HL incident on 2024-09-18 — TX

Operator
Energy Transfer Company
Cause
Other Accident Cause
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$225,580
Incident datetime
2024-09-18 00:00 UTC
Report number
Location
TX
Narrative
On 8/20/2024 at 08:57, operations received a notification concerning visible product leaking from a sidewalk on 13002 cmar-ctol-16inch line. Line was immediately shutdown and isolated. Approximately 5 barrels of crude oil was released. An osro was mobilized to cleanup free product and contaminated soil. The failed pipe was cutout and replaced. The line was restarted on 8/24/2024 at 09:45. The cause of the leak is still under investigation. A supplemental report will be submitted once the investigation is complete.
Detailed record list
Report Received Date
2024-09-18 00:00:00
Iyear
2024
Report Number
20240219
Supplemental Number
40008
Report Type
Original
Operator Id
Name
Energy Transfer Company
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Crude Oil
Unintentional Release Bbls
5
Recovered Bbls
5
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Notification From Public
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Communication State Fed Ind
No
Nrc Rpt Num
Additional Nrc Report Numbers
1408663
Ignite Ind
No
Upstream Action Taken
Valve Closure
Upstream Valve Type Ind
Manual
Downstream Action Taken
Valve Closure
Downstream Valve Type Ind
Manual
Notify Qualified Indiv Ind
Yes
Oil Spill Removal Org Ind
Yes
Osro Arrived On Site Dt
8/20/2024 12:10
Num Pub Evacuated
0
Pipe Fac Name
Marysville To Toledo
Segment Name
13002 Cmar-Ctol-16inch
Onshore State Abbreviation
Mi
Onshore Postal Code
48154
Onshore City Name
Livonia
Onshore County Name
Wayne
Designated Location
Survey Station No.
Designated Name
344498.8
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
42
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Pipe
Pipe Type
Pipe Body
Puddle Weld Ind
No
Pipe Diameter
16
Pipe Wall Thickness
0.25
Pipe Smys
60000
Pipe Specification
X-60
Pipe Seam Type
Erw - High Frequency
Pipe Manufacturer
Republic Steel
Pipe Coating Type
Coal Tar
Coating Applied Ind
Yes
Installation Year
1967
Manufactured Year
1967
Material Involved
Carbon Steel
Release Type
Other
Release Type Details
Still Under Investigation
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
18000
Est Cost Gas Released
360
Est Cost Prop Damage
225580
Est Cost Emergency
155995
Est Cost Environmental
275000
Est Cost Other
0
Prpty
674935
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
1205
Mop Psig
1300
Mop Cfr Section
Subpart E Pressure Test �195.406(A)(3)
Maop Established Date
1987-04-21 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Length Segment Isolated
55986
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
A review of the accident determined that there were no control room actions that contributed to the event.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Accident Cause
Cause Details
Unknown
Other Type
Unknown
Unknown Subtype
Still Under Investigation, Cause Of Accident To Be Determined* (*supplemental Report Required)
Preparer Name
T*** N*******
Preparer Title
Director - Dot Compliance
Preparer Email
T************@e*************.com
Preparer Telephone
713-989-7126
Prepared Date
2024-09-18 00:00:00
Authorizer Name
T*** N*******
Authorizer Telephone
713-989-7126
Authorizer Title
Director - Dot Compliance
Authorizer Email
T************@e*************.com
Narrative
On 8/20/2024 at 08:57, operations received a notification concerning visible product leaking from a sidewalk on 13002 cmar-ctol-16inch line. Line was immediately shutdown and isolated. Approximately 5 barrels of crude oil was released. An osro was mobilized to cleanup free product and contaminated soil. The failed pipe was cutout and replaced. The line was restarted on 8/24/2024 at 09:45. The cause of the leak is still under investigation. A supplemental report will be submitted once the investigation is complete.
