100 Louisiana Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
29.75895
Location Longitude
-96.148369
Commodity Released Type
Crude Oil
Unintentional Release Bbls
0.48
Recovered Bbls
0.48
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Communication State Fed Ind
No
Nrc Rpt Num
1426787
Additional Nrc Report Numbers
1426922
Ignite Ind
No
Upstream Action Taken
Valve Closure
Upstream Valve Type Ind
Remotely Controlled
Downstream Action Taken
Valve Closure
Downstream Valve Type Ind
Remotely Controlled
Notify Qualified Indiv Ind
Yes
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Sealy Terminal
Segment Name
C129/c116
Onshore State Abbreviation
Tx
Onshore Postal Code
77474
Onshore City Name
Sealy
Onshore County Name
Austin
Designated Location
Milepost
Designated Name
0+0.00
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Pipe
Pipe Type
Pipe Body
Puddle Weld Ind
No
Pipe Diameter
24
Pipe Wall Thickness
0.5
Pipe Smys
70000
Pipe Specification
Api-5ls
Pipe Seam Type
Erw - High Frequency
Pipe Manufacturer
Unknown
Pipe Coating Type
Fusion Bonded Epoxy(Fbe)
Coating Applied Ind
No
Installation Year
2017
Manufactured Year
2017
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
40
Est Cost Prop Damage
60000
Est Cost Emergency
30000
Est Cost Environmental
0
Est Cost Other
0
Prpty
90040
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
125
Mop Psig
275
Mop Cfr Section
Four Hour Test Or Operation �195.406(A)(5)
Maop Established Date
2017-01-16 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Length Segment Isolated
200
Internal Inspection Ind
No
Other Inspection Ind
Yes
Internal Inspection Details
Non-Mainline Pipe, Station Piping.
Operation Complications Ind
Yes
Other Complications Ind
Yes
Inspect Comp Details
Non-Mainline Pipe, Station Piping.
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Accident caused by internal corrosion.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
Internal Corrosion
Internal External
Internal Corrosion
Int Visual Exam Results
General Corrosion
Int Microbiological Ind
Yes
Int Field Exam Basis Ind
Yes
Int Low Point Pipe Loc Ind
Yes
Corrosion Inhibitors
Yes
Corrosion Lining
No
Cleaning Dewatering
Not Applicable - Not Mainline Pipe
Corrosion Coupons
Yes
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Intrnl Cor Microbiologic Ind
Yes
Preparer Name
M****** K********
Preparer Title
Pipeline Compliance Engineer
Preparer Email
M*********@e****.com
Preparer Telephone
713-376-9799
Prepared Date
2025-05-05 00:00:00
Local Contact Name
M****** K********
Local Contact Email
M*********@e****.com
Local Contact Telephone
713-376-9799
Authorizer Name
S**** D****
Authorizer Telephone
7133815585
Authorizer Title
Senior Manager Compliance
Authorizer Email
S******@e****.com
Narrative
On 3/24/202 at 5:14 pm cst enterprise pipeline operator discovered a crude oil release on bypass pipeline at sealy station. The leak was immediately isolated. Approximately 0.48 barrels of crude oil was released. Upon further investigation, it was determined that internal corrosion from microbiological growth caused the crude oil release. The bypass line has been repaired and put back into service.
Report Received Date | 2025-04-23 00:00:00 |
---|---|
Iyear | 2025 |
Report Number | 20250102 |
Supplemental Number | 40841 |
Report Type | Supplemental Final |
Operator Id | 30829 PHMSA Enforcement |
Name | Enterprise Crude Pipeline Llc |
Operator Street Address | 1100 Louisiana Street |
Operator City Name | Houston |
Operator State Abbreviation | TX |
Operator Postal Code | 77002 |
Time Zone | Central |
Daylight Savings Ind | Yes |
Location Latitude | 29.75895 Google Maps OpenStreetMap |
Location Longitude | -96.148369 Google Maps OpenStreetMap |
Commodity Released Type | Crude Oil |
Unintentional Release Bbls | 0.48 |
Recovered Bbls | 0.48 |
Fatality Ind | No |
Fatal | 0 |
Injury Ind | No |
Injure | 0 |
Accident Identifier | Local Operating Personnel, Including Contractors |
Operator Type | Operator Employee |
System Part Involved | Onshore Pipeline, Including Valve Sites |
On Off Shore | Onshore |
Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
Shutdown Due Accident Ind | Yes |
Communication State Fed Ind | No |
Nrc Rpt Num | 1426787 NRC Report How to search |
Additional Nrc Report Numbers | 1426922 |
Ignite Ind | No |
