Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2024-10-11 — TX
Operator
Energy Transfer Nederland Terminal Llc
Cause
Equipment Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$6,500
Incident datetime
2024-10-11 00:00 UTC
Report number
Location
TX
Narrative
On 9/11/2024 at approximately 05:00, a contractor discovered a release of crude oil at the marshland manifold on inlet piping associated with #2 booster. The booster pump was shut down and the pressure relief valve was isolated which stopped the leak. The leak was determined to be coming from a crack in the 1.5-inch pressure relief line from the booster discharge line. Approximately 100 barrels of crude oil was released into containment. Cleanup crews removed free product and remediated contaminated soil. The 48hr nrc report was made as soon as possible after it was discovered that it had not been made w/in 48 hours of the original nrc report. An investigation was completed, and it was determined that a thermal pressure safety valve (psv) had setpoint level too close to the facility line normal operating pressure which allowed activation of the psv during routine startups of the associated booster pump. The psv failed to reseat which caused vibration during the continued flow through the psv and led to a crack in the schedule 80 pipe associated with the psv leading to the release. To prevent reoccurrence, the psv and associated piping has been replaced. The new psv has an increased setpoint to ensure it will not activate under normal operating conditions but will still protect the piping from thermal overpressure.
Detailed record list
Report Received Date
2024-10-11 00:00:00
Iyear
2024
Report Number
20240243
Supplemental Number
40098
Report Type
Supplemental Final
Operator Id
39706
Name
Energy Transfer Nederland Terminal Llc
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
30.001325
Location Longitude
-93.992525
Commodity Released Type
Crude Oil
Unintentional Release Bbls
100
Recovered Bbls
100
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Contractor Working For The Operator
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Communication State Fed Ind
No
Nrc Rpt Num
1410452
Additional Nrc Report Numbers
1411792
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Nederland Terminal
Segment Name
Marshland Manifold
Onshore State Abbreviation
Tx
Onshore Postal Code
77627
Onshore City Name
Nederland
Onshore County Name
Jefferson
Designated Location
Survey Station No.
Designated Name
0+00
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Relief Line And Relief Equipment
Installation Year
2016
Manufactured Year
2016
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Crack
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
10000
Est Cost Prop Damage
6500
Est Cost Emergency
7000
Est Cost Environmental
300000
Est Cost Other
0
Prpty
323500
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
147
Mop Psig
290
Mop Cfr Section
Subpart E Pressure Test �195.406(A)(3)
Maop Established Date
2016-12-22 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
A review of the accident determined that there were no control room actions that contributed to the event.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Malfunction Of Control/relief Equipment
Eq Failure Type
Malfunction Of Control/relief Equipment
Relief Valve Ind
Yes
Eq Additional Other Ind
Yes
Eq Additional Other Details
Harmonic Distortion
Io Wrong Equipment Ind
Yes
Preparer Name
T*** N*******
Preparer Title
Director - Dot Compliance
Preparer Email
T************@e*************.com
Preparer Telephone
713-989-7126
Prepared Date
2024-10-11 00:00:00
Authorizer Name
T*** N*******
Authorizer Telephone
713-989-7126
Authorizer Title
Director - Dot Compliance
Authorizer Email
T************@e*************.com
Narrative
On 9/11/2024 at approximately 05:00, a contractor discovered a release of crude oil at the marshland manifold on inlet piping associated with #2 booster. The booster pump was shut down and the pressure relief valve was isolated which stopped the leak. The leak was determined to be coming from a crack in the 1.5-inch pressure relief line from the booster discharge line. Approximately 100 barrels of crude oil was released into containment. Cleanup crews removed free product and remediated contaminated soil. The 48hr nrc report was made as soon as possible after it was discovered that it had not been made w/in 48 hours of the original nrc report. An investigation was completed, and it was determined that a thermal pressure safety valve (psv) had setpoint level too close to the facility line normal operating pressure which allowed activation of the psv during routine startups of the associated booster pump. The psv failed to reseat which caused vibration during the continued flow through the psv and led to a crack in the schedule 80 pipe associated with the psv leading to the release. To prevent reoccurrence, the psv and associated piping has been replaced. The new psv has an increased setpoint to ensure it will not activate under normal operating conditions but will still protect the piping from thermal overpressure.
