HL incident on 2023-08-03 — TX

Operator
Kinder Morgan Wink Pipeline Llc
Cause
Corrosion Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$17,128
Incident datetime
2023-08-03 00:00 UTC
Report number
Location
TX
Narrative
On 07/05/23, a kinder morgan employee noticed a leak inside the wink tank farm coming off the km2 16 inch pipeline station piping and installed temporary repair to stop the leak . The leak was coming from a 8 feet long 10 inch diameter pipe connection at the bottom of the 16 inch pipeline that was blind flanged for a future connection to a tank. An engineering clamp was installed on pipeline on 07/05 and the pipeline was restarted. On 07/06 the km2 pipeline was shut down and isolated, and associated valves and equipment were locked out and tagged out for the drain down operations. On 07/09, the dead leg was cutout and replaced with a hydro tested 16 inch piece of pipe. The pipeline was restarted on 07/10. The failed cutout section of pipe has been sent off to the metallurgical lab. 09/11/2023 update : the metallurgical analysis has been completed and based on the failure analysis report, part g question responses have been updated. The cause of the pinhole leak was determined to be microbiologically influenced corrosion (mic).
Detailed record list
Report Received Date
2023-08-03 00:00:00
Iyear
2023
Report Number
20230176
Supplemental Number
38528
Report Type
Supplemental Final
Operator Id
Name
Kinder Morgan Wink Pipeline Llc
Operator Street Address
1001 Louisiana St, Suite 1000
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Crude Oil
Unintentional Release Bbls
0.5
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Communication State Fed Ind
No
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Notify Qualified Indiv Ind
No
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Wink Tank Farm
Segment Name
Km2
Onshore State Abbreviation
Tx
Onshore Postal Code
79789
Onshore City Name
Wink
Onshore County Name
Winkler
Designated Location
Milepost
Designated Name
Mp 195
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Pipe
Pipe Type
Pipe Body
Puddle Weld Ind
No
Pipe Diameter
10
Pipe Wall Thickness
0.365
Pipe Smys
42000
Pipe Specification
Api 5l; Astm A106
Pipe Seam Type
Seamless
Pipe Manufacturer
Tenaris
Pipe Coating Type
Paint
Coating Applied Ind
Yes
Installation Year
2017
Manufactured Year
2016
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
35
Est Cost Prop Damage
17128
Est Cost Emergency
0
Est Cost Environmental
4424
Est Cost Other
0
Prpty
21587
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
63
Mop Psig
285
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
2017-07-01 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
No
Cpm In Place Ind
No
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the accident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
Internal Corrosion
Internal External
Internal Corrosion
Int Visual Exam Results
Localized Pitting
Int Water Acid Ind
Yes
Int Microbiological Ind
Yes
Int Metallurgical Basis Ind
Yes
Int Dead Leg Loc Ind
Yes
Corrosion Inhibitors
Yes
Corrosion Lining
No
Cleaning Dewatering
Not Applicable - Not Mainline Pipe
Corrosion Coupons
Yes
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Preparer Name
J*** J****
Preparer Title
Manager - Codes And Standards
Preparer Email
J*********@k***********.com
Preparer Telephone
7133698078
Prepared Date
2023-09-11 00:00:00
Authorizer Name
M***** L*******
Authorizer Telephone
713-420-4649
Authorizer Title
Director - Operations And Engineering
Authorizer Email
M**************@k***********.com
Narrative
On 07/05/23, a kinder morgan employee noticed a leak inside the wink tank farm coming off the km2 16 inch pipeline station piping and installed temporary repair to stop the leak . The leak was coming from a 8 feet long 10 inch diameter pipe connection at the bottom of the 16 inch pipeline that was blind flanged for a future connection to a tank. An engineering clamp was installed on pipeline on 07/05 and the pipeline was restarted. On 07/06 the km2 pipeline was shut down and isolated, and associated valves and equipment were locked out and tagged out for the drain down operations. On 07/09, the dead leg was cutout and replaced with a hydro tested 16 inch piece of pipe. The pipeline was restarted on 07/10. The failed cutout section of pipe has been sent off to the metallurgical lab. 09/11/2023 update : the metallurgical analysis has been completed and based on the failure analysis report, part g question responses have been updated. The cause of the pinhole leak was determined to be microbiologically influenced corrosion (mic).
