GTG incident on 2025-08-24 — TX

Operator
Phillips 66 Dos Picos Llc
Cause
Equipment Failure
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$1,200,000
Incident datetime
2025-08-24 00:00 UTC
Report number
Location
TX
Narrative
During routine pigging operation flange between block valve and barrel began leaking. Steps taken to isolate leak immediately. Leaking gas ignited with no injuries and was allowed to burn out. Investigation determined that construction contractor installed incorrect gasket. Remainder of pipeline checked for correct gaskets.
Detailed record list
Report Received Date
2025-08-24 00:00:00
Iyear
2025
Report Number
20250096
Supplemental Number
41297
Report Type
Original Final
Operator Id
Name
Phillips 66 Dos Picos Llc
Operator Street Address
2331 Citywest Blvd Hq-08s-S820-06
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77042
Time Zone
Central
Daylight Savings Ind
No
Location Latitude
Location Longitude
Nrc Rpt Num
Additional Nrc Report Numbers
1438017
Commodity Released Type
Natural Gas
Unintentional Release
2652
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
Yes
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Ignite Ind
Yes
How Extinguished
Allowed To Burn Out
Gas Consumed By Fire In Mcf
2652
Explode Ind
No
Upstream Action Taken
Valve Closure
Downstream Action Taken
Valve Closure
Num Pub Evacuated
0
On Off Shore
Onshore
Onshore State Abbreviation
Tx
Onshore Postal Code
79782
Onshore City Name
Not Within A Municipality
Onshore County Name
Martin
Designated Location
Not Applicable
Pipe Fac Name
Dp-319
Segment Name
None
Federal
No
Location Type
Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
System Part Involved
Onshore Pipeline, Including Valve Sites
Item Involved
Flange Assembly
Installation Year
2025
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Seal Or Packing
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
531
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
No
Est Cost Oper Paid
750000
Est Cost Unintentional Release
8221
Est Cost Intentional Release
0
Est Cost Prop Damage
1200000
Est Cost Emergency
1500
Est Cost Other
0
Gas Cost In Mcf
3.1
Prpty
1959721
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
1100
Gas Flow In Pipe In Mcf
50000
Mop Psig
1480
Mop Cfr Section
192.619(A)(2)
Maop Established Date
2025-07-11 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Upstream Valve Type Ind
Manual
Downstream Valve Type Ind
Manual
Length Segment Isolated
24825
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
Type C Gathering
Scada In Place Ind
No
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Non-Threaded Connection Failure
Eq Failure Type
Non-Threaded Connection Failure
Other Non Threaded Ind
Gasket
Eq Additional Other Ind
Yes
Eq Additional Other Details
Improper Gasket Installed
Preparer Name
R****** N******
Preparer Email
R**************@p**.com
Preparer Telephone
4325571637
Local Contact Name
R****** N******
Local Contact Email
R**************@p**.com
Local Contact Telephone
4325571637
Authorizer Name
M*** P*****
Authorizer Telephone
9703970732
Authorizer Email
M*************@p**.com
Narrative
During routine pigging operation flange between block valve and barrel began leaking. Steps taken to isolate leak immediately. Leaking gas ignited with no injuries and was allowed to burn out. Investigation determined that construction contractor installed incorrect gasket. Remainder of pipeline checked for correct gaskets.
Report Received Date 2025-08-24 00:00:00
Iyear 2025
Report Number 20250096
Supplemental Number 41297
Report Type Original Final
Operator Id 40321 PHMSA Enforcement
Name Phillips 66 Dos Picos Llc
Operator Street Address 2331 Citywest Blvd Hq-08s-S820-06
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77042
Time Zone Central
Daylight Savings Ind No
Location Latitude 32.141325 Google Maps OpenStreetMap
Location Longitude -101.984608 Google Maps OpenStreetMap
Nrc Rpt Num 1437962 NRC Report How to search
Additional Nrc Report Numbers 1438017
Commodity Released Type Natural Gas
Unintentional Release 2652
Intentional Release 0
Accompanying Liquid 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Status When Identified Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind Yes
Communication State Fed Ind Yes
Party Initiated Communication Operator
Ignite Ind Yes
How Extinguished Allowed To Burn Out
Gas Consumed By Fire In Mcf 2652
Explode Ind No
Upstream Action Taken Valve Closure
Downstream Action Taken Valve Closure
Num Pub Evacuated 0
On Off Shore Onshore
Onshore State Abbreviation Tx
Onshore Postal Code 79782
Onshore City Name Not Within A Municipality
Onshore County Name Martin
Designated Location Not Applicable
Pipe Fac Name Dp-319
Segment Name None
Federal No
Location Type Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Intrastate
System Part Involved Onshore Pipeline, Including Valve Sites
Item Involved Flange Assembly
Installation Year 2025
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Leak
Leak Type Seal Or Packing
Class Location Type Class 1 Location
Could Be Hca No
Pir Radius 531
Heat Damage Ind No
Non Heat Damage Ind No
Did Occur In Mca Ind No
Est Cost Oper Paid 750000
Est Cost Unintentional Release 8221
Est Cost Intentional Release 0
Est Cost Prop Damage 1200000
Est Cost Emergency 1500
Est Cost Other 0
Gas Cost In Mcf 3.1
Prpty 1959721
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Wildlife Impact Ind No
Accident Psig 1100
Gas Flow In Pipe In Mcf 50000
Mop Psig 1480
Mop Cfr Section 192.619(A)(2) View CFR 49 §192
Maop Established Date 2025-07-11 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Maop
Pressure Restriction Ind No
Gas Required Odorized Ind No
Upstream Valve Type Ind Manual
Downstream Valve Type Ind Manual
Length Segment Isolated 24825
Internal Inspection Ind Yes
Operation Complications Ind No
Pipeline Function Type C Gathering
Scada In Place Ind No
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Investigation Status No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Non-Threaded Connection Failure
Eq Failure Type Non-Threaded Connection Failure
Other Non Threaded Ind Gasket
Eq Additional Other Ind Yes
Eq Additional Other Details Improper Gasket Installed
Preparer Name R****** N******
Preparer Email R**************@p**.com
Preparer Telephone 4325571637
Local Contact Name R****** N******
Local Contact Email R**************@p**.com
Local Contact Telephone 4325571637
Authorizer Name M*** P*****
Authorizer Telephone 9703970732
Authorizer Email M*************@p**.com
Narrative During routine pigging operation flange between block valve and barrel began leaking. Steps taken to isolate leak immediately. Leaking gas ignited with no injuries and was allowed to burn out. Investigation determined that construction contractor installed incorrect gasket. Remainder of pipeline checked for correct gaskets.

All rights reserved. Copyright © by ClearPHMSA