GTG incident on 2024-09-24 — TX

Operator
Gulf South Pipeline Company, Llc
Cause
Corrosion Failure
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$146,000
Incident datetime
2024-09-24 00:00 UTC
Report number
Location
TX
Narrative
On 8/31/2024, gulf south operations personnel discovered a potential leak while in the bistineau under-ground natural gas storage field. The well designated b-10 was shut in along with block valves on the opposite end of the line segment. The pipeline was depressurized and will remain out of service until repairs are completed. A supplemental report will be submitted once repairs have been made. 1/29/2025 updated to submit final report. Repair was made by pipe replacement and the pipeline was returned to service on 11/16/24. Additionally, PHMSA asked if scada showed a pressure drop or leak indication; it did not because the leak was only a pinhole leak. 3/7/2025 updated per PHMSA request to change the response for question a14 (part of system involved in incident) from "belowground storage, including associated equipment and piping" to "onshore pipeline, including valve sites," and provide response to additional questions resulting from the change.
Detailed record list
Report Received Date
2024-09-24 00:00:00
Iyear
2024
Report Number
20240112
Supplemental Number
40618
Report Type
Supplemental Final
Operator Id
Name
Gulf South Pipeline Company, Llc
Operator Street Address
9 Greenway Plaza Suite 2800
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77046
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Nrc Rpt Num
Additional Nrc Report Numbers
1409655
Commodity Released Type
Natural Gas
Unintentional Release
52
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
Yes
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Ignite Ind
No
Upstream Action Taken
Valve Closure
Downstream Action Taken
Valve Closure
Num Pub Evacuated
0
On Off Shore
Onshore
Onshore State Abbreviation
La
Onshore Postal Code
71068
Onshore City Name
Not Within A Municipality
Onshore County Name
Bienville
Designated Location
Survey Station No.
Designated Name
9+52
Pipe Fac Name
Bistineau Field B-10 Well
Segment Name
Index 901-8
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
36
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Interstate
System Part Involved
Onshore Pipeline, Including Valve Sites
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
8
Puddle Weld Ind
No
Pipe Wall Thickness
0.312
Pipe Smys
52000
Pipe Specification
Api 5lx
Pipe Seam Type
Seamless
Pipe Manufacturer
Us Steel
Pipe Coating Type
Coal Tar
Coating Applied Ind
Unknown
Installation Year
1966
Manufactured Year
1966
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
284
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
99
Est Cost Intentional Release
0
Est Cost Prop Damage
146000
Est Cost Emergency
0
Est Cost Other
0
Gas Cost In Mcf
1.91
Prpty
146099
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
1596
Gas Flow In Pipe In Mcf
4000
Mop Psig
2160
Mop Cfr Section
192.619(A)(1)
Maop Established Date
1970-11-12 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Upstream Valve Type Ind
Manual
Downstream Valve Type Ind
Manual
Length Segment Isolated
1054
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
Transmission In Storage Field
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
Internal Corrosion
Internal External
Internal Corrosion
Int Visual Exam Results
Localized Pitting
Int Corrosive Commodity Ind
Yes
Int Field Exam Basis Ind
Yes
Int Low Point Pipe Loc Ind
Yes
Corrosion Inhibitors
Yes
Corrosion Lining
No
Cleaning Dewatering
No
Corrosion Coupons
No
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Preparer Name
S****** M********
Preparer Title
Compliance Program Leader
Preparer Email
S****************@b**********.com
Preparer Telephone
2709035764
Authorizer Name
T*** B****
Authorizer Title
Manager Compliance Services
Authorizer Telephone
2703146546
Authorizer Email
T*********@b**********.com
Narrative
On 8/31/2024, gulf south operations personnel discovered a potential leak while in the bistineau under-ground natural gas storage field. The well designated b-10 was shut in along with block valves on the opposite end of the line segment. The pipeline was depressurized and will remain out of service until repairs are completed. A supplemental report will be submitted once repairs have been made. 1/29/2025 updated to submit final report. Repair was made by pipe replacement and the pipeline was returned to service on 11/16/24. Additionally, PHMSA asked if scada showed a pressure drop or leak indication; it did not because the leak was only a pinhole leak. 3/7/2025 updated per PHMSA request to change the response for question a14 (part of system involved in incident) from "belowground storage, including associated equipment and piping" to "onshore pipeline, including valve sites," and provide response to additional questions resulting from the change.