Report Received Date 2023-08-03 00:00:00
Iyear 2023
Report Number 20230176
Supplemental Number 38528
Report Type Supplemental Final
Operator Id 31957 PHMSA Enforcement
Name Kinder Morgan Wink Pipeline Llc
Operator Street Address 1001 Louisiana St, Suite 1000
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 31.770482 Google Maps OpenStreetMap
Location Longitude -103.176936 Google Maps OpenStreetMap
Commodity Released Type Crude Oil
Unintentional Release Bbls 0.5
Recovered Bbls 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
System Part Involved Onshore Terminal/tank Farm Equipment And Piping
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind Yes
Communication State Fed Ind No
Nrc Rpt Num Nrc Notification Not Required NRC Report How to search
Ignite Ind No
Notify Qualified Indiv Ind No
Oil Spill Removal Org Ind No
Num Pub Evacuated 0
Pipe Fac Name Wink Tank Farm
Segment Name Km2
Onshore State Abbreviation Tx
Onshore Postal Code 79789
Onshore City Name Wink
Onshore County Name Winkler
Designated Location Milepost
Designated Name Mp 195
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
Item Involved Pipe
Pipe Type Pipe Body
Puddle Weld Ind No
Pipe Diameter 10
Pipe Wall Thickness 0.365
Pipe Smys 42000
Pipe Specification Api 5l; Astm A106
Pipe Seam Type Seamless
Pipe Manufacturer Tenaris
Pipe Coating Type Paint
Coating Applied Ind Yes
Installation Year 2017
Manufactured Year 2016
Material Involved Carbon Steel
Release Type Leak
Leak Type Pinhole
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment No
Remediation Ind Yes
Soil Remed Ind Yes
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 35
Est Cost Prop Damage 17128
Est Cost Emergency 0
Est Cost Environmental 4424
Est Cost Other 0
Prpty 21587
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 63
Mop Psig 285
Mop Cfr Section Component Design Pressure �195.406(A)(2) View CFR 49 §192
Maop Established Date 2017-07-01 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind No
Cpm In Place Ind No
Investigation Status No, the facility was not monitored by a controller(s) at the time of the accident
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Corrosion Failure
Cause Details Internal Corrosion
Internal External Internal Corrosion
Int Visual Exam Results Localized Pitting
Int Water Acid Ind Yes
Int Microbiological Ind Yes
Int Metallurgical Basis Ind Yes
Int Dead Leg Loc Ind Yes
Corrosion Inhibitors Yes
Corrosion Lining No
Cleaning Dewatering Not Applicable - Not Mainline Pipe
Corrosion Coupons Yes
Collected Data Ind No
Has Hydrtst Conduc Before Ind No
Direct Asmnt Conducted No
Non Destructive Exam Ind No
Preparer Name J*** J****
Preparer Title Manager - Codes And Standards
Preparer Email J*********@k***********.com
Preparer Telephone 7133698078
Prepared Date 2023-09-11 00:00:00
Authorizer Name M***** L*******
Authorizer Telephone 713-420-4649
Authorizer Title Director - Operations And Engineering
Authorizer Email M**************@k***********.com
Narrative On 07/05/23, a kinder morgan employee noticed a leak inside the wink tank farm coming off the km2 16 inch pipeline station piping and installed temporary repair to stop the leak . The leak was coming from a 8 feet long 10 inch diameter pipe connection at the bottom of the 16 inch pipeline that was blind flanged for a future connection to a tank. An engineering clamp was installed on pipeline on 07/05 and the pipeline was restarted. On 07/06 the km2 pipeline was shut down and isolated, and associated valves and equipment were locked out and tagged out for the drain down operations. On 07/09, the dead leg was cutout and replaced with a hydro tested 16 inch piece of pipe. The pipeline was restarted on 07/10. The failed cutout section of pipe has been sent off to the metallurgical lab. 09/11/2023 update : the metallurgical analysis has been completed and based on the failure analysis report, part g question responses have been updated. The cause of the pinhole leak was determined to be microbiologically influenced corrosion (mic).