Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2024-08-02 — TX
Operator
Energy Transfer Nederland Terminal Llc
Cause
Incorrect Operation
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$26,000
Incident datetime
2024-08-02 00:00 UTC
Report number
Location
TX
Narrative
On 7/13/24 at approximately 04:00, a crude oil release occurred within the texoma manifold. Operations personnel were immediately dispatched to the area of the release to assess the situation and begin cleanup. It was determined that tank 1541 tank gate valve was not opened in sequence, which caused an overpressure of the seaway 30-inch transfer line. The pipeline overpressure caused the shutdown valve to block in automatically and stop the flow of crude. Approximately one (1) barrel of crude oil was released. On-site contractors cleaned-up released product. Gaskets were replaced. All flanges were torqued to spec and checked for leaks. The line was static pressure tested and was monitored for leaks prior to restart. The cause of the leak was an overpressure due to the local facility control room operator's failure to follow procedure. Operator was sent for drug and alcohol testing (negative) and oq was suspended and the individual will be retrained to prevent reoccurrence.
Detailed record list
Report Received Date
2024-08-02 00:00:00
Iyear
2024
Report Number
20240180
Supplemental Number
39854
Report Type
Original Final
Operator Id
39706
Name
Energy Transfer Nederland Terminal Llc
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
29.994989
Location Longitude
-93.9926
Commodity Released Type
Crude Oil
Unintentional Release Bbls
1
Recovered Bbls
1
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Communication State Fed Ind
No
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Nederland Terminal
Segment Name
Seaway 30-Inch
Onshore State Abbreviation
Tx
Onshore Postal Code
77627
Onshore City Name
Nederland
Onshore County Name
Jefferson
Designated Location
Survey Station No.
Designated Name
0+00
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Flange Assembly
Installation Year
Unknown
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Connection Failure
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
100
Est Cost Prop Damage
26000
Est Cost Emergency
2500
Est Cost Environmental
1000
Est Cost Other
0
Prpty
29600
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
308
Mop Psig
285
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
2015-01-01 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Exceeded Mop, But Did Not Exceed 110% Of Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest Incorrect Action Ind
Yes
Employee Drug Test Ind
Yes
Contractor Drug Test Ind
No
Num Employees Tested
1
Num Employees Failed
0
Cause
Incorrect Operation
Cause Details
Pipeline Or Equipment Overpressured
Operation Type
Pipeline Or Equipment Overpressured
Related Failure Follow Ind
Yes
Category Type
Normal Operating Conditions
Operator Qualification Ind
Yes
Qualified Individuals
Yes, They Were Qualified For The Task(S)
Preparer Name
T*** N*******
Preparer Title
Director - Dot Compliance
Preparer Email
T************@e*************.com
Preparer Telephone
713-989-7126
Prepared Date
2024-08-01 00:00:00
Authorizer Name
T*** N*******
Authorizer Telephone
713-989-7126
Authorizer Title
Director - Dot Compliance
Authorizer Email
T************@e*************.com
Narrative
On 7/13/24 at approximately 04:00, a crude oil release occurred within the texoma manifold. Operations personnel were immediately dispatched to the area of the release to assess the situation and begin cleanup. It was determined that tank 1541 tank gate valve was not opened in sequence, which caused an overpressure of the seaway 30-inch transfer line. The pipeline overpressure caused the shutdown valve to block in automatically and stop the flow of crude. Approximately one (1) barrel of crude oil was released. On-site contractors cleaned-up released product. Gaskets were replaced. All flanges were torqued to spec and checked for leaks. The line was static pressure tested and was monitored for leaks prior to restart. The cause of the leak was an overpressure due to the local facility control room operator's failure to follow procedure. Operator was sent for drug and alcohol testing (negative) and oq was suspended and the individual will be retrained to prevent reoccurrence.
