HL incident on 2023-08-09 — TX

Operator
Mid - Valley Pipeline Co
Cause
Equipment Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$171,935
Incident datetime
2023-08-09 00:00 UTC
Report number
Location
TX
Narrative
On 7/11/23 at 04:18 the control center received an lel, seal failure and fire suppression system alarm for pump unit 2120 at longview station. The controller shut the pump down and notified local operations personnel. Upon arrival at the station, field personnel observed a release of approximately, 2 gallons of crude oil into secondary containment and noted that the fire suppression system had activated. A mist of crude oil had ignited due to contact with ancillary pump components that were hot. The facility dry chemical fire suppression system activated and extinguished the fire with minimal damage. An investigation determined the release was due to a pump seal failure. The seal failure occurred because of coupling misalignment between the pump and the pump motor which caused vibration. Further, the multilin relay protective unit did not activate and shut the pump down due to vibration automatically as is intended. To prevent reoccurrence, operations is adding logic to shut the pump units down when the multilin loses communication and/or the multilin health check bit is faulted. An engineering analysis will be conducted to determine the best piping modifications to prevent coupling misalignment issues. The pump and motor are being repaired and will be reinstalled along with a new multilin relay protective unit.
Detailed record list
Report Received Date
2023-08-09 00:00:00
Iyear
2023
Report Number
20230182
Supplemental Number
38376
Report Type
Supplemental Final
Operator Id
Name
Mid - Valley Pipeline Co
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Crude Oil
Unintentional Release Bbls
0.1
Recovered Bbls
0.1
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Communication State Fed Ind
No
Nrc Rpt Num
Additional Nrc Report Numbers
1375789
Ignite Ind
Yes
How Extinguished
Other
How Extinguished Other Detail
Automatic Fire Suppression System
Consumed By Fire In Barrels
0.01
Explode Ind
No
Notify Qualified Indiv Ind
Yes
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Longview Station
Segment Name
Unit 2120
Onshore State Abbreviation
Tx
Onshore Postal Code
75604
Onshore City Name
Longview
Onshore County Name
Gregg
Designated Location
Milepost
Designated Name
0+00
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Inside A Building
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Pump
Pump Type
Centrifugal
Pump Service Type
Mainline
Installation Year
Unknown
Manufactured Year
Unknown
Material Involved
Material Other Than Carbon Steel
Material Details
Viton
Release Type
Leak
Leak Type
Seal Or Packing
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
4
Est Cost Prop Damage
171935
Est Cost Emergency
4765
Est Cost Environmental
0
Est Cost Other
0
Prpty
176704
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
558
Mop Psig
936
Mop Cfr Section
Internal Design Pressure �195.406(A)(1)
Maop Established Date
2021-05-03 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Pump Or Pump-Related Equipment
Eq Failure Type
Pump Or Pump-Related Equipment
Other Pump Ind
Seal/packing Failure
Additional Vibration Ind
Yes
Ief Addl Misalignment Ind
Yes
Eqf Control Releaf Ind
Yes
Preparer Name
T*** N*******
Preparer Title
Director - Regulatory Compliance
Preparer Email
T************@e*************.com
Preparer Telephone
713-989-7126
Prepared Date
2023-08-10 00:00:00
Authorizer Name
T*** N*******
Authorizer Telephone
713-989-7126
Authorizer Title
Director - Regulatory Compliance
Authorizer Email
T************@e*************.com
Narrative
On 7/11/23 at 04:18 the control center received an lel, seal failure and fire suppression system alarm for pump unit 2120 at longview station. The controller shut the pump down and notified local operations personnel. Upon arrival at the station, field personnel observed a release of approximately, 2 gallons of crude oil into secondary containment and noted that the fire suppression system had activated. A mist of crude oil had ignited due to contact with ancillary pump components that were hot. The facility dry chemical fire suppression system activated and extinguished the fire with minimal damage. An investigation determined the release was due to a pump seal failure. The seal failure occurred because of coupling misalignment between the pump and the pump motor which caused vibration. Further, the multilin relay protective unit did not activate and shut the pump down due to vibration automatically as is intended. To prevent reoccurrence, operations is adding logic to shut the pump units down when the multilin loses communication and/or the multilin health check bit is faulted. An engineering analysis will be conducted to determine the best piping modifications to prevent coupling misalignment issues. The pump and motor are being repaired and will be reinstalled along with a new multilin relay protective unit.
