GTG incident on 2025-08-20 — NC

Operator
Piedmont Natural Gas Co Inc
Cause
Other Incident Cause
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$492,742
Incident datetime
2025-08-20 00:00 UTC
Report number
Location
NC
Narrative
At approximately 11:15 a.M. On 7/23/25, a leak was reported along line 5 section 4 in an area being excavated for an ili reassessment interval dig. Gas initially was present and recorded with a combustible gas indicator (cgi). Stopples were welded on and a by-pass was utilized to maintain flow along the pipeline. A 65 foot section of pipeline was removed and replaced with tested pipe. The cut out section contained the assumed location of the leak, the anomaly that was to be assessed, as well as a previously repaired anomaly. The cutout section was non destructively examined, but no leaks were found; therefore, an estimate of gas released could not be determined.
Detailed record list
Report Received Date
2025-08-20 00:00:00
Iyear
2025
Report Number
20250090
Supplemental Number
41279
Report Type
Original Final
Operator Id
Name
Piedmont Natural Gas Co Inc
Operator Street Address
525 South Tryon Street
Operator City Name
Charlotte
Operator State Abbreviation
NC
Operator Postal Code
28202
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Nrc Rpt Num
Additional Nrc Report Numbers
1437807
Commodity Released Type
Natural Gas
Unintentional Release
0.01
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
A Stopple Bypass Was Used To Isolate The Section.
Communication State Fed Ind
No
Ignite Ind
No
Upstream Action Taken
Operational Control
Upstream Oprtnl Cntrl Detail
A Bypass Was Made On The Pipe.
Downstream Action Taken
Operational Control
Downstream Oprtnl Cntrl Detail
A Bypass Was Made On The Pipe.
Num Pub Evacuated
0
On Off Shore
Onshore
Onshore State Abbreviation
Nc
Onshore Postal Code
27530
Onshore City Name
Goldsboro
Onshore County Name
Wayne
Designated Location
Not Applicable
Pipe Fac Name
Line 5
Segment Name
Line 5 Section 4
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
5
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Intrastate
System Part Involved
Onshore Pipeline, Including Valve Sites
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
10
Puddle Weld Ind
No
Pipe Wall Thickness
0.188
Pipe Smys
42000
Pipe Specification
X46
Pipe Seam Type
Longitudinal Erw - Low Frequency
Pipe Manufacturer
Unknown
Pipe Coating Type
Coal Tar
Coating Applied Ind
No
Installation Year
1959
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Other
Release Type Details
Suspect Leak But A Leak Was Not Identified.
Class Location Type
Class 3 Location
Could Be Hca
No
Not Flammable Ind
Not Flammable
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
Yes
Mca Buildng Human Occupy Ind
Yes
Est Cost Oper Paid
0
Est Cost Unintentional Release
0
Est Cost Intentional Release
0
Est Cost Prop Damage
492742
Est Cost Emergency
0
Est Cost Other
0
Gas Cost In Mcf
4.5
Prpty
492742
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
647
Gas Flow In Pipe In Mcf
28000
Mop Psig
695
Mop Cfr Section
Maop Established Date
1969-10-29 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
Yes
Gas Odorized Ind
Yes
Length Segment Isolated
20590
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Contractor Working For The Operator
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Identification by field team during a field activity.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Incident Cause
Cause Details
Unknown
Other Type
Unknown
Unknown Subtype
Investigation Complete, Cause Of Incident Unknown
Incident Unknown Comments
After Testing A Cause Could Not Be Determined.
Preparer Name
C********** R******
Preparer Title
Gas Regulatory Compliance Analyst
Preparer Email
C******************@d**********.com
Preparer Telephone
704-731-4680
Authorizer Name
F***** B****
Authorizer Title
Pipeline Safety Governance Manager
Authorizer Telephone
704-731-4618
Authorizer Email
F***********@d**********.com
Narrative
At approximately 11:15 a.M. On 7/23/25, a leak was reported along line 5 section 4 in an area being excavated for an ili reassessment interval dig. Gas initially was present and recorded with a combustible gas indicator (cgi). Stopples were welded on and a by-pass was utilized to maintain flow along the pipeline. A 65 foot section of pipeline was removed and replaced with tested pipe. The cut out section contained the assumed location of the leak, the anomaly that was to be assessed, as well as a previously repaired anomaly. The cutout section was non destructively examined, but no leaks were found; therefore, an estimate of gas released could not be determined.
