HL incident on 2023-07-21 — TX
Operator
Plains Pipeline, L.p.
Cause
Corrosion Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$5,000
Incident datetime
2023-07-21 00:00 UTC
Report number
Location
TX
Narrative
Approximately 2 barrels of crude oil were released from low-pressure surge relief station piping at corpus christi west. The date and time of the release (part a q4) is indicative of the earliest possible time the release could have started as it was the last time the incident location had been visited and confirmed to be no release of crude oil. The cause of the release is attributed to internal corrosion and the investigation is ongoing into the sub-cause. To prevent future releases, the flange was removed from service and replaced. A supplemental report will be submitted pending further investigation into the sub-cause and additional preventative measures. Supplemental: the cause of the incident is attributed to microbiologically induced corrosion based on field examination. Additionally, a third-party analysis of the continuity at the facility was performed, which found that anodic/cathodic interference on one side of the failed flange increased the rate of corrosion. In addition to the previously mentioned preventative measures, isolating gaskets were removed to ensure continuity throughout the facility.
Detailed record list
Report Received Date
2023-07-21 00:00:00
Iyear
2023
Report Number
20230165
Supplemental Number
38732
Report Type
Supplemental Final
Operator Id
Name
Plains Pipeline, L.p.
Operator Street Address
333 Clay Street, Suite 1900
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
27.821954
Location Longitude
-97.514374
Commodity Released Type
Crude Oil
Unintentional Release Bbls
2
Recovered Bbls
2
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
Facility Not Shutdown Or Isolated For Release Or Repairs; Pump Was Not Running
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Corpus Christi West
Segment Name
Low Pressure Surge Relief Station Piping
Onshore State Abbreviation
Tx
Onshore Postal Code
78409
Onshore City Name
Corpus Christi
Onshore County Name
Nueces
Designated Location
Milepost
Designated Name
0+00
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Other
Item Involved Details
12" Weld-Neck Portion Of Flange
Installation Year
2018
Manufactured Year
2018
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
70
Est Cost Prop Damage
5000
Est Cost Emergency
4000
Est Cost Environmental
0
Est Cost Other
0
Prpty
9070
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
20
Mop Psig
275
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
2018-09-06 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The release was below detectable limits.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
Internal Corrosion
Internal External
Internal Corrosion
Int Visual Exam Results
Not Cut Open
Int Microbiological Ind
Yes
Int Other Corrosion Ind
Yes
Int Corrosion Type Details
Anodic/cathodic Interference
Int Field Exam Basis Ind
Yes
Int Low Point Pipe Loc Ind
Yes
Corrosion Inhibitors
No
Corrosion Lining
No
Cleaning Dewatering
Not Applicable - Not Mainline Pipe
Corrosion Coupons
Not Applicable - Not Mainline Pipe
Preparer Name
N****** G*******
Preparer Title
Supervisor Hse-Regulatory Compliance
Preparer Email
N***************@p*****.com
Preparer Telephone
7136464376
Prepared Date
2023-11-01 00:00:00
Local Contact Name
N****** G*******
Local Contact Email
N***************@p*****.com
Local Contact Telephone
7136464376
Authorizer Name
N***** G*****
Authorizer Telephone
7136464336
Authorizer Title
Hse Mgr Director
Authorizer Email
N************@p*****.com
Narrative
Approximately 2 barrels of crude oil were released from low-pressure surge relief station piping at corpus christi west. The date and time of the release (part a q4) is indicative of the earliest possible time the release could have started as it was the last time the incident location had been visited and confirmed to be no release of crude oil. The cause of the release is attributed to internal corrosion and the investigation is ongoing into the sub-cause. To prevent future releases, the flange was removed from service and replaced. A supplemental report will be submitted pending further investigation into the sub-cause and additional preventative measures. Supplemental: the cause of the incident is attributed to microbiologically induced corrosion based on field examination. Additionally, a third-party analysis of the continuity at the facility was performed, which found that anodic/cathodic interference on one side of the failed flange increased the rate of corrosion. In addition to the previously mentioned preventative measures, isolating gaskets were removed to ensure continuity throughout the facility.
