HL incident on 2024-11-22 — CO

Operator
Elevation Midstream
Cause
Equipment Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$700
Incident datetime
2024-11-22 00:00 UTC
Report number
Location
CO
Narrative
While preparing the pipeline to send the ili tool down the line; operators contacted mvp control room to let them know that they were placing the valves in local operation. Mvp control room operated the main valve to the closed position, opened up bypass, closed kicker valve, control room confirmed valves 0% open and then on-site operations confirmed that the valves were closed then put in manual operations by operations. Drained barrel to sump . Bypass was open everything else was closed. When control room started the flow; liquid began spraying out of kicker valve. Operations immediately called control room to stop flow. It appears the cause was failure of the valve to fully seat. Update: elevation physically tested the valve and could not recreate the situation. The valve is fully operational. Programming of the valve closure was also tested and no issues identified. It appears that there was some paraffin debris that may have prevented the valve from fully seating. Elevation is updating the site specific procedure to address this potential issue, paraffin debris preventing full seating of the valve, in the future.
Detailed record list
Report Received Date
2024-11-22 00:00:00
Iyear
2024
Report Number
20240279
Supplemental Number
40476
Report Type
Supplemental
Operator Id
Name
Elevation Midstream
Operator Street Address
1200 17th Street, Suite 750
Operator City Name
Denver
Operator State Abbreviation
CO
Operator Postal Code
80202
Time Zone
Mountain
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Crude Oil
Unintentional Release Bbls
10
Recovered Bbls
8
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Communication State Fed Ind
No
Nrc Rpt Num
Ignite Ind
No
Upstream Action Taken
Valve Closure
Upstream Valve Type Ind
Remotely Controlled
Downstream Action Taken
Valve Closure
Downstream Valve Type Ind
Remotely Controlled
Notify Qualified Indiv Ind
Yes
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Freedom Pipeline
Segment Name
Saddlehorn Freedom Launcher
Onshore State Abbreviation
Co
Onshore Postal Code
80642
Onshore City Name
Not Within A Municipality
Onshore County Name
Weld
Designated Location
Milepost
Designated Name
0
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Valve
Valve Type
Mainline
Valve Mainline Type
Other
Valve Mainline Details
Kicker Valve
Valve Manufacturer
M&j
Installation Year
2020
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Other
Leak Type Other
May Have Not Been Fully Seated
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
0
Est Cost Prop Damage
700
Est Cost Emergency
0
Est Cost Environmental
125000
Est Cost Other
0
Prpty
125700
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
110
Mop Psig
1480
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
2020-05-07 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Length Segment Isolated
20
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
Yes
Contractor Drug Test Ind
No
Num Employees Tested
3
Num Employees Failed
0
Cause
Equipment Failure
Cause Details
Malfunction Of Control/relief Equipment
Eq Failure Type
Malfunction Of Control/relief Equipment
Control Valve Ind
Yes
Ief Addl Misalignment Ind
Yes
Eqf Control Releaf Ind
Yes
Preparer Name
L** K****
Preparer Title
Vice President Ehs Regulatory Compliance
Preparer Email
L*****@e*****************.com
Preparer Telephone
3038824404
Prepared Date
2025-02-04 00:00:00
Local Contact Name
K**** S******
Local Contact Email
K*******@e*****************.com
Local Contact Telephone
9703965494
Authorizer Name
L** K****
Authorizer Telephone
3038824404
Authorizer Title
Vice President Ehs Regulatory Compliance
Authorizer Email
L*****@e*****************.com
Narrative
While preparing the pipeline to send the ili tool down the line; operators contacted mvp control room to let them know that they were placing the valves in local operation. Mvp control room operated the main valve to the closed position, opened up bypass, closed kicker valve, control room confirmed valves 0% open and then on-site operations confirmed that the valves were closed then put in manual operations by operations. Drained barrel to sump . Bypass was open everything else was closed. When control room started the flow; liquid began spraying out of kicker valve. Operations immediately called control room to stop flow. It appears the cause was failure of the valve to fully seat. Update: elevation physically tested the valve and could not recreate the situation. The valve is fully operational. Programming of the valve closure was also tested and no issues identified. It appears that there was some paraffin debris that may have prevented the valve from fully seating. Elevation is updating the site specific procedure to address this potential issue, paraffin debris preventing full seating of the valve, in the future.
