GD incident on 2024-12-12 — TX

Operator
Texas Gas Service Company, A Division Of One Gas, Inc.
Cause
Notification Issue
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$10,902
Incident datetime
2024-12-12 00:00 UTC
Report number
Location
TX, HIDALGO
Narrative
Third party contractor struck a buried 12" high-pressure distribution main while excavating for stormwater management facilities. Texas gas service shut down the impacted main segment with emergency isolation valves and repaired the damage with a steel sleeve.
Detailed record list
Report Received Date
2024-12-12 00:00:00
Iyear
2024.0
Report Number
20240068.0
Supplemental Number
40625.0
Report Type
Supplemental Final
Operator Id
Name
Texas Gas Service Company, A Division Of One Gas, Inc.
Operator Street Address
1301 Mopac Expressway Suite 400
Operator City Name
Austin
Operator State Abbreviation
TX
Operator Postal Code
78746.0
Time Zone
Central
Daylight Savings Ind
No
Location Street Address
709 W Polk Avenue
Location City Name
Pharr
Location County Name
Hidalgo
Location State Abbreviation
TX
Location Postal Code
78577.0
Location Latitude
Location Longitude
Flow Cont Key Crit Ind
Yes
Nrc Rpt Num
Additional Nrc Report Numbers
1416222.0
Commodity Released Type
Natural Gas
Unintentional Release
4570.0
Intentional Release
30.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Num Pub Evacuated
0.0
Communication State Fed Ind
Yes
Party Initiated Communication
Local/state/federal Emergency Responder
Federal
No
Location Type
Public Property
Incident Area Type
Underground
Incident Area Subtype
Exposed Due To Excavation
Depth Of Cover
78.0
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
Main
Pipe Diameter
12.75
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Steel
Steel Seam Type
Other
Steel Seam Type Details
Unknown
Wt Steel
0.22
Release Type
Mechanical Puncture
Puncture Axial
4.0
Puncture Circum
3.0
Class Location Type
Class 3 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
10902.0
Est Cost Emergency
12739.0
Est Cost Other
12896.0
Est Cost Other Details
Administrative Cost
Gas Cost In Mcf
3.0
Est Cost Unintentional Release
13710.0
Est Cost Intentional Release
90.0
Prpty
50337.0
Commercial Affected
2.0
Industrial Affected
0.0
Residences Affected
7.0
Num Persons Hosp Not Ovnght
0.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
7.0
Num Business Building Affctd
2.0
Accident Psig
173.0
Normal Psig
175.0
Mop Psig
188.0
Mop Cfr Section
192.619(A)(2)
Maop Established Date
2010-08-31 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Injection Pump
Gas Odorized Lvl Not Msrd Ind
Yes
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Caused by third party damage.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Excavation Damage By Third Party
Ex Party Type
Excavation Damage By Third Party
Prior Notification Ind
No
State Law Exempt Ind
No
Notify Cga Dirt
Yes
Public Row Ind
Yes
Public Subtype
State Highway
Joint Trench Ind
No
Cross Bore Ind
No
Depth Of Grade
Measured Depth From Grade
Depth Of Grade Detail
78
Excavator Type
Contractor
Excavator Equipment
Backhoe/trackhoe
Work Performed
Drainage
One Call Notified Ind
No
Locator Type
Contract Locator
Visible Marks
No
Service Interruption
Yes
Service Interruption Hours
19.0
Root Cause Category
Notification Issue
Root Cause Type
No Notification Made To The One-Call Center/811
Preparer Name
B**** W****
Preparer Email
B**********@o*****.com
Authorizer Name
B**** W****
Authorizer Title
Director Of Engineering
Authorizer Telephone
5124071529
Authorizer Email
B**********@o*****.com
Narrative
Third party contractor struck a buried 12" high-pressure distribution main while excavating for stormwater management facilities. Texas gas service shut down the impacted main segment with emergency isolation valves and repaired the damage with a steel sleeve.