Report Received Date 2023-08-09 00:00:00
Iyear 2023
Report Number 20230182
Supplemental Number 38376
Report Type Supplemental Final
Operator Id 12470 PHMSA Enforcement
Name Mid - Valley Pipeline Co
Operator Street Address 1300 Main Street
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 32.483611 Google Maps OpenStreetMap
Location Longitude -94.830278 Google Maps OpenStreetMap
Commodity Released Type Crude Oil
Unintentional Release Bbls 0.1
Recovered Bbls 0.1
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
System Part Involved Onshore Pump/meter Station Equipment And Piping
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind Yes
Communication State Fed Ind No
Nrc Rpt Num 1372721 NRC Report How to search
Additional Nrc Report Numbers 1375789
Ignite Ind Yes
How Extinguished Other
How Extinguished Other Detail Automatic Fire Suppression System
Consumed By Fire In Barrels 0.01
Explode Ind No
Notify Qualified Indiv Ind Yes
Oil Spill Removal Org Ind No
Num Pub Evacuated 0
Pipe Fac Name Longview Station
Segment Name Unit 2120
Onshore State Abbreviation Tx
Onshore Postal Code 75604
Onshore City Name Longview
Onshore County Name Gregg
Designated Location Milepost
Designated Name 0+00
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Inside A Building
Crossing No
Pipe Facility Type Interstate
Item Involved Pump
Pump Type Centrifugal
Pump Service Type Mainline
Installation Year Unknown
Manufactured Year Unknown
Material Involved Material Other Than Carbon Steel
Material Details Viton
Release Type Leak
Leak Type Seal Or Packing
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca No
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 4
Est Cost Prop Damage 171935
Est Cost Emergency 4765
Est Cost Environmental 0
Est Cost Other 0
Prpty 176704
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 558
Mop Psig 936
Mop Cfr Section Internal Design Pressure �195.406(A)(1) View CFR 49 §192
Maop Established Date 2021-05-03 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind Yes
Cpm In Place Ind Yes
Cpm Operating Ind Yes
Cpm Functional Ind Yes
Cpm Detection Ind No
Cpm Conf Ind No
Investigation Status Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind Yes
Invest No Controller Ind Yes
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Pump Or Pump-Related Equipment
Eq Failure Type Pump Or Pump-Related Equipment
Other Pump Ind Seal/packing Failure
Additional Vibration Ind Yes
Ief Addl Misalignment Ind Yes
Eqf Control Releaf Ind Yes
Preparer Name T*** N*******
Preparer Title Director - Regulatory Compliance
Preparer Email T************@e*************.com
Preparer Telephone 713-989-7126
Prepared Date 2023-08-10 00:00:00
Authorizer Name T*** N*******
Authorizer Telephone 713-989-7126
Authorizer Title Director - Regulatory Compliance
Authorizer Email T************@e*************.com
Narrative On 7/11/23 at 04:18 the control center received an lel, seal failure and fire suppression system alarm for pump unit 2120 at longview station. The controller shut the pump down and notified local operations personnel. Upon arrival at the station, field personnel observed a release of approximately, 2 gallons of crude oil into secondary containment and noted that the fire suppression system had activated. A mist of crude oil had ignited due to contact with ancillary pump components that were hot. The facility dry chemical fire suppression system activated and extinguished the fire with minimal damage. An investigation determined the release was due to a pump seal failure. The seal failure occurred because of coupling misalignment between the pump and the pump motor which caused vibration. Further, the multilin relay protective unit did not activate and shut the pump down due to vibration automatically as is intended. To prevent reoccurrence, operations is adding logic to shut the pump units down when the multilin loses communication and/or the multilin health check bit is faulted. An engineering analysis will be conducted to determine the best piping modifications to prevent coupling misalignment issues. The pump and motor are being repaired and will be reinstalled along with a new multilin relay protective unit.