GTG incident on 2025-08-07 — TX

Operator
Dcp Midstream, Lp
Cause
Corrosion Failure
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$261,000
Incident datetime
2025-08-07 00:00 UTC
Report number
Location
TX
Narrative
At approximately 4:10 pm on 7/9/2025 sj-1 pipeline experienced a rupture adjacent to fm-2437 in lavaca county, gas ignited and burned off within 15 minutes. Dcp field techs completed isolation of entire section by 4:42 pm. Fm-2437 was closed until remediation and repairs were completed. Line was cut and capped and left out of service pending further evaluation.
Detailed record list
Report Received Date
2025-08-07 00:00:00
Iyear
2025
Report Number
20250087
Supplemental Number
41232
Report Type
Original
Operator Id
Name
Dcp Midstream, Lp
Operator Street Address
2331 Citywest Blvd. Hq-08-S812-02
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77042
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Nrc Rpt Num
Additional Nrc Report Numbers
1436582
Commodity Released Type
Natural Gas
Unintentional Release
631.9
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
Yes
Still Shutdown Ind
Yes
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Ignite Ind
Yes
How Extinguished
Allowed To Burn Out
Gas Consumed By Fire In Mcf
631.9
Explode Ind
Yes
Upstream Action Taken
Valve Closure
Downstream Action Taken
Valve Closure
Num Pub Evacuated
0
On Off Shore
Onshore
Onshore State Abbreviation
Tx
Onshore Postal Code
77964
Onshore City Name
Not Within A Municipality
Onshore County Name
Lavaca
Designated Location
Not Applicable
Pipe Fac Name
Prov. City To Hasting Station (Line 5)
Segment Name
Sj-1
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
84
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Intrastate
System Part Involved
Onshore Pipeline, Including Valve Sites
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
16
Puddle Weld Ind
No
Pipe Wall Thickness
0.281
Pipe Smys
46000
Pipe Specification
X46
Pipe Seam Type
Flash Welded
Pipe Manufacturer
Unknown
Pipe Coating Type
Coal Tar
Coating Applied Ind
Unknown
Installation Year
1950
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Rupture
Rupture Orient
Longitudinal
Rupture Length
8.5
Rupture Width
2
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
313
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
No
Est Cost Oper Paid
1500
Est Cost Unintentional Release
1580
Est Cost Intentional Release
0
Est Cost Prop Damage
261000
Est Cost Emergency
2000
Est Cost Other
9800
Est Cost Other Details
Metallurgical Analysis.
Gas Cost In Mcf
2.5
Prpty
275880
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
1021
Gas Flow In Pipe In Mcf
2500
Mop Psig
1163
Mop Cfr Section
192.619(A)(1)
Maop Established Date
2002-07-23 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Upstream Valve Type Ind
Manual
Downstream Valve Type Ind
Remotely Controlled
Length Segment Isolated
11897
Internal Inspection Ind
Yes
Operation Complications Ind
Yes
Low Flow Ind
Yes
Pipeline Function
Type C Gathering
Scada In Place Ind
No
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
Internal Corrosion
Internal External
Internal Corrosion
Int Visual Exam Results
Localized Pitting
Int Water Acid Ind
Yes
Int Metallurgical Basis Ind
Yes
Int Low Point Pipe Loc Ind
Yes
Corrosion Inhibitors
Yes
Corrosion Lining
No
Cleaning Dewatering
No
Corrosion Coupons
Yes
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Preparer Name
O****** R********
Preparer Title
Dot Specialist
Preparer Email
O*****************@p**.com
Preparer Telephone
361-730-8520
Local Contact Name
O****** R********
Local Contact Email
O*****************@p**.com
Local Contact Telephone
361-730-8520
Authorizer Name
M****** P*****
Authorizer Title
Director Dot Gas Operations Compliance
Authorizer Telephone
970-397-0732
Authorizer Email
M*************@p**.com
Narrative
At approximately 4:10 pm on 7/9/2025 sj-1 pipeline experienced a rupture adjacent to fm-2437 in lavaca county, gas ignited and burned off within 15 minutes. Dcp field techs completed isolation of entire section by 4:42 pm. Fm-2437 was closed until remediation and repairs were completed. Line was cut and capped and left out of service pending further evaluation.