Report Received Date 2024-12-12 00:00:00
Iyear 2024.0
Report Number 20240068.0
Supplemental Number 40625.0
Report Type Supplemental Final
Operator Id 18532 PHMSA Enforcement
Name Texas Gas Service Company, A Division Of One Gas, Inc.
Operator Street Address 1301 Mopac Expressway Suite 400
Operator City Name Austin
Operator State Abbreviation TX
Operator Postal Code 78746.0
Time Zone Central
Daylight Savings Ind No
Location Street Address 709 W Polk Avenue
Location City Name Pharr
Location County Name Hidalgo
Location State Abbreviation TX
Location Postal Code 78577.0
Location Latitude 26.206 Google Maps OpenStreetMap
Location Longitude -98.1931 Google Maps OpenStreetMap
Flow Cont Key Crit Ind Yes
Nrc Rpt Num 1416414.0 NRC Report How to search
Additional Nrc Report Numbers 1416222.0
Commodity Released Type Natural Gas
Unintentional Release 4570.0
Intentional Release 30.0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Ignite Ind No
Num Pub Evacuated 0.0
Communication State Fed Ind Yes
Party Initiated Communication Local/state/federal Emergency Responder
Federal No
Location Type Public Property
Incident Area Type Underground
Incident Area Subtype Exposed Due To Excavation
Depth Of Cover 78.0
Other Underground Facilities No
Crossing No
Pipe Facility Type Investor Owned
System Part Involved Main
Pipe Diameter 12.75
Pipe Specification Unknown
Pipe Manufacturer Unknown
Material Involved Steel
Steel Seam Type Other
Steel Seam Type Details Unknown
Wt Steel 0.22
Release Type Mechanical Puncture
Puncture Axial 4.0
Puncture Circum 3.0
Class Location Type Class 3 Location
Est Cost Oper Paid 0.0
Est Cost Prop Damage 10902.0
Est Cost Emergency 12739.0
Est Cost Other 12896.0
Est Cost Other Details Administrative Cost
Gas Cost In Mcf 3.0
Est Cost Unintentional Release 13710.0
Est Cost Intentional Release 90.0
Prpty 50337.0
Commercial Affected 2.0
Industrial Affected 0.0
Residences Affected 7.0
Num Persons Hosp Not Ovnght 0.0
Num Injured Treated By Emt 0.0
Num Resident Building Affctd 7.0
Num Business Building Affctd 2.0
Accident Psig 173.0
Normal Psig 175.0
Mop Psig 188.0
Mop Cfr Section 192.619(A)(2) View CFR 49 §192
Maop Established Date 2010-08-31 00:00:00
Accident Pressure Pressure Did Not Exceed Maop
Gas Odorized System Type Injection Pump
Gas Odorized Lvl Not Msrd Ind Yes
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind Yes
Accident Identifier Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details Caused by third party damage.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Excavation Damage
Cause Details Excavation Damage By Third Party
Ex Party Type Excavation Damage By Third Party
Prior Notification Ind No
State Law Exempt Ind No
Notify Cga Dirt Yes
Public Row Ind Yes
Public Subtype State Highway
Joint Trench Ind No
Cross Bore Ind No
Depth Of Grade Measured Depth From Grade
Depth Of Grade Detail 78
Excavator Type Contractor
Excavator Equipment Backhoe/trackhoe
Work Performed Drainage
One Call Notified Ind No
Locator Type Contract Locator
Visible Marks No
Service Interruption Yes
Service Interruption Hours 19.0
Root Cause Category Notification Issue
Root Cause Type No Notification Made To The One-Call Center/811
Preparer Name B**** W****
Preparer Email B**********@o*****.com
Authorizer Name B**** W****
Authorizer Title Director Of Engineering
Authorizer Telephone 5124071529
Authorizer Email B**********@o*****.com
Narrative Third party contractor struck a buried 12" high-pressure distribution main while excavating for stormwater management facilities. Texas gas service shut down the impacted main segment with emergency isolation valves and repaired the damage with a steel sleeve.

All rights reserved. Copyright © by ClearPHMSA