Report Received Date | 2024-08-02 00:00:00 |
---|---|
Iyear | 2024 |
Report Number | 20240180 |
Supplemental Number | 39854 |
Report Type | Original Final |
Operator Id | 39706 PHMSA Enforcement |
Name | Energy Transfer Nederland Terminal Llc |
Operator Street Address | 1300 Main Street |
Operator City Name | Houston |
Operator State Abbreviation | TX |
Operator Postal Code | 77002 |
Time Zone | Central |
Daylight Savings Ind | Yes |
Location Latitude | 29.994989 Google Maps OpenStreetMap |
Location Longitude | -93.9926 Google Maps OpenStreetMap |
Commodity Released Type | Crude Oil |
Unintentional Release Bbls | 1 |
Recovered Bbls | 1 |
Fatality Ind | No |
Fatal | 0 |
Injury Ind | No |
Injure | 0 |
Accident Identifier | Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations) |
System Part Involved | Onshore Terminal/tank Farm Equipment And Piping |
On Off Shore | Onshore |
Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
Shutdown Due Accident Ind | Yes |
Communication State Fed Ind | No |
Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
Ignite Ind | No |
Notify Qualified Indiv Ind | Yes |
Oil Spill Removal Org Ind | No |
Num Pub Evacuated | 0 |
Pipe Fac Name | Nederland Terminal |
Segment Name | Seaway 30-Inch |
Onshore State Abbreviation | Tx |
Onshore Postal Code | 77627 |
Onshore City Name | Nederland |
Onshore County Name | Jefferson |
Designated Location | Survey Station No. |
Designated Name | 0+00 |
Federal | No |
Location Type | Totally Contained On Operator-Controlled Property |
Incident Area Type | Aboveground |
Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
Crossing | No |
Pipe Facility Type | Interstate |
Item Involved | Flange Assembly |
Installation Year | Unknown |
Manufactured Year | Unknown |
Material Involved | Carbon Steel |
Release Type | Leak |
Leak Type | Connection Failure |
Wildlife Impact Ind | No |
Soil Contamination | No |
Long Term Assessment | No |
Remediation Ind | No |
Water Contam Ind | No |
Could Be Hca | Yes |
Commodity Reached Hca | Yes |
High Pop Ind | Yes |
High Pop Yes No | Yes |
Est Cost Oper Paid | 0 |
Est Cost Gas Released | 100 |
Est Cost Prop Damage | 26000 |
Est Cost Emergency | 2500 |
Est Cost Environmental | 1000 |
Est Cost Other | 0 |
Prpty | 29600 |
Num Persons Hosp Not Ovnght | 0 |
Num Injured Treated By Emt | 0 |
Num Resident Building Affctd | 0 |
Num Business Building Affctd | 0 |
Accident Psig | 308 |
Mop Psig | 285 |
Mop Cfr Section | Component Design Pressure �195.406(A)(2) View CFR 49 §192 |
Maop Established Date | 2015-01-01 00:00:00 |
Maop Reversal Flow Ind | No |
Accident Pressure | Pressure Exceeded Mop, But Did Not Exceed 110% Of Mop |
Pressure Restriction Ind | No |
Pipeline Function | > 20% Smys Regulated Transmission |
Scada In Place Ind | Yes |
Scada Operating Ind | Yes |
Scada Functional Ind | Yes |
Scada Detection Ind | Yes |
Scada Conf Ind | Yes |
Cpm In Place Ind | Yes |
Cpm Operating Ind | Yes |
Cpm Functional Ind | Yes |
Cpm Detection Ind | No |
Cpm Conf Ind | No |
Investigation Status | Yes, specify investigation result(s): (select all that apply) |
Invest Incorrect Action Ind | Yes |
Employee Drug Test Ind | Yes |
Contractor Drug Test Ind | No |
Num Employees Tested | 1 |
Num Employees Failed | 0 |
Cause | Incorrect Operation |
Cause Details | Pipeline Or Equipment Overpressured |
Operation Type | Pipeline Or Equipment Overpressured |
Related Failure Follow Ind | Yes |
Category Type | Normal Operating Conditions |
Operator Qualification Ind | Yes |
Qualified Individuals | Yes, They Were Qualified For The Task(S) |
Preparer Name | T*** N******* |
Preparer Title | Director - Dot Compliance |
Preparer Email | T************@e*************.com |
Preparer Telephone | 713-989-7126 |
Prepared Date | 2024-08-01 00:00:00 |
Authorizer Name | T*** N******* |
Authorizer Telephone | 713-989-7126 |
Authorizer Title | Director - Dot Compliance |
Authorizer Email | T************@e*************.com |
Narrative | On 7/13/24 at approximately 04:00, a crude oil release occurred within the texoma manifold. Operations personnel were immediately dispatched to the area of the release to assess the situation and begin cleanup. It was determined that tank 1541 tank gate valve was not opened in sequence, which caused an overpressure of the seaway 30-inch transfer line. The pipeline overpressure caused the shutdown valve to block in automatically and stop the flow of crude. Approximately one (1) barrel of crude oil was released. On-site contractors cleaned-up released product. Gaskets were replaced. All flanges were torqued to spec and checked for leaks. The line was static pressure tested and was monitored for leaks prior to restart. The cause of the leak was an overpressure due to the local facility control room operator's failure to follow procedure. Operator was sent for drug and alcohol testing (negative) and oq was suspended and the individual will be retrained to prevent reoccurrence. |