HL incident on 2023-10-06 — TX

Operator
Enbridge Energy, Limited Partnership
Cause
Corrosion Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$10,000
Incident datetime
2023-10-06 00:00 UTC
Report number
Location
TX
Narrative
On september 9, 2023, at 2:09 pm edt the edmonton control center received a building leak detection alarm at the marysville metering station. The control center notified operations personnel of the alarm and a field technician was dispatched to the station. The station isolation command was sent, and marysville metering station was fully shut down and isolated at 2:14 pm edt. At 2:30 pm edt field technician arrived at the station and discovered approximately 25 gallons of crude oil had been released inside the building. The source of the release was confirmed to be a pinhole on the underside of the drain line of strainer vessel 3 on the line 5 meter skid. All released product was contained in the concrete secondary containment beneath the meter skid. The meter was isolated and drained, and product was immediately cleaned up. The cause of the release was identified as internal corrosion due to low/no flow of product in the drain line. The drain line has been removed and blinded off. The meter is currently locked out until repairs can be made at a later date.
Detailed record list
Report Received Date
2023-10-06 00:00:00
Iyear
2023
Report Number
20230237
Supplemental Number
38853
Report Type
Supplemental Final
Operator Id
Name
Enbridge Energy, Limited Partnership
Operator Street Address
915 N Eldridge Parkway, Suite 1100
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77079
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Crude Oil
Unintentional Release Bbls
0.6
Recovered Bbls
0.6
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Communication State Fed Ind
No
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Notify Qualified Indiv Ind
No
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Marysville Metering Station
Segment Name
Line 5 Meter 3
Onshore State Abbreviation
Mi
Onshore Postal Code
48079
Onshore City Name
Marysville
Onshore County Name
St. Clair
Designated Location
Milepost
Designated Name
1732.71
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Inside A Building
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Drain Lines
Installation Year
1992
Manufactured Year
1992
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
52
Est Cost Prop Damage
10000
Est Cost Emergency
5000
Est Cost Environmental
0
Est Cost Other
0
Prpty
15052
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
173
Mop Psig
720
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
1993-03-26 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
Internal Corrosion
Internal External
Internal Corrosion
Int Visual Exam Results
Localized Pitting
Int Other Corrosion Ind
Yes
Int Corrosion Type Details
Low/no Flow Conditions
Int Field Exam Basis Ind
Yes
Int Low Point Pipe Loc Ind
Yes
Corrosion Inhibitors
No
Corrosion Lining
No
Cleaning Dewatering
Not Applicable - Not Mainline Pipe
Corrosion Coupons
Not Applicable - Not Mainline Pipe
Preparer Name
S**** S****
Preparer Title
Advisor Regulatory Compliance
Preparer Email
S**********@e*******.com
Preparer Telephone
7153953620
Prepared Date
2023-11-28 00:00:00
Authorizer Name
L*** S**********
Authorizer Telephone
7153941584
Authorizer Title
Supervisor Regulatory Affairs Compliance
Authorizer Email
L***************@e*******.com
Narrative
On september 9, 2023, at 2:09 pm edt the edmonton control center received a building leak detection alarm at the marysville metering station. The control center notified operations personnel of the alarm and a field technician was dispatched to the station. The station isolation command was sent, and marysville metering station was fully shut down and isolated at 2:14 pm edt. At 2:30 pm edt field technician arrived at the station and discovered approximately 25 gallons of crude oil had been released inside the building. The source of the release was confirmed to be a pinhole on the underside of the drain line of strainer vessel 3 on the line 5 meter skid. All released product was contained in the concrete secondary containment beneath the meter skid. The meter was isolated and drained, and product was immediately cleaned up. The cause of the release was identified as internal corrosion due to low/no flow of product in the drain line. The drain line has been removed and blinded off. The meter is currently locked out until repairs can be made at a later date.
Report Received Date 2023-10-06 00:00:00
Iyear 2023
Report Number 20230237
Supplemental Number 38853
Report Type Supplemental Final
Operator Id 11169 PHMSA Enforcement
Name Enbridge Energy, Limited Partnership
Operator Street Address 915 N Eldridge Parkway, Suite 1100
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77079
Time Zone Eastern
Daylight Savings Ind Yes
Location Latitude 42.9013 Google Maps OpenStreetMap
Location Longitude -82.50885 Google Maps OpenStreetMap
Commodity Released Type Crude Oil
Unintentional Release Bbls 0.6
Recovered Bbls 0.6
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
System Part Involved Onshore Pump/meter Station Equipment And Piping
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind Yes
Communication State Fed Ind No
Nrc Rpt Num Nrc Notification Not Required NRC Report How to search
Ignite Ind No
Notify Qualified Indiv Ind No
Oil Spill Removal Org Ind No
Num Pub Evacuated 0
Pipe Fac Name Marysville Metering Station
Segment Name Line 5 Meter 3
Onshore State Abbreviation Mi
Onshore Postal Code 48079
Onshore City Name Marysville
Onshore County Name St. Clair
Designated Location Milepost
Designated Name 1732.71
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Inside A Building
Crossing No
Pipe Facility Type Interstate
Item Involved Drain Lines
Installation Year 1992
Manufactured Year 1992
Material Involved Carbon Steel
Release Type Leak
Leak Type Pinhole
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 52
Est Cost Prop Damage 10000
Est Cost Emergency 5000
Est Cost Environmental 0
Est Cost Other 0
Prpty 15052
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 173
Mop Psig 720
Mop Cfr Section Component Design Pressure �195.406(A)(2) View CFR 49 §192
Maop Established Date 1993-03-26 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind No
Cpm In Place Ind Yes
Cpm Operating Ind Yes
Cpm Functional Ind Yes
Cpm Detection Ind No
Cpm Conf Ind No
Investigation Status Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind Yes
Invest No Controller Ind Yes
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Corrosion Failure
Cause Details Internal Corrosion
Internal External Internal Corrosion
Int Visual Exam Results Localized Pitting
Int Other Corrosion Ind Yes
Int Corrosion Type Details Low/no Flow Conditions
Int Field Exam Basis Ind Yes
Int Low Point Pipe Loc Ind Yes
Corrosion Inhibitors No
Corrosion Lining No
Cleaning Dewatering Not Applicable - Not Mainline Pipe
Corrosion Coupons Not Applicable - Not Mainline Pipe
Preparer Name S**** S****
Preparer Title Advisor Regulatory Compliance
Preparer Email S**********@e*******.com
Preparer Telephone 7153953620
Prepared Date 2023-11-28 00:00:00
Authorizer Name L*** S**********
Authorizer Telephone 7153941584
Authorizer Title Supervisor Regulatory Affairs Compliance
Authorizer Email L***************@e*******.com
Narrative On september 9, 2023, at 2:09 pm edt the edmonton control center received a building leak detection alarm at the marysville metering station. The control center notified operations personnel of the alarm and a field technician was dispatched to the station. The station isolation command was sent, and marysville metering station was fully shut down and isolated at 2:14 pm edt. At 2:30 pm edt field technician arrived at the station and discovered approximately 25 gallons of crude oil had been released inside the building. The source of the release was confirmed to be a pinhole on the underside of the drain line of strainer vessel 3 on the line 5 meter skid. All released product was contained in the concrete secondary containment beneath the meter skid. The meter was isolated and drained, and product was immediately cleaned up. The cause of the release was identified as internal corrosion due to low/no flow of product in the drain line. The drain line has been removed and blinded off. The meter is currently locked out until repairs can be made at a later date.