GTG incident on 2024-11-11 — TX
Operator
Southern Natural Gas Co
Cause
Incorrect Operation
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$0
Incident datetime
2024-11-11 00:00 UTC
Report number
Location
TX
Narrative
Sng louisville compressor station 4132 improper valve sequence configuration on jd mode of operation. Valve 137 was not configured properly for jd mode sequence. Line pressure exceeded maop of 500 psig initiating over pressure device activation on low side discharge header at louisville compressor station. The highest pressure reached was 524.84 psig. Relief valve blew for 21 minutes an 7 seconds. Calculated gas loss is 4,610.47 mcf and is recordable to PHMSA. No injuries, no contractor involvement, not part of a project.
Detailed record list
Report Received Date
2024-11-11 00:00:00
Iyear
2024
Report Number
20240124
Supplemental Number
40207
Report Type
Original Final
Operator Id
18516
Name
Southern Natural Gas Co
Operator Street Address
1001 Louisiana St, Ste 1000 Suite 1000
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Time Zone
Central
Daylight Savings Ind
No
Location Latitude
33.13480083
Location Longitude
-89.07002652
Nrc Rpt Num
1414112
Commodity Released Type
Natural Gas
Unintentional Release
4611
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
Yes
Communication State Fed Ind
No
Ignite Ind
No
Num Pub Evacuated
0
On Off Shore
Onshore
Onshore State Abbreviation
Ms
Onshore Postal Code
39339
Onshore City Name
Louisville
Onshore County Name
Winston
Designated Location
Not Applicable
Pipe Fac Name
Louisville Compressor Station
Segment Name
Valve 137
Federal
No
Location Type
Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
System Part Involved
Onshore Compressor Station Equipment And Piping
Item Involved
Valve
Valve Type
Relief Valve
Installation Year
Unknown
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Other
Release Type Details
Line Pressure Exceeded Maop Initiating Over Pressure Device Activation On Low Side Discharge Header.
Class Location Type
Class 3 Location
Could Be Hca
No
Pir Radius
370
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
11066
Est Cost Intentional Release
0
Est Cost Prop Damage
0
Est Cost Emergency
0
Est Cost Other
0
Gas Cost In Mcf
2.4
Prpty
11066
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
525
Gas Flow In Pipe In Mcf
2908560
Mop Psig
500
Mop Cfr Section
192.619(A)(2)
Maop Established Date
1948-10-01 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Exceeded Maop, But Did Not Exceed The Applicable Allowance In 192.201
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Investigation Status
Yes, but the investigation of the control room and/or controller actions has not yet been completed by the operator (supplemental report required)
Employee Drug Test Ind
Yes
Contractor Drug Test Ind
No
Num Employees Tested
1
Num Employees Failed
0
Cause
Incorrect Operation
Cause Details
Pipeline Or Equipment Overpressured
Operation Type
Pipeline Or Equipment Overpressured
Related Other Ind
Yes
Operation Related Details
Improper Valve Sequence Configuration On Jd Mode Of Operation. Valve 137 Was Not Configured Properly For Jd Mode Sequence.
Category Type
Normal Operating Conditions
Operator Qualification Ind
Yes
Qualified Individuals
Yes, They Were Qualified For The Task(S)
Preparer Name
R***** B***** I*
Preparer Title
Engineer - Codes And Standards
Preparer Email
R************@k***********.com
Preparer Telephone
713-420-2324
Authorizer Name
Z*** R*****
Authorizer Title
Director - Engineering Codes And Standards
Authorizer Telephone
713-420-2609
Authorizer Email
Z**********@k***********.com
Narrative
Sng louisville compressor station 4132 improper valve sequence configuration on jd mode of operation. Valve 137 was not configured properly for jd mode sequence. Line pressure exceeded maop of 500 psig initiating over pressure device activation on low side discharge header at louisville compressor station. The highest pressure reached was 524.84 psig. Relief valve blew for 21 minutes an 7 seconds. Calculated gas loss is 4,610.47 mcf and is recordable to PHMSA. No injuries, no contractor involvement, not part of a project.