Upstream Action Taken | Valve Closure |
Upstream Valve Type Ind | Remotely Controlled |
Downstream Action Taken | Valve Closure |
Downstream Valve Type Ind | Remotely Controlled |
Notify Qualified Indiv Ind | Yes |
Oil Spill Removal Org Ind | No |
Num Pub Evacuated | 0 |
Pipe Fac Name | Sealy Terminal |
Segment Name | C129/c116 |
Onshore State Abbreviation | Tx |
Onshore Postal Code | 77474 |
Onshore City Name | Sealy |
Onshore County Name | Austin |
Designated Location | Milepost |
Designated Name | 0+0.00 |
Federal | No |
Location Type | Totally Contained On Operator-Controlled Property |
Incident Area Type | Aboveground |
Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
Crossing | No |
Pipe Facility Type | Interstate |
Item Involved | Pipe |
Pipe Type | Pipe Body |
Puddle Weld Ind | No |
Pipe Diameter | 24 |
Pipe Wall Thickness | 0.5 |
Pipe Smys | 70000 |
Pipe Specification | Api-5ls |
Pipe Seam Type | Erw - High Frequency |
Pipe Manufacturer | Unknown |
Pipe Coating Type | Fusion Bonded Epoxy(Fbe) |
Coating Applied Ind | No |
Installation Year | 2017 |
Manufactured Year | 2017 |
Material Involved | Carbon Steel |
Release Type | Leak |
Leak Type | Pinhole |
Wildlife Impact Ind | No |
Soil Contamination | Yes |
Long Term Assessment | No |
Remediation Ind | Yes |
Soil Remed Ind | Yes |
Water Contam Ind | No |
Could Be Hca | Yes |
Commodity Reached Hca | No |
Est Cost Oper Paid | 0 |
Est Cost Gas Released | 40 |
Est Cost Prop Damage | 60000 |
Est Cost Emergency | 30000 |
Est Cost Environmental | 0 |
Est Cost Other | 0 |
Prpty | 90040 |
Num Persons Hosp Not Ovnght | 0 |
Num Injured Treated By Emt | 0 |
Num Resident Building Affctd | 0 |
Num Business Building Affctd | 0 |
Accident Psig | 125 |
Mop Psig | 275 |
Mop Cfr Section | Four Hour Test Or Operation �195.406(A)(5) View CFR 49 §192 |
Maop Established Date | 2017-01-16 00:00:00 |
Maop Reversal Flow Ind | No |
Accident Pressure | Pressure Did Not Exceed Mop |
Pressure Restriction Ind | No |
Length Segment Isolated | 200 |
Internal Inspection Ind | No |
Other Inspection Ind | Yes |
Internal Inspection Details | Non-Mainline Pipe, Station Piping. |
Operation Complications Ind | Yes |
Other Complications Ind | Yes |
Inspect Comp Details | Non-Mainline Pipe, Station Piping. |
Pipeline Function | > 20% Smys Regulated Transmission |
Scada In Place Ind | Yes |
Scada Operating Ind | Yes |
Scada Functional Ind | Yes |
Scada Detection Ind | No |
Scada Conf Ind | No |
Cpm In Place Ind | Yes |
Cpm Operating Ind | Yes |
Cpm Functional Ind | Yes |
Cpm Detection Ind | No |
Cpm Conf Ind | No |
Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
Investigation Status Details | Accident caused by internal corrosion. |
Employee Drug Test Ind | No |
Contractor Drug Test Ind | No |
Cause | Corrosion Failure |
Cause Details | Internal Corrosion |
Internal External | Internal Corrosion |
Int Visual Exam Results | General Corrosion |
Int Microbiological Ind | Yes |
Int Field Exam Basis Ind | Yes |
Int Low Point Pipe Loc Ind | Yes |
Corrosion Inhibitors | Yes |
Corrosion Lining | No |
Cleaning Dewatering | Not Applicable - Not Mainline Pipe |
Corrosion Coupons | Yes |
Collected Data Ind | No |
Has Hydrtst Conduc Before Ind | No |
Direct Asmnt Conducted | No |
Non Destructive Exam Ind | No |
Intrnl Cor Microbiologic Ind | Yes |
Preparer Name | M****** K******** |
Preparer Title | Pipeline Compliance Engineer |
Preparer Email | M*********@e****.com |
Preparer Telephone | 713-376-9799 |
Prepared Date | 2025-05-05 00:00:00 |
Local Contact Name | M****** K******** |
Local Contact Email | M*********@e****.com |
Local Contact Telephone | 713-376-9799 |
Authorizer Name | S**** D**** |
Authorizer Telephone | 7133815585 |
Authorizer Title | Senior Manager Compliance |
Authorizer Email | S******@e****.com |
Narrative | On 3/24/202 at 5:14 pm cst enterprise pipeline operator discovered a crude oil release on bypass pipeline at sealy station. The leak was immediately isolated. Approximately 0.48 barrels of crude oil was released. Upon further investigation, it was determined that internal corrosion from microbiological growth caused the crude oil release. The bypass line has been repaired and put back into service. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company
All rights reserved. Copyright © by ClearPHMSA