HL incident on 2024-09-25 — TX

Operator
Enterprise Products Operating Llc
Cause
Material Failure Of Pipe Or Weld
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$235,000
Incident datetime
2024-09-25 00:00 UTC
Report number
Location
TX
Narrative
At 09:44 cdt on 9/1/2024 a third party called the enterprise pipeline control center to report a possible vapor cloud at the shin oak cross plains pump station. The pump station was then immediately isolated and bypassed. An enterprise pipeline technician arrived on site at 11:30 cdt on 9/1/2024 and observed a small ice ball on the station discharge piping. The piping was blown down, and a crack was observed where the ice ball had been found. On 9/2/2024 at 08:15 cdt the decision was made that a section of piping would need to be cut out and replaced, resulting in repair costs exceeding $50,000. Results of metallurgical analysis indicated a fatigue crack that originated at a mechanical imperfection or anomaly at the toe of the weld joining an elbow fitting to the discharge piping. Nrc #1409698, 48-hour update #1409829.
Detailed record list
Report Received Date
2024-09-25 00:00:00
Iyear
2024
Report Number
20240227
Supplemental Number
40232
Report Type
Supplemental Final
Operator Id
Name
Enterprise Products Operating Llc
Operator Street Address
1100 Louisiana Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls
0.1
Intentional Release Bbls
80
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Notification From Public
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
Pump Station Was Isolated And Bypassed.
Communication State Fed Ind
No
Nrc Rpt Num
Additional Nrc Report Numbers
1409829
Ignite Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Shin Oak Pipeline/cross Plains Pump Station
Segment Name
1050
Onshore State Abbreviation
Tx
Onshore Postal Code
76443
Onshore City Name
Cross Plains
Onshore County Name
Callahan
Designated Location
Milepost
Designated Name
296
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Pipe
Pipe Type
Pipe Body
Puddle Weld Ind
No
Pipe Diameter
24
Pipe Wall Thickness
0.353
Pipe Smys
70000
Pipe Specification
Api 5l X70
Pipe Seam Type
Erw - High Frequency
Pipe Manufacturer
Unknown
Pipe Coating Type
Fusion Bonded Epoxy(Fbe)
Coating Applied Ind
No
Installation Year
2018
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Crack
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
2500
Est Cost Prop Damage
235000
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
0
Prpty
237500
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
1200
Mop Psig
1480
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
2019-03-09 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Neither controller nor control room contributed to the accident.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Material Failure Of Pipe Or Weld
Cause Details
Design-, Construction-, Installation-, Or Fabrication-Related
Field Exam Ind
Yes
Metallurgical Ind
Yes
Failure Type
Design-, Construction-, Installation-, Or Fabrication-Related
Fatigue Vibr Related
Yes
Failure Subtype
Other
Fatigue Vibr Related Other
Fatigue - Crack Originated At Mechanical Imperfection Or Anomaly.
Additional Crack Ind
Yes
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Preparer Name
T****** A* G********
Preparer Title
Senior Staff Pipeline Compliance Engineer
Preparer Email
T**********@e****.com
Preparer Telephone
713-381-6433
Prepared Date
2024-11-19 00:00:00
Local Contact Name
T****** A* G********
Local Contact Email
Senior Staff Pipeline Compliance Engineer
Local Contact Telephone
713-381-6433
Authorizer Name
T****** A* G********
Authorizer Telephone
713-381-6433
Authorizer Title
Senior Staff Pipeline Compliance Engineer
Authorizer Email
T**********@e****.com
Narrative
At 09:44 cdt on 9/1/2024 a third party called the enterprise pipeline control center to report a possible vapor cloud at the shin oak cross plains pump station. The pump station was then immediately isolated and bypassed. An enterprise pipeline technician arrived on site at 11:30 cdt on 9/1/2024 and observed a small ice ball on the station discharge piping. The piping was blown down, and a crack was observed where the ice ball had been found. On 9/2/2024 at 08:15 cdt the decision was made that a section of piping would need to be cut out and replaced, resulting in repair costs exceeding $50,000. Results of metallurgical analysis indicated a fatigue crack that originated at a mechanical imperfection or anomaly at the toe of the weld joining an elbow fitting to the discharge piping. Nrc #1409698, 48-hour update #1409829.