Report Received Date 2025-08-20 00:00:00
Iyear 2025
Report Number 20250090
Supplemental Number 41279
Report Type Original Final
Operator Id 15518 PHMSA Enforcement
Name Piedmont Natural Gas Co Inc
Operator Street Address 525 South Tryon Street
Operator City Name Charlotte
Operator State Abbreviation NC
Operator Postal Code 28202
Time Zone Eastern
Daylight Savings Ind Yes
Location Latitude 35.396262 Google Maps OpenStreetMap
Location Longitude -78.071065 Google Maps OpenStreetMap
Nrc Rpt Num 1437735 NRC Report How to search
Additional Nrc Report Numbers 1437807
Commodity Released Type Natural Gas
Unintentional Release 0.01
Intentional Release 0
Accompanying Liquid 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Status When Identified Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind No
Shutdown Explain A Stopple Bypass Was Used To Isolate The Section.
Communication State Fed Ind No
Ignite Ind No
Upstream Action Taken Operational Control
Upstream Oprtnl Cntrl Detail A Bypass Was Made On The Pipe.
Downstream Action Taken Operational Control
Downstream Oprtnl Cntrl Detail A Bypass Was Made On The Pipe.
Num Pub Evacuated 0
On Off Shore Onshore
Onshore State Abbreviation Nc
Onshore Postal Code 27530
Onshore City Name Goldsboro
Onshore County Name Wayne
Designated Location Not Applicable
Pipe Fac Name Line 5
Segment Name Line 5 Section 4
Federal No
Location Type Pipeline Right-Of-Way
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover 5
Other Underground Facilities No
Crossing No
Pipe Facility Type Intrastate
System Part Involved Onshore Pipeline, Including Valve Sites
Item Involved Pipe
Pipe Type Pipe Body
Pipe Diameter 10
Puddle Weld Ind No
Pipe Wall Thickness 0.188
Pipe Smys 42000
Pipe Specification X46
Pipe Seam Type Longitudinal Erw - Low Frequency
Pipe Manufacturer Unknown
Pipe Coating Type Coal Tar
Coating Applied Ind No
Installation Year 1959
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Other
Release Type Details Suspect Leak But A Leak Was Not Identified.
Class Location Type Class 3 Location
Could Be Hca No
Not Flammable Ind Not Flammable
Heat Damage Ind No
Non Heat Damage Ind No
Did Occur In Mca Ind Yes
Mca Buildng Human Occupy Ind Yes
Est Cost Oper Paid 0
Est Cost Unintentional Release 0
Est Cost Intentional Release 0
Est Cost Prop Damage 492742
Est Cost Emergency 0
Est Cost Other 0
Gas Cost In Mcf 4.5
Prpty 492742
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Wildlife Impact Ind No
Accident Psig 647
Gas Flow In Pipe In Mcf 28000
Mop Psig 695
Mop Cfr Section 192.619(C) View CFR 49 §192
Maop Established Date 1969-10-29 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Maop
Pressure Restriction Ind No
Gas Required Odorized Ind Yes
Gas Odorized Ind Yes
Length Segment Isolated 20590
Internal Inspection Ind Yes
Operation Complications Ind No
Pipeline Function Transmission System
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Contractor Working For The Operator
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details Identification by field team during a field activity.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Other Incident Cause
Cause Details Unknown
Other Type Unknown
Unknown Subtype Investigation Complete, Cause Of Incident Unknown
Incident Unknown Comments After Testing A Cause Could Not Be Determined.
Preparer Name C********** R******
Preparer Title Gas Regulatory Compliance Analyst
Preparer Email C******************@d**********.com
Preparer Telephone 704-731-4680
Authorizer Name F***** B****
Authorizer Title Pipeline Safety Governance Manager
Authorizer Telephone 704-731-4618
Authorizer Email F***********@d**********.com
Narrative At approximately 11:15 a.M. On 7/23/25, a leak was reported along line 5 section 4 in an area being excavated for an ili reassessment interval dig. Gas initially was present and recorded with a combustible gas indicator (cgi). Stopples were welded on and a by-pass was utilized to maintain flow along the pipeline. A 65 foot section of pipeline was removed and replaced with tested pipe. The cut out section contained the assumed location of the leak, the anomaly that was to be assessed, as well as a previously repaired anomaly. The cutout section was non destructively examined, but no leaks were found; therefore, an estimate of gas released could not be determined.

All rights reserved. Copyright © by ClearPHMSA