GD incident on 2024-10-23 — NY

Operator
Consolidated Edison Co Of New York
Cause
Equipment Failure
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$738,648
Incident datetime
2024-10-23 00:00 UTC
Report number
Location
NY, BRONX
Narrative
On 9/22/24 at 09:47, the fire department of the city of new york (fdny) called con edison's gas emergency response center (gerc) and reported that they were on location with a ruptured gas main at the intersection of bedford park boulevard and webster avenue in the bronx. Con edison's gerc immediately initiated a multiple resource response event (code murre) and dispatched multiple personnel to the location from several departments, including gas distribution services (gds), gas emergency response force (erf) construction, leak survey, and its gas emergency response group (erg). At 09:47, con edison's gas control group reported receiving a low-pressure alarm at gas regulator station gr-110, which supplies the same area. Con edison gds personnel arrived on location at 09:57 and began investigating. The fdny was already on location. At 10:00, gds personnel reported a blowing gas condition from under a steel plate at the intersection of bedford park boulevard and webster avenue. At 10:07, con edison's gerc identified high-pressure main valves (7707, 7708 and 8740) for isolating the high-pressure steel gas supply main at that location (12-inch steel, installed in 1977). At 12:00, gds closed the main valves, thereby isolating the affected supply main and eliminating the blowing gas condition. The incident resulted in 31 service line interruptions affecting 767 customers with no other system impact. Con edison received a total of ninety-four (94) related gas odor complaints. Con edison investigated each complaint and found all to be associated with the incident. Con edison's gas engineering group determined that approximately seventeen million cubic feet of natural gas was lost during the incident. Three members of the public were transported to an unknown hospital with illnesses potentially related to the incident. Repairs were made and customers were fully restored at 17:25 on 9/24/2024. Con edison notified the department of public service staff (dps staff), the new york city department of environmental protection (nycdep), and the u.S. Department of transportation (usdot). Multiple media outlets were on location during the incident.
Detailed record list
Report Received Date
2024-10-23 00:00:00
Iyear
2024.0
Report Number
20240055.0
Supplemental Number
40602.0
Report Type
Supplemental Final
Operator Id
Name
Consolidated Edison Co Of New York
Operator Street Address
4 Irving Place
Operator City Name
New York
Operator State Abbreviation
NY
Operator Postal Code
10003.0
Time Zone
Eastern
Daylight Savings Ind
No
Location Street Address
Intersection Of Bedford Park Blvd And Webster Avenue
Location City Name
New York
Location County Name
Bronx
Location State Abbreviation
NY
Location Postal Code
10458.0
Location Latitude
Location Longitude
Flow Cont Main Valve Ind
Yes
Nrc Rpt Num
Additional Nrc Report Numbers
141585.0
Commodity Released Type
Natural Gas
Unintentional Release
16985.0
Intentional Release
0.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Num Pub Evacuated
0.0
Federal
No
Location Type
Public Property
Incident Area Type
Underground
Incident Area Subtype
Exposed Due To Excavation
Depth Of Cover
36.0
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Privately Owned
System Part Involved
Main
Installation Year
1977.0
Pipe Diameter
12.0
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Steel
Steel Seam Type
Other
Steel Seam Type Details
Unknown
Release Type
Leak
Leak Type
Connection Failure
Class Location Type
Class 4 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
738648.0
Est Cost Emergency
37148.0
Est Cost Other
0.0
Gas Cost In Mcf
1.55
Est Cost Unintentional Release
26327.0
Est Cost Intentional Release
0.0
Prpty
802123.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
31.0
Num Persons Hosp Not Ovnght
0.0
Num Injured Treated By Emt
3.0
Num Resident Building Affctd
31.0
Num Business Building Affctd
0.0
Accident Psig
64.0
Normal Psig
64.0
Mop Psig
89.0
Mop Cfr Section
192.619(A)(1)
Maop Established Date
2015-03-26 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Odorized By Others
Gas Odorized Lvl Not Msrd Ind
Yes
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Non-restraining coupling leaked causing a blowing gas condition
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Non-Threaded Connection Failure
Eq Failure Type
Non-Threaded Connection Failure
Other Non Threaded Ind
Other
Other Non Threaded Details
Non-Restraining Coupling
Preparer Name
R*** B****
Preparer Title
Department Manager
Preparer Email
B*****@c****.com
Preparer Telephone
646-941-0423
Local Contact Name
R*** B****
Local Contact Email
B*****@c****.com
Local Contact Telephone
6469410423
Authorizer Name
R*** B****
Authorizer Telephone
6469410423
Authorizer Email
B*****@c****.com
Narrative
On 9/22/24 at 09:47, the fire department of the city of new york (fdny) called con edison's gas emergency response center (gerc) and reported that they were on location with a ruptured gas main at the intersection of bedford park boulevard and webster avenue in the bronx. Con edison's gerc immediately initiated a multiple resource response event (code murre) and dispatched multiple personnel to the location from several departments, including gas distribution services (gds), gas emergency response force (erf) construction, leak survey, and its gas emergency response group (erg). At 09:47, con edison's gas control group reported receiving a low-pressure alarm at gas regulator station gr-110, which supplies the same area. Con edison gds personnel arrived on location at 09:57 and began investigating. The fdny was already on location. At 10:00, gds personnel reported a blowing gas condition from under a steel plate at the intersection of bedford park boulevard and webster avenue. At 10:07, con edison's gerc identified high-pressure main valves (7707, 7708 and 8740) for isolating the high-pressure steel gas supply main at that location (12-inch steel, installed in 1977). At 12:00, gds closed the main valves, thereby isolating the affected supply main and eliminating the blowing gas condition. The incident resulted in 31 service line interruptions affecting 767 customers with no other system impact. Con edison received a total of ninety-four (94) related gas odor complaints. Con edison investigated each complaint and found all to be associated with the incident. Con edison's gas engineering group determined that approximately seventeen million cubic feet of natural gas was lost during the incident. Three members of the public were transported to an unknown hospital with illnesses potentially related to the incident. Repairs were made and customers were fully restored at 17:25 on 9/24/2024. Con edison notified the department of public service staff (dps staff), the new york city department of environmental protection (nycdep), and the u.S. Department of transportation (usdot). Multiple media outlets were on location during the incident.