Report Received Date 2024-11-22 00:00:00
Iyear 2024
Report Number 20240279
Supplemental Number 40476
Report Type Supplemental
Operator Id 39746 PHMSA Enforcement
Name Elevation Midstream
Operator Street Address 1200 17th Street, Suite 750
Operator City Name Denver
Operator State Abbreviation CO
Operator Postal Code 80202
Time Zone Mountain
Daylight Savings Ind Yes
Location Latitude 40.20235 Google Maps OpenStreetMap
Location Longitude -104.60803 Google Maps OpenStreetMap
Commodity Released Type Crude Oil
Unintentional Release Bbls 10
Recovered Bbls 8
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
System Part Involved Onshore Pipeline, Including Valve Sites
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind Yes
Communication State Fed Ind No
Nrc Rpt Num 1414462 NRC Report How to search
Ignite Ind No
Upstream Action Taken Valve Closure
Upstream Valve Type Ind Remotely Controlled
Downstream Action Taken Valve Closure
Downstream Valve Type Ind Remotely Controlled
Notify Qualified Indiv Ind Yes
Oil Spill Removal Org Ind No
Num Pub Evacuated 0
Pipe Fac Name Freedom Pipeline
Segment Name Saddlehorn Freedom Launcher
Onshore State Abbreviation Co
Onshore Postal Code 80642
Onshore City Name Not Within A Municipality
Onshore County Name Weld
Designated Location Milepost
Designated Name 0
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Intrastate
Item Involved Valve
Valve Type Mainline
Valve Mainline Type Other
Valve Mainline Details Kicker Valve
Valve Manufacturer M&j
Installation Year 2020
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Leak
Leak Type Other
Leak Type Other May Have Not Been Fully Seated
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment No
Remediation Ind Yes
Soil Remed Ind Yes
Water Contam Ind No
Could Be Hca No
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 0
Est Cost Prop Damage 700
Est Cost Emergency 0
Est Cost Environmental 125000
Est Cost Other 0
Prpty 125700
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 110
Mop Psig 1480
Mop Cfr Section Component Design Pressure �195.406(A)(2) View CFR 49 §192
Maop Established Date 2020-05-07 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Length Segment Isolated 20
Internal Inspection Ind Yes
Operation Complications Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind No
Investigation Status Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind Yes
Invest No Controller Ind Yes
Employee Drug Test Ind Yes
Contractor Drug Test Ind No
Num Employees Tested 3
Num Employees Failed 0
Cause Equipment Failure
Cause Details Malfunction Of Control/relief Equipment
Eq Failure Type Malfunction Of Control/relief Equipment
Control Valve Ind Yes
Ief Addl Misalignment Ind Yes
Eqf Control Releaf Ind Yes
Preparer Name L** K****
Preparer Title Vice President Ehs Regulatory Compliance
Preparer Email L*****@e*****************.com
Preparer Telephone 3038824404
Prepared Date 2025-02-04 00:00:00
Local Contact Name K**** S******
Local Contact Email K*******@e*****************.com
Local Contact Telephone 9703965494
Authorizer Name L** K****
Authorizer Telephone 3038824404
Authorizer Title Vice President Ehs Regulatory Compliance
Authorizer Email L*****@e*****************.com
Narrative While preparing the pipeline to send the ili tool down the line; operators contacted mvp control room to let them know that they were placing the valves in local operation. Mvp control room operated the main valve to the closed position, opened up bypass, closed kicker valve, control room confirmed valves 0% open and then on-site operations confirmed that the valves were closed then put in manual operations by operations. Drained barrel to sump . Bypass was open everything else was closed. When control room started the flow; liquid began spraying out of kicker valve. Operations immediately called control room to stop flow. It appears the cause was failure of the valve to fully seat. Update: elevation physically tested the valve and could not recreate the situation. The valve is fully operational. Programming of the valve closure was also tested and no issues identified. It appears that there was some paraffin debris that may have prevented the valve from fully seating. Elevation is updating the site specific procedure to address this potential issue, paraffin debris preventing full seating of the valve, in the future.