Report Received Date | 2024-10-11 00:00:00 |
---|---|
Iyear | 2024 |
Report Number | 20240243 |
Supplemental Number | 40098 |
Report Type | Supplemental Final |
Operator Id | 39706 PHMSA Enforcement |
Name | Energy Transfer Nederland Terminal Llc |
Operator Street Address | 1300 Main Street |
Operator City Name | Houston |
Operator State Abbreviation | TX |
Operator Postal Code | 77002 |
Time Zone | Central |
Daylight Savings Ind | Yes |
Location Latitude | 30.001325 Google Maps OpenStreetMap |
Location Longitude | -93.992525 Google Maps OpenStreetMap |
Commodity Released Type | Crude Oil |
Unintentional Release Bbls | 100 |
Recovered Bbls | 100 |
Fatality Ind | No |
Fatal | 0 |
Injury Ind | No |
Injure | 0 |
Accident Identifier | Local Operating Personnel, Including Contractors |
Operator Type | Contractor Working For The Operator |
System Part Involved | Onshore Terminal/tank Farm Equipment And Piping |
On Off Shore | Onshore |
Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
Shutdown Due Accident Ind | Yes |
Communication State Fed Ind | No |
Nrc Rpt Num | 1410452 NRC Report How to search |
Additional Nrc Report Numbers | 1411792 |
Ignite Ind | No |
Notify Qualified Indiv Ind | Yes |
Oil Spill Removal Org Ind | No |
Num Pub Evacuated | 0 |
Pipe Fac Name | Nederland Terminal |
Segment Name | Marshland Manifold |
Onshore State Abbreviation | Tx |
Onshore Postal Code | 77627 |
Onshore City Name | Nederland |
Onshore County Name | Jefferson |
Designated Location | Survey Station No. |
Designated Name | 0+00 |
Federal | No |
Location Type | Totally Contained On Operator-Controlled Property |
Incident Area Type | Aboveground |
Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
Crossing | No |
Pipe Facility Type | Interstate |
Item Involved | Relief Line And Relief Equipment |
Installation Year | 2016 |
Manufactured Year | 2016 |
Material Involved | Carbon Steel |
Release Type | Leak |
Leak Type | Crack |
Wildlife Impact Ind | No |
Soil Contamination | Yes |
Long Term Assessment | No |
Remediation Ind | Yes |
Soil Remed Ind | Yes |
Water Contam Ind | No |
Could Be Hca | Yes |
Commodity Reached Hca | Yes |
High Pop Ind | Yes |
High Pop Yes No | Yes |
Est Cost Oper Paid | 0 |
Est Cost Gas Released | 10000 |
Est Cost Prop Damage | 6500 |
Est Cost Emergency | 7000 |
Est Cost Environmental | 300000 |
Est Cost Other | 0 |
Prpty | 323500 |
Num Persons Hosp Not Ovnght | 0 |
Num Injured Treated By Emt | 0 |
Num Resident Building Affctd | 0 |
Num Business Building Affctd | 0 |
Accident Psig | 147 |
Mop Psig | 290 |
Mop Cfr Section | Subpart E Pressure Test �195.406(A)(3) View CFR 49 §192 |
Maop Established Date | 2016-12-22 00:00:00 |
Maop Reversal Flow Ind | No |
Accident Pressure | Pressure Did Not Exceed Mop |
Pressure Restriction Ind | No |
Pipeline Function | > 20% Smys Regulated Transmission |
Scada In Place Ind | Yes |
Scada Operating Ind | Yes |
Scada Functional Ind | Yes |
Scada Detection Ind | No |
Scada Conf Ind | No |
Cpm In Place Ind | Yes |
Cpm Operating Ind | Yes |
Cpm Functional Ind | Yes |
Cpm Detection Ind | No |
Cpm Conf Ind | No |
Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
Investigation Status Details | A review of the accident determined that there were no control room actions that contributed to the event. |
Employee Drug Test Ind | No |
Contractor Drug Test Ind | No |
Cause | Equipment Failure |
Cause Details | Malfunction Of Control/relief Equipment |
Eq Failure Type | Malfunction Of Control/relief Equipment |
Relief Valve Ind | Yes |
Eq Additional Other Ind | Yes |
Eq Additional Other Details | Harmonic Distortion |
Io Wrong Equipment Ind | Yes |
Preparer Name | T*** N******* |
Preparer Title | Director - Dot Compliance |
Preparer Email | T************@e*************.com |
Preparer Telephone | 713-989-7126 |
Prepared Date | 2024-10-11 00:00:00 |
Authorizer Name | T*** N******* |
Authorizer Telephone | 713-989-7126 |
Authorizer Title | Director - Dot Compliance |
Authorizer Email | T************@e*************.com |
Narrative | On 9/11/2024 at approximately 05:00, a contractor discovered a release of crude oil at the marshland manifold on inlet piping associated with #2 booster. The booster pump was shut down and the pressure relief valve was isolated which stopped the leak. The leak was determined to be coming from a crack in the 1.5-inch pressure relief line from the booster discharge line. Approximately 100 barrels of crude oil was released into containment. Cleanup crews removed free product and remediated contaminated soil. The 48hr nrc report was made as soon as possible after it was discovered that it had not been made w/in 48 hours of the original nrc report. An investigation was completed, and it was determined that a thermal pressure safety valve (psv) had setpoint level too close to the facility line normal operating pressure which allowed activation of the psv during routine startups of the associated booster pump. The psv failed to reseat which caused vibration during the continued flow through the psv and led to a crack in the schedule 80 pipe associated with the psv leading to the release. To prevent reoccurrence, the psv and associated piping has been replaced. The new psv has an increased setpoint to ensure it will not activate under normal operating conditions but will still protect the piping from thermal overpressure. |