Report Received Date 2025-08-07 00:00:00
Iyear 2025
Report Number 20250087
Supplemental Number 41232
Report Type Original
Operator Id 31130 PHMSA Enforcement
Name Dcp Midstream, Lp
Operator Street Address 2331 Citywest Blvd. Hq-08-S812-02
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77042
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 29.3356 Google Maps OpenStreetMap
Location Longitude -96.67039 Google Maps OpenStreetMap
Nrc Rpt Num 1436439 NRC Report How to search
Additional Nrc Report Numbers 1436582
Commodity Released Type Natural Gas
Unintentional Release 631.9
Intentional Release 0
Accompanying Liquid 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Status When Identified Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind Yes
Still Shutdown Ind Yes
Communication State Fed Ind Yes
Party Initiated Communication Operator
Ignite Ind Yes
How Extinguished Allowed To Burn Out
Gas Consumed By Fire In Mcf 631.9
Explode Ind Yes
Upstream Action Taken Valve Closure
Downstream Action Taken Valve Closure
Num Pub Evacuated 0
On Off Shore Onshore
Onshore State Abbreviation Tx
Onshore Postal Code 77964
Onshore City Name Not Within A Municipality
Onshore County Name Lavaca
Designated Location Not Applicable
Pipe Fac Name Prov. City To Hasting Station (Line 5)
Segment Name Sj-1
Federal No
Location Type Pipeline Right-Of-Way
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover 84
Other Underground Facilities No
Crossing No
Pipe Facility Type Intrastate
System Part Involved Onshore Pipeline, Including Valve Sites
Item Involved Pipe
Pipe Type Pipe Body
Pipe Diameter 16
Puddle Weld Ind No
Pipe Wall Thickness 0.281
Pipe Smys 46000
Pipe Specification X46
Pipe Seam Type Flash Welded
Pipe Manufacturer Unknown
Pipe Coating Type Coal Tar
Coating Applied Ind Unknown
Installation Year 1950
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Rupture
Rupture Orient Longitudinal
Rupture Length 8.5
Rupture Width 2
Class Location Type Class 1 Location
Could Be Hca No
Pir Radius 313
Heat Damage Ind No
Non Heat Damage Ind No
Did Occur In Mca Ind No
Est Cost Oper Paid 1500
Est Cost Unintentional Release 1580
Est Cost Intentional Release 0
Est Cost Prop Damage 261000
Est Cost Emergency 2000
Est Cost Other 9800
Est Cost Other Details Metallurgical Analysis.
Gas Cost In Mcf 2.5
Prpty 275880
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Wildlife Impact Ind No
Accident Psig 1021
Gas Flow In Pipe In Mcf 2500
Mop Psig 1163
Mop Cfr Section 192.619(A)(1) View CFR 49 §192
Maop Established Date 2002-07-23 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Maop
Pressure Restriction Ind No
Gas Required Odorized Ind No
Upstream Valve Type Ind Manual
Downstream Valve Type Ind Remotely Controlled
Length Segment Isolated 11897
Internal Inspection Ind Yes
Operation Complications Ind Yes
Low Flow Ind Yes
Pipeline Function Type C Gathering
Scada In Place Ind No
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Investigation Status No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Corrosion Failure
Cause Details Internal Corrosion
Internal External Internal Corrosion
Int Visual Exam Results Localized Pitting
Int Water Acid Ind Yes
Int Metallurgical Basis Ind Yes
Int Low Point Pipe Loc Ind Yes
Corrosion Inhibitors Yes
Corrosion Lining No
Cleaning Dewatering No
Corrosion Coupons Yes
Collected Data Ind No
Has Hydrtst Conduc Before Ind No
Direct Asmnt Conducted No
Non Destructive Exam Ind No
Preparer Name O****** R********
Preparer Title Dot Specialist
Preparer Email O*****************@p**.com
Preparer Telephone 361-730-8520
Local Contact Name O****** R********
Local Contact Email O*****************@p**.com
Local Contact Telephone 361-730-8520
Authorizer Name M****** P*****
Authorizer Title Director Dot Gas Operations Compliance
Authorizer Telephone 970-397-0732
Authorizer Email M*************@p**.com
Narrative At approximately 4:10 pm on 7/9/2025 sj-1 pipeline experienced a rupture adjacent to fm-2437 in lavaca county, gas ignited and burned off within 15 minutes. Dcp field techs completed isolation of entire section by 4:42 pm. Fm-2437 was closed until remediation and repairs were completed. Line was cut and capped and left out of service pending further evaluation.