Report Received Date 2024-09-24 00:00:00
Iyear 2024
Report Number 20240112
Supplemental Number 40618
Report Type Supplemental Final
Operator Id 31728 PHMSA Enforcement
Name Gulf South Pipeline Company, Llc
Operator Street Address 9 Greenway Plaza Suite 2800
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77046
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 32.373976 Google Maps OpenStreetMap
Location Longitude -93.341737 Google Maps OpenStreetMap
Nrc Rpt Num 1409582 NRC Report How to search
Additional Nrc Report Numbers 1409655
Commodity Released Type Natural Gas
Unintentional Release 52
Intentional Release 0
Accompanying Liquid 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Status When Identified Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind Yes
Communication State Fed Ind Yes
Party Initiated Communication Operator
Ignite Ind No
Upstream Action Taken Valve Closure
Downstream Action Taken Valve Closure
Num Pub Evacuated 0
On Off Shore Onshore
Onshore State Abbreviation La
Onshore Postal Code 71068
Onshore City Name Not Within A Municipality
Onshore County Name Bienville
Designated Location Survey Station No.
Designated Name 9+52
Pipe Fac Name Bistineau Field B-10 Well
Segment Name Index 901-8
Federal No
Location Type Pipeline Right-Of-Way
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover 36
Other Underground Facilities No
Crossing No
Pipe Facility Type Interstate
System Part Involved Onshore Pipeline, Including Valve Sites
Item Involved Pipe
Pipe Type Pipe Body
Pipe Diameter 8
Puddle Weld Ind No
Pipe Wall Thickness 0.312
Pipe Smys 52000
Pipe Specification Api 5lx
Pipe Seam Type Seamless
Pipe Manufacturer Us Steel
Pipe Coating Type Coal Tar
Coating Applied Ind Unknown
Installation Year 1966
Manufactured Year 1966
Material Involved Carbon Steel
Release Type Leak
Leak Type Pinhole
Class Location Type Class 1 Location
Could Be Hca No
Pir Radius 284
Heat Damage Ind No
Non Heat Damage Ind No
Did Occur In Mca Ind No
Est Cost Oper Paid 0
Est Cost Unintentional Release 99
Est Cost Intentional Release 0
Est Cost Prop Damage 146000
Est Cost Emergency 0
Est Cost Other 0
Gas Cost In Mcf 1.91
Prpty 146099
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Wildlife Impact Ind No
Accident Psig 1596
Gas Flow In Pipe In Mcf 4000
Mop Psig 2160
Mop Cfr Section 192.619(A)(1) View CFR 49 §192
Maop Established Date 1970-11-12 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Maop
Pressure Restriction Ind No
Gas Required Odorized Ind No
Upstream Valve Type Ind Manual
Downstream Valve Type Ind Manual
Length Segment Isolated 1054
Internal Inspection Ind Yes
Operation Complications Ind No
Pipeline Function Transmission In Storage Field
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Investigation Status Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind Yes
Invest No Controller Ind Yes
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Corrosion Failure
Cause Details Internal Corrosion
Internal External Internal Corrosion
Int Visual Exam Results Localized Pitting
Int Corrosive Commodity Ind Yes
Int Field Exam Basis Ind Yes
Int Low Point Pipe Loc Ind Yes
Corrosion Inhibitors Yes
Corrosion Lining No
Cleaning Dewatering No
Corrosion Coupons No
Collected Data Ind No
Has Hydrtst Conduc Before Ind No
Direct Asmnt Conducted No
Non Destructive Exam Ind No
Preparer Name S****** M********
Preparer Title Compliance Program Leader
Preparer Email S****************@b**********.com
Preparer Telephone 2709035764
Authorizer Name T*** B****
Authorizer Title Manager Compliance Services
Authorizer Telephone 2703146546
Authorizer Email T*********@b**********.com
Narrative On 8/31/2024, gulf south operations personnel discovered a potential leak while in the bistineau under-ground natural gas storage field. The well designated b-10 was shut in along with block valves on the opposite end of the line segment. The pipeline was depressurized and will remain out of service until repairs are completed. A supplemental report will be submitted once repairs have been made. 1/29/2025 updated to submit final report. Repair was made by pipe replacement and the pipeline was returned to service on 11/16/24. Additionally, PHMSA asked if scada showed a pressure drop or leak indication; it did not because the leak was only a pinhole leak. 3/7/2025 updated per PHMSA request to change the response for question a14 (part of system involved in incident) from "belowground storage, including associated equipment and piping" to "onshore pipeline, including valve sites," and provide response to additional questions resulting from the change.

All rights reserved. Copyright © by ClearPHMSA