Report Received Date | 2024-11-11 00:00:00 |
---|---|
Iyear | 2024 |
Report Number | 20240124 |
Supplemental Number | 40207 |
Report Type | Original Final |
Operator Id | 18516 PHMSA Enforcement |
Name | Southern Natural Gas Co |
Operator Street Address | 1001 Louisiana St, Ste 1000 Suite 1000 |
Operator City Name | Houston |
Operator State Abbreviation | TX |
Operator Postal Code | 77002 |
Time Zone | Central |
Daylight Savings Ind | No |
Location Latitude | 33.13480083 Google Maps OpenStreetMap |
Location Longitude | -89.07002652 Google Maps OpenStreetMap |
Nrc Rpt Num | 1414112 NRC Report How to search |
Commodity Released Type | Natural Gas |
Unintentional Release | 4611 |
Intentional Release | 0 |
Accompanying Liquid | 0 |
Fatality Ind | No |
Fatal | 0 |
Injury Ind | No |
Injure | 0 |
Status When Identified | Normal Operation, Includes Pauses During Maintenance |
Shutdown Due Accident Ind | Yes |
Communication State Fed Ind | No |
Ignite Ind | No |
Num Pub Evacuated | 0 |
On Off Shore | Onshore |
Onshore State Abbreviation | Ms |
Onshore Postal Code | 39339 |
Onshore City Name | Louisville |
Onshore County Name | Winston |
Designated Location | Not Applicable |
Pipe Fac Name | Louisville Compressor Station |
Segment Name | Valve 137 |
Federal | No |
Location Type | Operator-Controlled Property |
Incident Area Type | Aboveground |
Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
Crossing | No |
Pipe Facility Type | Interstate |
System Part Involved | Onshore Compressor Station Equipment And Piping |
Item Involved | Valve |
Valve Type | Relief Valve |
Installation Year | Unknown |
Manufactured Year | Unknown |
Material Involved | Carbon Steel |
Release Type | Other |
Release Type Details | Line Pressure Exceeded Maop Initiating Over Pressure Device Activation On Low Side Discharge Header. |
Class Location Type | Class 3 Location |
Could Be Hca | No |
Pir Radius | 370 |
Heat Damage Ind | No |
Non Heat Damage Ind | No |
Did Occur In Mca Ind | No |
Est Cost Oper Paid | 0 |
Est Cost Unintentional Release | 11066 |
Est Cost Intentional Release | 0 |
Est Cost Prop Damage | 0 |
Est Cost Emergency | 0 |
Est Cost Other | 0 |
Gas Cost In Mcf | 2.4 |
Prpty | 11066 |
Num Persons Hosp Not Ovnght | 0 |
Num Injured Treated By Emt | 0 |
Num Resident Building Affctd | 0 |
Num Business Building Affctd | 0 |
Wildlife Impact Ind | No |
Accident Psig | 525 |
Gas Flow In Pipe In Mcf | 2908560 |
Mop Psig | 500 |
Mop Cfr Section | 192.619(A)(2) View CFR 49 §192 |
Maop Established Date | 1948-10-01 00:00:00 |
Maop Reversal Flow Ind | No |
Accident Pressure | Pressure Exceeded Maop, But Did Not Exceed The Applicable Allowance In 192.201 |
Pressure Restriction Ind | No |
Gas Required Odorized Ind | No |
Pipeline Function | Transmission System |
Scada In Place Ind | Yes |
Scada Operating Ind | Yes |
Scada Functional Ind | Yes |
Scada Detection Ind | Yes |
Scada Conf Ind | Yes |
Accident Identifier | Local Operating Personnel, Including Contractors |
Operator Type | Operator Employee |
Investigation Status | Yes, but the investigation of the control room and/or controller actions has not yet been completed by the operator (supplemental report required) |
Employee Drug Test Ind | Yes |
Contractor Drug Test Ind | No |
Num Employees Tested | 1 |
Num Employees Failed | 0 |
Cause | Incorrect Operation |
Cause Details | Pipeline Or Equipment Overpressured |
Operation Type | Pipeline Or Equipment Overpressured |
Related Other Ind | Yes |
Operation Related Details | Improper Valve Sequence Configuration On Jd Mode Of Operation. Valve 137 Was Not Configured Properly For Jd Mode Sequence. |
Category Type | Normal Operating Conditions |
Operator Qualification Ind | Yes |
Qualified Individuals | Yes, They Were Qualified For The Task(S) |
Preparer Name | R***** B***** I* |
Preparer Title | Engineer - Codes And Standards |
Preparer Email | R************@k***********.com |
Preparer Telephone | 713-420-2324 |
Authorizer Name | Z*** R***** |
Authorizer Title | Director - Engineering Codes And Standards |
Authorizer Telephone | 713-420-2609 |
Authorizer Email | Z**********@k***********.com |
Narrative | Sng louisville compressor station 4132 improper valve sequence configuration on jd mode of operation. Valve 137 was not configured properly for jd mode sequence. Line pressure exceeded maop of 500 psig initiating over pressure device activation on low side discharge header at louisville compressor station. The highest pressure reached was 524.84 psig. Relief valve blew for 21 minutes an 7 seconds. Calculated gas loss is 4,610.47 mcf and is recordable to PHMSA. No injuries, no contractor involvement, not part of a project. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company
All rights reserved. Copyright © by ClearPHMSA