Narrative description: on 7/7/23 at 15:45, sfpp imperial (PHMSA opid 18092) the shift operator was making rounds and identified product being released from tank ip-16 fill line. Product was coming from a crack at the nipple of a 1" prv (pressure relief system) return line and the tank fill line. The volume released was 26 bbls of jet. Cal state notifications were made and the osro responded to the site. The tank was emptied of the necessary product volume and the leak stopped at 13:00 7/8/23. Repairs were completed and system returned to normal operations at 15:45. 4/11/2024 update: this supplemental final report is being submitted to include updated cause information. Nrc control numbers: initial nrc - non PHMSA criteria - 1372428 update nrc - PHMSA 50k criteria - 1376160 48hr update nrc - 1376321
Detailed record list
Report Received Date
2023-07-31 00:00:00
Iyear
2023
Report Number
20230175
Supplemental Number
39472
Report Type
Supplemental Final
Operator Id
Name
Sfpp, Lp
Operator Street Address
1001 Louisiana St., Suite 1000
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Time Zone
Pacific
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Diesel, Fuel Oil, Kerosene, Jet Fuel
Unintentional Release Bbls
26
Recovered Bbls
22
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
System Part Involved
Onshore Breakout Tank Or Storage Vessel, Including Attached Appurtenances
On Off Shore
Onshore
Status When Identified
Idle
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Nrc Rpt Num
Additional Nrc Report Numbers
1376160, 1376321
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Oil Spill Removal Org Ind
Yes
Osro Arrived On Site Dt
7/7/2023 19:15
Num Pub Evacuated
0
Pipe Fac Name
Sfpp Imperial Terminal
Segment Name
Ip16
Onshore State Abbreviation
Ca
Onshore Postal Code
92251
Onshore City Name
Imperial
Onshore County Name
Imperial
Designated Location
Milepost
Designated Name
Terminal
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Tank, Including Attached Appurtenances
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Tank/vessel
Tank Vessel Subtype
Appurtenance
Tank Type
Atmospheric
Safe Fill Level
43
Safe Fill Level Exceeded Ind
No
Api Std Out Of Service Year
2010
Api Std In Service Year
2022
Installation Year
1964
Manufactured Year
1964
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Crack
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
Yes
Remediation Ind
Yes
Groundwater Remed Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
Yes
Groundwater Contam Ind
Yes
Amount Released
4
Rel Water Name
Imperial Hydrologic Unit
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Usa Drinking Ind
Yes
Usa Drinking Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
757
Est Cost Prop Damage
0
Est Cost Emergency
120000
Est Cost Environmental
52339
Est Cost Other
0
Prpty
173096
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
10
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The controller had no impact on this release.
Employee Drug Test Ind
Yes
Contractor Drug Test Ind
No
Num Employees Tested
1
Num Employees Failed
0
Cause
Material Failure Of Pipe Or Weld
Cause Details
Design-, Construction-, Installation-, Or Fabrication-Related
Metallurgical Ind
Yes
Failure Type
Design-, Construction-, Installation-, Or Fabrication-Related
Fatigue Vibr Related
Yes
Failure Subtype
Other
Fatigue Vibr Related Other
High Cycle Low Stress Fatigue Crack
Additional Crack Ind
Yes
Preparer Name
S**** A W***
Preparer Title
Pipeline Technical Specialist
Preparer Email
W****@k***********.com
Preparer Telephone
5206310711
Prepared Date
2024-04-22 00:00:00
Local Contact Name
M***** M***** J**
Local Contact Email
M********@k***********.com
Local Contact Telephone
1-760-352-0677
Authorizer Name
M****** P****
Authorizer Telephone
2052132026
Authorizer Title
Manager Codes And Standards
Authorizer Email
M************@k***********.com
Narrative
Narrative description: on 7/7/23 at 15:45, sfpp imperial (PHMSA opid 18092) the shift operator was making rounds and identified product being released from tank ip-16 fill line. Product was coming from a crack at the nipple of a 1" prv (pressure relief system) return line and the tank fill line. The volume released was 26 bbls of jet. Cal state notifications were made and the osro responded to the site. The tank was emptied of the necessary product volume and the leak stopped at 13:00 7/8/23. Repairs were completed and system returned to normal operations at 15:45. 4/11/2024 update: this supplemental final report is being submitted to include updated cause information. Nrc control numbers: initial nrc - non PHMSA criteria - 1372428 update nrc - PHMSA 50k criteria - 1376160 48hr update nrc - 1376321