Report Received Date 2024-10-23 00:00:00
Iyear 2024.0
Report Number 20240055.0
Supplemental Number 40602.0
Report Type Supplemental Final
Operator Id 2704 PHMSA Enforcement
Name Consolidated Edison Co Of New York
Operator Street Address 4 Irving Place
Operator City Name New York
Operator State Abbreviation NY
Operator Postal Code 10003.0
Time Zone Eastern
Daylight Savings Ind No
Location Street Address Intersection Of Bedford Park Blvd And Webster Avenue
Location City Name New York
Location County Name Bronx
Location State Abbreviation NY
Location Postal Code 10458.0
Location Latitude 40.86803 Google Maps OpenStreetMap
Location Longitude -73.88429 Google Maps OpenStreetMap
Flow Cont Main Valve Ind Yes
Nrc Rpt Num 1411748.0 NRC Report How to search
Additional Nrc Report Numbers 141585.0
Commodity Released Type Natural Gas
Unintentional Release 16985.0
Intentional Release 0.0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Ignite Ind No
Num Pub Evacuated 0.0
Federal No
Location Type Public Property
Incident Area Type Underground
Incident Area Subtype Exposed Due To Excavation
Depth Of Cover 36.0
Other Underground Facilities No
Crossing No
Pipe Facility Type Privately Owned
System Part Involved Main
Installation Year 1977.0
Pipe Diameter 12.0
Pipe Specification Unknown
Pipe Manufacturer Unknown
Material Involved Steel
Steel Seam Type Other
Steel Seam Type Details Unknown
Release Type Leak
Leak Type Connection Failure
Class Location Type Class 4 Location
Est Cost Oper Paid 0.0
Est Cost Prop Damage 738648.0
Est Cost Emergency 37148.0
Est Cost Other 0.0
Gas Cost In Mcf 1.55
Est Cost Unintentional Release 26327.0
Est Cost Intentional Release 0.0
Prpty 802123.0
Commercial Affected 0.0
Industrial Affected 0.0
Residences Affected 31.0
Num Persons Hosp Not Ovnght 0.0
Num Injured Treated By Emt 3.0
Num Resident Building Affctd 31.0
Num Business Building Affctd 0.0
Accident Psig 64.0
Normal Psig 64.0
Mop Psig 89.0
Mop Cfr Section 192.619(A)(1) View CFR 49 §192
Maop Established Date 2015-03-26 00:00:00
Accident Pressure Pressure Did Not Exceed Maop
Gas Odorized System Type Odorized By Others
Gas Odorized Lvl Not Msrd Ind Yes
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind Yes
Accident Identifier Notification From Emergency Responder
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details Non-restraining coupling leaked causing a blowing gas condition
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Non-Threaded Connection Failure
Eq Failure Type Non-Threaded Connection Failure
Other Non Threaded Ind Other
Other Non Threaded Details Non-Restraining Coupling
Preparer Name R*** B****
Preparer Title Department Manager
Preparer Email B*****@c****.com
Preparer Telephone 646-941-0423
Local Contact Name R*** B****
Local Contact Email B*****@c****.com
Local Contact Telephone 6469410423
Authorizer Name R*** B****
Authorizer Telephone 6469410423
Authorizer Email B*****@c****.com
Narrative On 9/22/24 at 09:47, the fire department of the city of new york (fdny) called con edison's gas emergency response center (gerc) and reported that they were on location with a ruptured gas main at the intersection of bedford park boulevard and webster avenue in the bronx. Con edison's gerc immediately initiated a multiple resource response event (code murre) and dispatched multiple personnel to the location from several departments, including gas distribution services (gds), gas emergency response force (erf) construction, leak survey, and its gas emergency response group (erg). At 09:47, con edison's gas control group reported receiving a low-pressure alarm at gas regulator station gr-110, which supplies the same area. Con edison gds personnel arrived on location at 09:57 and began investigating. The fdny was already on location. At 10:00, gds personnel reported a blowing gas condition from under a steel plate at the intersection of bedford park boulevard and webster avenue. At 10:07, con edison's gerc identified high-pressure main valves (7707, 7708 and 8740) for isolating the high-pressure steel gas supply main at that location (12-inch steel, installed in 1977). At 12:00, gds closed the main valves, thereby isolating the affected supply main and eliminating the blowing gas condition. The incident resulted in 31 service line interruptions affecting 767 customers with no other system impact. Con edison received a total of ninety-four (94) related gas odor complaints. Con edison investigated each complaint and found all to be associated with the incident. Con edison's gas engineering group determined that approximately seventeen million cubic feet of natural gas was lost during the incident. Three members of the public were transported to an unknown hospital with illnesses potentially related to the incident. Repairs were made and customers were fully restored at 17:25 on 9/24/2024. Con edison notified the department of public service staff (dps staff), the new york city department of environmental protection (nycdep), and the u.S. Department of transportation (usdot). Multiple media outlets were on location during the incident.

All rights reserved. Copyright © by ClearPHMSA