Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2023-07-21 — TX
Operator
Energy Transfer Nederland Terminal Llc
Cause
Equipment Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$500
Incident datetime
2023-07-21 00:00 UTC
Report number
Location
TX
Narrative
On 6/28/2023 at approximately 07:50, the duty foreman received a call that the front sump at central manifold was overflowing. Local operations personnel responded to the central manifold and stopped all transfers to determine which line the oil was coming from. Approximately, 20 gallons of crude oil released into the sump containment area. Clean-up contractors were dispatched to the area to collect the free product. Investigation determined that 4-inch drain valve was leaking by and bypassing crude oil into the sump causing it to overfill into the containment. Further investigation in the local control room identified that the scada hi sump alarm was not located on the active screen when controlling the central manifold. The alarm was moved to be visible on the active screen to prevent recurrence. A new drain valve was installed, and a vapor blind was installed to block the oil coming from the 26-inch line.
Detailed record list
Report Received Date
2023-07-21 00:00:00
Iyear
2023
Report Number
20230166
Supplemental Number
38300
Report Type
Original Final
Operator Id
39706
Name
Energy Transfer Nederland Terminal Llc
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
29.998306
Location Longitude
-93.990131
Commodity Released Type
Crude Oil
Unintentional Release Bbls
0.48
Recovered Bbls
0.48
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
Sump Isolated From The Manifold.
Communication State Fed Ind
No
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Nederland Terminal
Segment Name
Central Manifold 24-Inch
Onshore State Abbreviation
Tx
Onshore Postal Code
77627
Onshore City Name
Nederland
Onshore County Name
Jefferson
Designated Location
Survey Station No.
Designated Name
0+00
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Sump
Installation Year
Unknown
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Overfill Or Overflow
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
55
Est Cost Prop Damage
500
Est Cost Emergency
1500
Est Cost Environmental
0
Est Cost Other
0
Prpty
2055
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
80
Mop Psig
275
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
1980-01-01 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
Yes
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest Schedule Ind
Yes
Invest No Controller Ind
Yes
Invest Other Ind
Yes
Invest Other Ind Details
Sump Alarm Not Displayed On Active Scada Screen When Operating Manifold. After Investigation The Alarm Has Been Moved To The Active Scada Screen To Prevent Recurrence.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Malfunction Of Control/relief Equipment
Eq Failure Type
Malfunction Of Control/relief Equipment
Block Valve Ind
Yes
Eq Additional Other Ind
Yes
Eq Additional Other Details
Wear On Valve Inner Components
Io Tank Vessel Ind
Yes
Preparer Name
T*** N*******
Preparer Title
Director - Regulatory Compliance
Preparer Email
T************@e*************.com
Preparer Telephone
713-989-7126
Prepared Date
2023-07-21 00:00:00
Authorizer Name
T*** N*******
Authorizer Telephone
713-989-7126
Authorizer Title
Director - Regulatory Compliance
Authorizer Email
T************@e*************.com
Narrative
On 6/28/2023 at approximately 07:50, the duty foreman received a call that the front sump at central manifold was overflowing. Local operations personnel responded to the central manifold and stopped all transfers to determine which line the oil was coming from. Approximately, 20 gallons of crude oil released into the sump containment area. Clean-up contractors were dispatched to the area to collect the free product. Investigation determined that 4-inch drain valve was leaking by and bypassing crude oil into the sump causing it to overfill into the containment. Further investigation in the local control room identified that the scada hi sump alarm was not located on the active screen when controlling the central manifold. The alarm was moved to be visible on the active screen to prevent recurrence. A new drain valve was installed, and a vapor blind was installed to block the oil coming from the 26-inch line.
