GTG incident on 2024-07-23 — TX

Operator
Columbia Gulf Transmission, Llc
Cause
Equipment Failure
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$1,200,000
Incident datetime
2024-07-23 00:00 UTC
Report number
Location
TX
Narrative
On june 25, 2024, at approximately 03:00 hrs. Edt, tc energy gas control received a scada callout-station alarm, esd alarm, 106 alarm for the stanton compressor station. Tc energy operations personnel arrived at the stanton compressor station, located in powell county, kentucky, and discovered that unit 106 had esd'd as designed. It was determined that the incident occurred as result of metal wear within the turbine diffuser housing of unit 106. The metal wear allowed heat to escape and allowed surrounding electrical equipment, such as, wiring, transmitters, and conduit to smolder and melt. The incident was identified by the station's fixed temperature detector system and therefore initiated the esd of unit 106. Unit 106 was shut down due to the incident and is currently shut down until repairs can be made. The stanton compressor station, as a whole, was not shut down due to this incident.
Detailed record list
Report Received Date
2024-07-23 00:00:00
Iyear
2024
Report Number
20240095
Supplemental Number
39811
Report Type
Original
Operator Id
Name
Columbia Gulf Transmission, Llc
Operator Street Address
700 Louisiana St. Suite 700
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Nrc Rpt Num
Additional Nrc Report Numbers
1403056
Commodity Released Type
Natural Gas
Unintentional Release
92.48
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
Yes
Still Shutdown Ind
Yes
Communication State Fed Ind
No
Ignite Ind
No
Num Pub Evacuated
0
On Off Shore
Onshore
Onshore State Abbreviation
Ky
Onshore Postal Code
40380
Onshore City Name
Stanton
Onshore County Name
Powell
Designated Location
Not Applicable
Pipe Fac Name
Stanton Compressor Station
Segment Name
034076
Federal
No
Location Type
Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
System Part Involved
Onshore Compressor Station Equipment And Piping
Item Involved
Compressor
Installation Year
1968
Manufactured Year
1968
Material Involved
Carbon Steel
Release Type
Other
Release Type Details
The Turbine Diffuser Housing Suffered Metal Wear And Thinning, Yielding Small Holes (Approximately 1.5-Inch In Diameter) Allowing Excessive Heat To Escape And Therefore Causing Surrounding Electrical Components, Such As, Wiring, Transmitters, And Conduit.to Smolder And Melt.
Class Location Type
Class 2 Location
Could Be Hca
No
Pir Radius
894
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
Yes
Mca Buildng Human Occupy Ind
Yes
Est Cost Oper Paid
0
Est Cost Unintentional Release
215
Est Cost Intentional Release
0
Est Cost Prop Damage
1200000
Est Cost Emergency
0
Est Cost Other
0
Gas Cost In Mcf
2.33
Prpty
1200215
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
876
Gas Flow In Pipe In Mcf
0
Mop Psig
935
Mop Cfr Section
192.619(A)(1)
Maop Established Date
1969-10-20 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
No
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The turbine diffuser housing suffered metal wear and thinning, yielding small holes (approximately 1.5-inch in diameter) allowing excessive heat to escape and therefore causing surrounding electrical components, such as, wiring, transmitters, and conduit.To smolder and melt.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Compressor Or Compressor-Related Equipment
Eq Failure Type
Compressor Or Compressor-Related Equipment
Other Compressor Ind
Other
Other Compressor Details
The Turbine Diffuser Housing Suffered Metal Wear And Thinning.
Eq Additional Other Ind
Yes
Eq Additional Other Details
The Turbine Diffuser Housing Suffered Metal Wear And Thinning.
Preparer Name
C*** S*******
Preparer Email
C************@t*******.com
Preparer Telephone
2814099257
Authorizer Name
C*** B*****
Authorizer Telephone
3045412170
Authorizer Email
C**********@t*******.com
Narrative
On june 25, 2024, at approximately 03:00 hrs. Edt, tc energy gas control received a scada callout-station alarm, esd alarm, 106 alarm for the stanton compressor station. Tc energy operations personnel arrived at the stanton compressor station, located in powell county, kentucky, and discovered that unit 106 had esd'd as designed. It was determined that the incident occurred as result of metal wear within the turbine diffuser housing of unit 106. The metal wear allowed heat to escape and allowed surrounding electrical equipment, such as, wiring, transmitters, and conduit to smolder and melt. The incident was identified by the station's fixed temperature detector system and therefore initiated the esd of unit 106. Unit 106 was shut down due to the incident and is currently shut down until repairs can be made. The stanton compressor station, as a whole, was not shut down due to this incident.