Report Received Date 2024-09-18 00:00:00
Iyear 2024
Report Number 20240219
Supplemental Number 40008
Report Type Original
Operator Id 32099 PHMSA Enforcement
Name Energy Transfer Company
Operator Street Address 1300 Main Street
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Time Zone Eastern
Daylight Savings Ind Yes
Location Latitude 42.384495 Google Maps OpenStreetMap
Location Longitude -83.353622 Google Maps OpenStreetMap
Commodity Released Type Crude Oil
Unintentional Release Bbls 5
Recovered Bbls 5
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Notification From Public
System Part Involved Onshore Pipeline, Including Valve Sites
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind Yes
Communication State Fed Ind No
Nrc Rpt Num 1408478 NRC Report How to search
Additional Nrc Report Numbers 1408663
Ignite Ind No
Upstream Action Taken Valve Closure
Upstream Valve Type Ind Manual
Downstream Action Taken Valve Closure
Downstream Valve Type Ind Manual
Notify Qualified Indiv Ind Yes
Oil Spill Removal Org Ind Yes
Osro Arrived On Site Dt 8/20/2024 12:10
Num Pub Evacuated 0
Pipe Fac Name Marysville To Toledo
Segment Name 13002 Cmar-Ctol-16inch
Onshore State Abbreviation Mi
Onshore Postal Code 48154
Onshore City Name Livonia
Onshore County Name Wayne
Designated Location Survey Station No.
Designated Name 344498.8
Federal No
Location Type Pipeline Right-Of-Way
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover 42
Crossing No
Pipe Facility Type Interstate
Item Involved Pipe
Pipe Type Pipe Body
Puddle Weld Ind No
Pipe Diameter 16
Pipe Wall Thickness 0.25
Pipe Smys 60000
Pipe Specification X-60
Pipe Seam Type Erw - High Frequency
Pipe Manufacturer Republic Steel
Pipe Coating Type Coal Tar
Coating Applied Ind Yes
Installation Year 1967
Manufactured Year 1967
Material Involved Carbon Steel
Release Type Other
Release Type Details Still Under Investigation
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment No
Remediation Ind Yes
Soil Remed Ind Yes
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca Yes
High Pop Ind Yes
High Pop Yes No Yes
Est Cost Oper Paid 18000
Est Cost Gas Released 360
Est Cost Prop Damage 225580
Est Cost Emergency 155995
Est Cost Environmental 275000
Est Cost Other 0
Prpty 674935
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 1205
Mop Psig 1300
Mop Cfr Section Subpart E Pressure Test �195.406(A)(3) View CFR 49 §192
Maop Established Date 1987-04-21 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Length Segment Isolated 55986
Internal Inspection Ind Yes
Operation Complications Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind Yes
Cpm Operating Ind Yes
Cpm Functional Ind Yes
Cpm Detection Ind No
Cpm Conf Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details A review of the accident determined that there were no control room actions that contributed to the event.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Other Accident Cause
Cause Details Unknown
Other Type Unknown
Unknown Subtype Still Under Investigation, Cause Of Accident To Be Determined* (*supplemental Report Required)
Preparer Name T*** N*******
Preparer Title Director - Dot Compliance
Preparer Email T************@e*************.com
Preparer Telephone 713-989-7126
Prepared Date 2024-09-18 00:00:00
Authorizer Name T*** N*******
Authorizer Telephone 713-989-7126
Authorizer Title Director - Dot Compliance
Authorizer Email T************@e*************.com
Narrative On 8/20/2024 at 08:57, operations received a notification concerning visible product leaking from a sidewalk on 13002 cmar-ctol-16inch line. Line was immediately shutdown and isolated. Approximately 5 barrels of crude oil was released. An osro was mobilized to cleanup free product and contaminated soil. The failed pipe was cutout and replaced. The line was restarted on 8/24/2024 at 09:45. The cause of the leak is still under investigation. A supplemental report will be submitted once the investigation is complete.