Report Received Date 2024-09-25 00:00:00
Iyear 2024
Report Number 20240227
Supplemental Number 40232
Report Type Supplemental Final
Operator Id 31618 PHMSA Enforcement
Name Enterprise Products Operating Llc
Operator Street Address 1100 Louisiana Street
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 32.1047889 Google Maps OpenStreetMap
Location Longitude -99.227858 Google Maps OpenStreetMap
Commodity Released Type Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls 0.1
Intentional Release Bbls 80
Recovered Bbls 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Notification From Public
System Part Involved Onshore Pump/meter Station Equipment And Piping
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind No
Shutdown Explain Pump Station Was Isolated And Bypassed.
Communication State Fed Ind No
Nrc Rpt Num 1409698 NRC Report How to search
Additional Nrc Report Numbers 1409829
Ignite Ind No
Num Pub Evacuated 0
Pipe Fac Name Shin Oak Pipeline/cross Plains Pump Station
Segment Name 1050
Onshore State Abbreviation Tx
Onshore Postal Code 76443
Onshore City Name Cross Plains
Onshore County Name Callahan
Designated Location Milepost
Designated Name 296
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Intrastate
Item Involved Pipe
Pipe Type Pipe Body
Puddle Weld Ind No
Pipe Diameter 24
Pipe Wall Thickness 0.353
Pipe Smys 70000
Pipe Specification Api 5l X70
Pipe Seam Type Erw - High Frequency
Pipe Manufacturer Unknown
Pipe Coating Type Fusion Bonded Epoxy(Fbe)
Coating Applied Ind No
Installation Year 2018
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Leak
Leak Type Crack
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca No
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 2500
Est Cost Prop Damage 235000
Est Cost Emergency 0
Est Cost Environmental 0
Est Cost Other 0
Prpty 237500
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 1200
Mop Psig 1480
Mop Cfr Section Component Design Pressure �195.406(A)(2) View CFR 49 §192
Maop Established Date 2019-03-09 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind Yes
Cpm Operating Ind Yes
Cpm Functional Ind Yes
Cpm Detection Ind No
Cpm Conf Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details Neither controller nor control room contributed to the accident.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Material Failure Of Pipe Or Weld
Cause Details Design-, Construction-, Installation-, Or Fabrication-Related
Field Exam Ind Yes
Metallurgical Ind Yes
Failure Type Design-, Construction-, Installation-, Or Fabrication-Related
Fatigue Vibr Related Yes
Failure Subtype Other
Fatigue Vibr Related Other Fatigue - Crack Originated At Mechanical Imperfection Or Anomaly.
Additional Crack Ind Yes
Collected Data Ind No
Has Hydrtst Conduc Before Ind No
Direct Asmnt Conducted No
Non Destructive Exam Ind No
Preparer Name T****** A* G********
Preparer Title Senior Staff Pipeline Compliance Engineer
Preparer Email T**********@e****.com
Preparer Telephone 713-381-6433
Prepared Date 2024-11-19 00:00:00
Local Contact Name T****** A* G********
Local Contact Email Senior Staff Pipeline Compliance Engineer
Local Contact Telephone 713-381-6433
Authorizer Name T****** A* G********
Authorizer Telephone 713-381-6433
Authorizer Title Senior Staff Pipeline Compliance Engineer
Authorizer Email T**********@e****.com
Narrative At 09:44 cdt on 9/1/2024 a third party called the enterprise pipeline control center to report a possible vapor cloud at the shin oak cross plains pump station. The pump station was then immediately isolated and bypassed. An enterprise pipeline technician arrived on site at 11:30 cdt on 9/1/2024 and observed a small ice ball on the station discharge piping. The piping was blown down, and a crack was observed where the ice ball had been found. On 9/2/2024 at 08:15 cdt the decision was made that a section of piping would need to be cut out and replaced, resulting in repair costs exceeding $50,000. Results of metallurgical analysis indicated a fatigue crack that originated at a mechanical imperfection or anomaly at the toe of the weld joining an elbow fitting to the discharge piping. Nrc #1409698, 48-hour update #1409829.