Report Received Date 2023-07-31 00:00:00
Iyear 2023
Report Number 20230175
Supplemental Number 39472
Report Type Supplemental Final
Operator Id 18092 PHMSA Enforcement
Name Sfpp, Lp
Operator Street Address 1001 Louisiana St., Suite 1000
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Time Zone Pacific
Daylight Savings Ind Yes
Location Latitude 32.823887 Google Maps OpenStreetMap
Location Longitude -115.564309 Google Maps OpenStreetMap
Commodity Released Type Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype Diesel, Fuel Oil, Kerosene, Jet Fuel
Unintentional Release Bbls 26
Recovered Bbls 22
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
System Part Involved Onshore Breakout Tank Or Storage Vessel, Including Attached Appurtenances
On Off Shore Onshore
Status When Identified Idle
Communication State Fed Ind Yes
Party Initiated Communication Operator
Nrc Rpt Num 1372428 NRC Report How to search
Additional Nrc Report Numbers 1376160, 1376321
Ignite Ind No
Notify Qualified Indiv Ind Yes
Oil Spill Removal Org Ind Yes
Osro Arrived On Site Dt 7/7/2023 19:15
Num Pub Evacuated 0
Pipe Fac Name Sfpp Imperial Terminal
Segment Name Ip16
Onshore State Abbreviation Ca
Onshore Postal Code 92251
Onshore City Name Imperial
Onshore County Name Imperial
Designated Location Milepost
Designated Name Terminal
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Tank, Including Attached Appurtenances
Crossing No
Pipe Facility Type Intrastate
Item Involved Tank/vessel
Tank Vessel Subtype Appurtenance
Tank Type Atmospheric
Safe Fill Level 43
Safe Fill Level Exceeded Ind No
Api Std Out Of Service Year 2010
Api Std In Service Year 2022
Installation Year 1964
Manufactured Year 1964
Material Involved Carbon Steel
Release Type Leak
Leak Type Crack
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment Yes
Remediation Ind Yes
Groundwater Remed Ind Yes
Soil Remed Ind Yes
Water Contam Ind Yes
Groundwater Contam Ind Yes
Amount Released 4
Rel Water Name Imperial Hydrologic Unit
Could Be Hca Yes
Commodity Reached Hca Yes
High Pop Ind Yes
High Pop Yes No Yes
Usa Drinking Ind Yes
Usa Drinking Yes No Yes
Est Cost Oper Paid 0
Est Cost Gas Released 757
Est Cost Prop Damage 0
Est Cost Emergency 120000
Est Cost Environmental 52339
Est Cost Other 0
Prpty 173096
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 10
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details The controller had no impact on this release.
Employee Drug Test Ind Yes
Contractor Drug Test Ind No
Num Employees Tested 1
Num Employees Failed 0
Cause Material Failure Of Pipe Or Weld
Cause Details Design-, Construction-, Installation-, Or Fabrication-Related
Metallurgical Ind Yes
Failure Type Design-, Construction-, Installation-, Or Fabrication-Related
Fatigue Vibr Related Yes
Failure Subtype Other
Fatigue Vibr Related Other High Cycle Low Stress Fatigue Crack
Additional Crack Ind Yes
Preparer Name S**** A W***
Preparer Title Pipeline Technical Specialist
Preparer Email W****@k***********.com
Preparer Telephone 5206310711
Prepared Date 2024-04-22 00:00:00
Local Contact Name M***** M***** J**
Local Contact Email M********@k***********.com
Local Contact Telephone 1-760-352-0677
Authorizer Name M****** P****
Authorizer Telephone 2052132026
Authorizer Title Manager Codes And Standards
Authorizer Email M************@k***********.com
Narrative Narrative description: on 7/7/23 at 15:45, sfpp imperial (PHMSA opid 18092) the shift operator was making rounds and identified product being released from tank ip-16 fill line. Product was coming from a crack at the nipple of a 1" prv (pressure relief system) return line and the tank fill line. The volume released was 26 bbls of jet. Cal state notifications were made and the osro responded to the site. The tank was emptied of the necessary product volume and the leak stopped at 13:00 7/8/23. Repairs were completed and system returned to normal operations at 15:45. 4/11/2024 update: this supplemental final report is being submitted to include updated cause information. Nrc control numbers: initial nrc - non PHMSA criteria - 1372428 update nrc - PHMSA 50k criteria - 1376160 48hr update nrc - 1376321

All rights reserved. Copyright © by ClearPHMSA