Report Received Date | 2023-07-21 00:00:00 |
---|---|
Iyear | 2023 |
Report Number | 20230166 |
Supplemental Number | 38300 |
Report Type | Original Final |
Operator Id | 39706 PHMSA Enforcement |
Name | Energy Transfer Nederland Terminal Llc |
Operator Street Address | 1300 Main Street |
Operator City Name | Houston |
Operator State Abbreviation | TX |
Operator Postal Code | 77002 |
Time Zone | Central |
Daylight Savings Ind | Yes |
Location Latitude | 29.998306 Google Maps OpenStreetMap |
Location Longitude | -93.990131 Google Maps OpenStreetMap |
Commodity Released Type | Crude Oil |
Unintentional Release Bbls | 0.48 |
Recovered Bbls | 0.48 |
Fatality Ind | No |
Fatal | 0 |
Injury Ind | No |
Injure | 0 |
Accident Identifier | Local Operating Personnel, Including Contractors |
Operator Type | Operator Employee |
System Part Involved | Onshore Terminal/tank Farm Equipment And Piping |
On Off Shore | Onshore |
Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
Shutdown Due Accident Ind | No |
Shutdown Explain | Sump Isolated From The Manifold. |
Communication State Fed Ind | No |
Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
Ignite Ind | No |
Notify Qualified Indiv Ind | Yes |
Oil Spill Removal Org Ind | No |
Num Pub Evacuated | 0 |
Pipe Fac Name | Nederland Terminal |
Segment Name | Central Manifold 24-Inch |
Onshore State Abbreviation | Tx |
Onshore Postal Code | 77627 |
Onshore City Name | Nederland |
Onshore County Name | Jefferson |
Designated Location | Survey Station No. |
Designated Name | 0+00 |
Federal | No |
Location Type | Totally Contained On Operator-Controlled Property |
Incident Area Type | Aboveground |
Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
Crossing | No |
Pipe Facility Type | Interstate |
Item Involved | Sump |
Installation Year | Unknown |
Manufactured Year | Unknown |
Material Involved | Carbon Steel |
Release Type | Overfill Or Overflow |
Wildlife Impact Ind | No |
Soil Contamination | No |
Long Term Assessment | No |
Remediation Ind | No |
Water Contam Ind | No |
Could Be Hca | Yes |
Commodity Reached Hca | Yes |
High Pop Ind | Yes |
High Pop Yes No | Yes |
Est Cost Oper Paid | 0 |
Est Cost Gas Released | 55 |
Est Cost Prop Damage | 500 |
Est Cost Emergency | 1500 |
Est Cost Environmental | 0 |
Est Cost Other | 0 |
Prpty | 2055 |
Num Persons Hosp Not Ovnght | 0 |
Num Injured Treated By Emt | 0 |
Num Resident Building Affctd | 0 |
Num Business Building Affctd | 0 |
Accident Psig | 80 |
Mop Psig | 275 |
Mop Cfr Section | Component Design Pressure �195.406(A)(2) View CFR 49 §192 |
Maop Established Date | 1980-01-01 00:00:00 |
Maop Reversal Flow Ind | No |
Accident Pressure | Pressure Did Not Exceed Mop |
Pressure Restriction Ind | No |
Pipeline Function | > 20% Smys Regulated Transmission |
Scada In Place Ind | Yes |
Scada Operating Ind | Yes |
Scada Functional Ind | Yes |
Scada Detection Ind | No |
Scada Conf Ind | Yes |
Cpm In Place Ind | Yes |
Cpm Operating Ind | Yes |
Cpm Functional Ind | Yes |
Cpm Detection Ind | No |
Cpm Conf Ind | No |
Investigation Status | Yes, specify investigation result(s): (select all that apply) |
Invest Schedule Ind | Yes |
Invest No Controller Ind | Yes |
Invest Other Ind | Yes |
Invest Other Ind Details | Sump Alarm Not Displayed On Active Scada Screen When Operating Manifold. After Investigation The Alarm Has Been Moved To The Active Scada Screen To Prevent Recurrence. |
Employee Drug Test Ind | No |
Contractor Drug Test Ind | No |
Cause | Equipment Failure |
Cause Details | Malfunction Of Control/relief Equipment |
Eq Failure Type | Malfunction Of Control/relief Equipment |
Block Valve Ind | Yes |
Eq Additional Other Ind | Yes |
Eq Additional Other Details | Wear On Valve Inner Components |
Io Tank Vessel Ind | Yes |
Preparer Name | T*** N******* |
Preparer Title | Director - Regulatory Compliance |
Preparer Email | T************@e*************.com |
Preparer Telephone | 713-989-7126 |
Prepared Date | 2023-07-21 00:00:00 |
Authorizer Name | T*** N******* |
Authorizer Telephone | 713-989-7126 |
Authorizer Title | Director - Regulatory Compliance |
Authorizer Email | T************@e*************.com |
Narrative | On 6/28/2023 at approximately 07:50, the duty foreman received a call that the front sump at central manifold was overflowing. Local operations personnel responded to the central manifold and stopped all transfers to determine which line the oil was coming from. Approximately, 20 gallons of crude oil released into the sump containment area. Clean-up contractors were dispatched to the area to collect the free product. Investigation determined that 4-inch drain valve was leaking by and bypassing crude oil into the sump causing it to overfill into the containment. Further investigation in the local control room identified that the scada hi sump alarm was not located on the active screen when controlling the central manifold. The alarm was moved to be visible on the active screen to prevent recurrence. A new drain valve was installed, and a vapor blind was installed to block the oil coming from the 26-inch line. |