Report Received Date 2024-07-23 00:00:00
Iyear 2024
Report Number 20240095
Supplemental Number 39811
Report Type Original
Operator Id 2620 PHMSA Enforcement
Name Columbia Gulf Transmission, Llc
Operator Street Address 700 Louisiana St. Suite 700
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Time Zone Eastern
Daylight Savings Ind Yes
Location Latitude 37.889839 Google Maps OpenStreetMap
Location Longitude -83.861828 Google Maps OpenStreetMap
Nrc Rpt Num 1402878 NRC Report How to search
Additional Nrc Report Numbers 1403056
Commodity Released Type Natural Gas
Unintentional Release 92.48
Intentional Release 0
Accompanying Liquid 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Status When Identified Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind Yes
Still Shutdown Ind Yes
Communication State Fed Ind No
Ignite Ind No
Num Pub Evacuated 0
On Off Shore Onshore
Onshore State Abbreviation Ky
Onshore Postal Code 40380
Onshore City Name Stanton
Onshore County Name Powell
Designated Location Not Applicable
Pipe Fac Name Stanton Compressor Station
Segment Name 034076
Federal No
Location Type Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
System Part Involved Onshore Compressor Station Equipment And Piping
Item Involved Compressor
Installation Year 1968
Manufactured Year 1968
Material Involved Carbon Steel
Release Type Other
Release Type Details The Turbine Diffuser Housing Suffered Metal Wear And Thinning, Yielding Small Holes (Approximately 1.5-Inch In Diameter) Allowing Excessive Heat To Escape And Therefore Causing Surrounding Electrical Components, Such As, Wiring, Transmitters, And Conduit.to Smolder And Melt.
Class Location Type Class 2 Location
Could Be Hca No
Pir Radius 894
Heat Damage Ind No
Non Heat Damage Ind No
Did Occur In Mca Ind Yes
Mca Buildng Human Occupy Ind Yes
Est Cost Oper Paid 0
Est Cost Unintentional Release 215
Est Cost Intentional Release 0
Est Cost Prop Damage 1200000
Est Cost Emergency 0
Est Cost Other 0
Gas Cost In Mcf 2.33
Prpty 1200215
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Wildlife Impact Ind No
Accident Psig 876
Gas Flow In Pipe In Mcf 0
Mop Psig 935
Mop Cfr Section 192.619(A)(1) View CFR 49 §192
Maop Established Date 1969-10-20 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Maop
Pressure Restriction Ind No
Gas Required Odorized Ind No
Pipeline Function Transmission System
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind No
Accident Identifier Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details The turbine diffuser housing suffered metal wear and thinning, yielding small holes (approximately 1.5-inch in diameter) allowing excessive heat to escape and therefore causing surrounding electrical components, such as, wiring, transmitters, and conduit.To smolder and melt.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Compressor Or Compressor-Related Equipment
Eq Failure Type Compressor Or Compressor-Related Equipment
Other Compressor Ind Other
Other Compressor Details The Turbine Diffuser Housing Suffered Metal Wear And Thinning.
Eq Additional Other Ind Yes
Eq Additional Other Details The Turbine Diffuser Housing Suffered Metal Wear And Thinning.
Preparer Name C*** S*******
Preparer Email C************@t*******.com
Preparer Telephone 2814099257
Authorizer Name C*** B*****
Authorizer Telephone 3045412170
Authorizer Email C**********@t*******.com
Narrative On june 25, 2024, at approximately 03:00 hrs. Edt, tc energy gas control received a scada callout-station alarm, esd alarm, 106 alarm for the stanton compressor station. Tc energy operations personnel arrived at the stanton compressor station, located in powell county, kentucky, and discovered that unit 106 had esd'd as designed. It was determined that the incident occurred as result of metal wear within the turbine diffuser housing of unit 106. The metal wear allowed heat to escape and allowed surrounding electrical equipment, such as, wiring, transmitters, and conduit to smolder and melt. The incident was identified by the station's fixed temperature detector system and therefore initiated the esd of unit 106. Unit 106 was shut down due to the incident and is currently shut down until repairs can be made. The stanton compressor station, as a whole, was not shut down due to this incident.