HL incident on 2023-07-21 — TX

Operator
Energy Transfer Nederland Terminal Llc
Cause
Equipment Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$500
Incident datetime
2023-07-21 00:00 UTC
Report number
Location
TX
Narrative
On 6/28/2023 at approximately 07:50, the duty foreman received a call that the front sump at central manifold was overflowing. Local operations personnel responded to the central manifold and stopped all transfers to determine which line the oil was coming from. Approximately, 20 gallons of crude oil released into the sump containment area. Clean-up contractors were dispatched to the area to collect the free product. Investigation determined that 4-inch drain valve was leaking by and bypassing crude oil into the sump causing it to overfill into the containment. Further investigation in the local control room identified that the scada hi sump alarm was not located on the active screen when controlling the central manifold. The alarm was moved to be visible on the active screen to prevent recurrence. A new drain valve was installed, and a vapor blind was installed to block the oil coming from the 26-inch line.
Detailed record list
Report Received Date
2023-07-21 00:00:00
Iyear
2023
Report Number
20230166
Supplemental Number
38300
Report Type
Original Final
Operator Id
Name
Energy Transfer Nederland Terminal Llc
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Crude Oil
Unintentional Release Bbls
0.48
Recovered Bbls
0.48
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
Sump Isolated From The Manifold.
Communication State Fed Ind
No
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Nederland Terminal
Segment Name
Central Manifold 24-Inch
Onshore State Abbreviation
Tx
Onshore Postal Code
77627
Onshore City Name
Nederland
Onshore County Name
Jefferson
Designated Location
Survey Station No.
Designated Name
0+00
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Sump
Installation Year
Unknown
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Overfill Or Overflow
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
55
Est Cost Prop Damage
500
Est Cost Emergency
1500
Est Cost Environmental
0
Est Cost Other
0
Prpty
2055
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
80
Mop Psig
275
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
1980-01-01 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
Yes
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest Schedule Ind
Yes
Invest No Controller Ind
Yes
Invest Other Ind
Yes
Invest Other Ind Details
Sump Alarm Not Displayed On Active Scada Screen When Operating Manifold. After Investigation The Alarm Has Been Moved To The Active Scada Screen To Prevent Recurrence.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Malfunction Of Control/relief Equipment
Eq Failure Type
Malfunction Of Control/relief Equipment
Block Valve Ind
Yes
Eq Additional Other Ind
Yes
Eq Additional Other Details
Wear On Valve Inner Components
Io Tank Vessel Ind
Yes
Preparer Name
T*** N*******
Preparer Title
Director - Regulatory Compliance
Preparer Email
T************@e*************.com
Preparer Telephone
713-989-7126
Prepared Date
2023-07-21 00:00:00
Authorizer Name
T*** N*******
Authorizer Telephone
713-989-7126
Authorizer Title
Director - Regulatory Compliance
Authorizer Email
T************@e*************.com
Narrative
On 6/28/2023 at approximately 07:50, the duty foreman received a call that the front sump at central manifold was overflowing. Local operations personnel responded to the central manifold and stopped all transfers to determine which line the oil was coming from. Approximately, 20 gallons of crude oil released into the sump containment area. Clean-up contractors were dispatched to the area to collect the free product. Investigation determined that 4-inch drain valve was leaking by and bypassing crude oil into the sump causing it to overfill into the containment. Further investigation in the local control room identified that the scada hi sump alarm was not located on the active screen when controlling the central manifold. The alarm was moved to be visible on the active screen to prevent recurrence. A new drain valve was installed, and a vapor blind was installed to block the oil coming from the 26-inch line.
Report Received Date 2023-07-21 00:00:00
Iyear 2023
Report Number 20230166
Supplemental Number 38300
Report Type Original Final
Operator Id 39706 PHMSA Enforcement
Name Energy Transfer Nederland Terminal Llc
Operator Street Address 1300 Main Street
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 29.998306 Google Maps OpenStreetMap
Location Longitude -93.990131 Google Maps OpenStreetMap
Commodity Released Type Crude Oil
Unintentional Release Bbls 0.48
Recovered Bbls 0.48
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
System Part Involved Onshore Terminal/tank Farm Equipment And Piping
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind No
Shutdown Explain Sump Isolated From The Manifold.
Communication State Fed Ind No
Nrc Rpt Num Nrc Notification Not Required NRC Report How to search
Ignite Ind No
Notify Qualified Indiv Ind Yes
Oil Spill Removal Org Ind No
Num Pub Evacuated 0
Pipe Fac Name Nederland Terminal
Segment Name Central Manifold 24-Inch
Onshore State Abbreviation Tx
Onshore Postal Code 77627
Onshore City Name Nederland
Onshore County Name Jefferson
Designated Location Survey Station No.
Designated Name 0+00
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
Item Involved Sump
Installation Year Unknown
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Overfill Or Overflow
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca Yes
High Pop Ind Yes
High Pop Yes No Yes
Est Cost Oper Paid 0
Est Cost Gas Released 55
Est Cost Prop Damage 500
Est Cost Emergency 1500
Est Cost Environmental 0
Est Cost Other 0
Prpty 2055
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 80
Mop Psig 275
Mop Cfr Section Component Design Pressure �195.406(A)(2) View CFR 49 §192
Maop Established Date 1980-01-01 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind Yes
Cpm In Place Ind Yes
Cpm Operating Ind Yes
Cpm Functional Ind Yes
Cpm Detection Ind No
Cpm Conf Ind No
Investigation Status Yes, specify investigation result(s): (select all that apply)
Invest Schedule Ind Yes
Invest No Controller Ind Yes
Invest Other Ind Yes
Invest Other Ind Details Sump Alarm Not Displayed On Active Scada Screen When Operating Manifold. After Investigation The Alarm Has Been Moved To The Active Scada Screen To Prevent Recurrence.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Malfunction Of Control/relief Equipment
Eq Failure Type Malfunction Of Control/relief Equipment
Block Valve Ind Yes
Eq Additional Other Ind Yes
Eq Additional Other Details Wear On Valve Inner Components
Io Tank Vessel Ind Yes
Preparer Name T*** N*******
Preparer Title Director - Regulatory Compliance
Preparer Email T************@e*************.com
Preparer Telephone 713-989-7126
Prepared Date 2023-07-21 00:00:00
Authorizer Name T*** N*******
Authorizer Telephone 713-989-7126
Authorizer Title Director - Regulatory Compliance
Authorizer Email T************@e*************.com
Narrative On 6/28/2023 at approximately 07:50, the duty foreman received a call that the front sump at central manifold was overflowing. Local operations personnel responded to the central manifold and stopped all transfers to determine which line the oil was coming from. Approximately, 20 gallons of crude oil released into the sump containment area. Clean-up contractors were dispatched to the area to collect the free product. Investigation determined that 4-inch drain valve was leaking by and bypassing crude oil into the sump causing it to overfill into the containment. Further investigation in the local control room identified that the scada hi sump alarm was not located on the active screen when controlling the central manifold. The alarm was moved to be visible on the active screen to prevent recurrence. A new drain valve was installed, and a vapor blind was installed to block the oil coming from the 26-inch line.