Report Received Date | 2023-07-21 00:00:00 |
---|---|
Iyear | 2023 |
Report Number | 20230165 |
Supplemental Number | 38732 |
Report Type | Supplemental Final |
Operator Id | 300 PHMSA Enforcement |
Name | Plains Pipeline, L.p. |
Operator Street Address | 333 Clay Street, Suite 1900 |
Operator City Name | Houston |
Operator State Abbreviation | TX |
Operator Postal Code | 77002 |
Time Zone | Central |
Daylight Savings Ind | Yes |
Location Latitude | 27.821954 Google Maps OpenStreetMap |
Location Longitude | -97.514374 Google Maps OpenStreetMap |
Commodity Released Type | Crude Oil |
Unintentional Release Bbls | 2 |
Recovered Bbls | 2 |
Fatality Ind | No |
Fatal | 0 |
Injury Ind | No |
Injure | 0 |
Accident Identifier | Local Operating Personnel, Including Contractors |
Operator Type | Operator Employee |
System Part Involved | Onshore Terminal/tank Farm Equipment And Piping |
On Off Shore | Onshore |
Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
Shutdown Due Accident Ind | No |
Shutdown Explain | Facility Not Shutdown Or Isolated For Release Or Repairs; Pump Was Not Running |
Communication State Fed Ind | Yes |
Party Initiated Communication | Operator |
Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
Ignite Ind | No |
Notify Qualified Indiv Ind | Yes |
Oil Spill Removal Org Ind | No |
Num Pub Evacuated | 0 |
Pipe Fac Name | Corpus Christi West |
Segment Name | Low Pressure Surge Relief Station Piping |
Onshore State Abbreviation | Tx |
Onshore Postal Code | 78409 |
Onshore City Name | Corpus Christi |
Onshore County Name | Nueces |
Designated Location | Milepost |
Designated Name | 0+00 |
Federal | No |
Location Type | Totally Contained On Operator-Controlled Property |
Incident Area Type | Aboveground |
Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
Crossing | No |
Pipe Facility Type | Intrastate |
Item Involved | Other |
Item Involved Details | 12" Weld-Neck Portion Of Flange |
Installation Year | 2018 |
Manufactured Year | 2018 |
Material Involved | Carbon Steel |
Release Type | Leak |
Leak Type | Pinhole |
Wildlife Impact Ind | No |
Soil Contamination | Yes |
Long Term Assessment | No |
Remediation Ind | No |
Water Contam Ind | No |
Could Be Hca | Yes |
Commodity Reached Hca | No |
Est Cost Oper Paid | 0 |
Est Cost Gas Released | 70 |
Est Cost Prop Damage | 5000 |
Est Cost Emergency | 4000 |
Est Cost Environmental | 0 |
Est Cost Other | 0 |
Prpty | 9070 |
Num Persons Hosp Not Ovnght | 0 |
Num Injured Treated By Emt | 0 |
Num Resident Building Affctd | 0 |
Num Business Building Affctd | 0 |
Accident Psig | 20 |
Mop Psig | 275 |
Mop Cfr Section | Component Design Pressure �195.406(A)(2) View CFR 49 §192 |
Maop Established Date | 2018-09-06 00:00:00 |
Maop Reversal Flow Ind | No |
Accident Pressure | Pressure Did Not Exceed Mop |
Pressure Restriction Ind | No |
Pipeline Function | > 20% Smys Regulated Transmission |
Scada In Place Ind | Yes |
Scada Operating Ind | Yes |
Scada Functional Ind | Yes |
Scada Detection Ind | No |
Scada Conf Ind | No |
Cpm In Place Ind | Yes |
Cpm Operating Ind | Yes |
Cpm Functional Ind | Yes |
Cpm Detection Ind | No |
Cpm Conf Ind | No |
Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
Investigation Status Details | The release was below detectable limits. |
Employee Drug Test Ind | No |
Contractor Drug Test Ind | No |
Cause | Corrosion Failure |
Cause Details | Internal Corrosion |
Internal External | Internal Corrosion |
Int Visual Exam Results | Not Cut Open |
Int Microbiological Ind | Yes |
Int Other Corrosion Ind | Yes |
Int Corrosion Type Details | Anodic/cathodic Interference |
Int Field Exam Basis Ind | Yes |
Int Low Point Pipe Loc Ind | Yes |
Corrosion Inhibitors | No |
Corrosion Lining | No |
Cleaning Dewatering | Not Applicable - Not Mainline Pipe |
Corrosion Coupons | Not Applicable - Not Mainline Pipe |
Preparer Name | N****** G******* |
Preparer Title | Supervisor Hse-Regulatory Compliance |
Preparer Email | N***************@p*****.com |
Preparer Telephone | 7136464376 |
Prepared Date | 2023-11-01 00:00:00 |
Local Contact Name | N****** G******* |
Local Contact Email | N***************@p*****.com |
Local Contact Telephone | 7136464376 |
Authorizer Name | N***** G***** |
Authorizer Telephone | 7136464336 |
Authorizer Title | Hse Mgr Director |
Authorizer Email | N************@p*****.com |
Narrative | Approximately 2 barrels of crude oil were released from low-pressure surge relief station piping at corpus christi west. The date and time of the release (part a q4) is indicative of the earliest possible time the release could have started as it was the last time the incident location had been visited and confirmed to be no release of crude oil. The cause of the release is attributed to internal corrosion and the investigation is ongoing into the sub-cause. To prevent future releases, the flange was removed from service and replaced. A supplemental report will be submitted pending further investigation into the sub-cause and additional preventative measures. Supplemental: the cause of the incident is attributed to microbiologically induced corrosion based on field examination. Additionally, a third-party analysis of the continuity at the facility was performed, which found that anodic/cathodic interference on one side of the failed flange increased the rate of corrosion. In addition to the previously mentioned preventative measures, isolating gaskets were removed to ensure continuity throughout the facility. |