HL incident on 2023-06-20 — TX
Operator
Energy Transfer Nederland Terminal Llc
Cause
Equipment Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$2,000
Incident datetime
2023-06-20 00:00 UTC
Report number
Location
TX
Narrative
On 5/19/20 at approximately 11:30, the associated prv piping developed a crack above the weld coming off of the 30" ship loading line. Operations was notified to shut down the loading of the ship in order to stop the leak and make the necessary repairs. It was determined that approximately 2 bbls of crude oil was released as a result of this broken prv line. Vacuum trucks responded to the site along with personnel for cleanup. Once the line was slacked, loto was completed and a plug was installed in the piping. A welding model was designed and a 4" flange was welded onto the pipe to facilitate a new prv and associated prv piping. The ship loading was restarted after the piping was completed and loto removed. All prv settings and designs within each manifold are being assessed by engineers to prevent reoccurrence.
Detailed record list
Report Received Date
2023-06-20 00:00:00
Iyear
2023
Report Number
20230133
Supplemental Number
38190
Report Type
Original Final
Operator Id
39706
Name
Energy Transfer Nederland Terminal Llc
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
30.000589
Location Longitude
-93.992382
Commodity Released Type
Crude Oil
Unintentional Release Bbls
2
Recovered Bbls
2
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Communication State Fed Ind
No
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Nederland Terminal
Segment Name
Marshland Manifold
Onshore State Abbreviation
Tx
Onshore Postal Code
77627
Onshore City Name
Nederland
Onshore County Name
Jefferson
Designated Location
Survey Station No.
Designated Name
0+00
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Relief Line And Relief Equipment
Installation Year
2010
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Crack
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
200
Est Cost Prop Damage
2000
Est Cost Emergency
1000
Est Cost Environmental
200
Est Cost Other
0
Prpty
3400
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
88
Mop Psig
275
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
2010-01-01 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
A review of the accident determined that there were no control room actions that contributed to the event.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Other Equipment Failure
Eq Failure Type
Other Equipment Failure
Failure Details
Psv-H002 Piping Cracked Above The Weld Coming Off The 30" Loading Line.
Additional Vibration Ind
Yes
Pwf Design Ind
Yes
Preparer Name
T*** N****
Preparer Title
Director - Regulatory Compliance
Preparer Email
T************@e*************.com
Preparer Telephone
713-989-7126
Prepared Date
2023-06-20 00:00:00
Authorizer Name
T*** N*******
Authorizer Telephone
713-989-7126
Authorizer Title
Director - Regulatory Compliance
Authorizer Email
T************@e*************.com
Narrative
On 5/19/20 at approximately 11:30, the associated prv piping developed a crack above the weld coming off of the 30" ship loading line. Operations was notified to shut down the loading of the ship in order to stop the leak and make the necessary repairs. It was determined that approximately 2 bbls of crude oil was released as a result of this broken prv line. Vacuum trucks responded to the site along with personnel for cleanup. Once the line was slacked, loto was completed and a plug was installed in the piping. A welding model was designed and a 4" flange was welded onto the pipe to facilitate a new prv and associated prv piping. The ship loading was restarted after the piping was completed and loto removed. All prv settings and designs within each manifold are being assessed by engineers to prevent reoccurrence.
Report Received Date | 2023-06-20 00:00:00 |
---|---|
Iyear | 2023 |
Report Number | 20230133 |
Supplemental Number | 38190 |
Report Type | Original Final |
Operator Id | 39706 PHMSA Enforcement |
Name | Energy Transfer Nederland Terminal Llc |
Operator Street Address | 1300 Main Street |
Operator City Name | Houston |
Operator State Abbreviation | TX |
Operator Postal Code | 77002 |
Time Zone | Central |
Daylight Savings Ind | Yes |
Location Latitude | 30.000589 Google Maps OpenStreetMap |
Location Longitude | -93.992382 Google Maps OpenStreetMap |
Commodity Released Type | Crude Oil |
Unintentional Release Bbls | 2 |
Recovered Bbls | 2 |
Fatality Ind | No |
Fatal | 0 |
Injury Ind | No |
Injure | 0 |
Accident Identifier | Local Operating Personnel, Including Contractors |
Operator Type | Operator Employee |
System Part Involved | Onshore Terminal/tank Farm Equipment And Piping |
On Off Shore | Onshore |
Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
Shutdown Due Accident Ind | Yes |
Communication State Fed Ind | No |
Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
Ignite Ind | No |
Notify Qualified Indiv Ind | Yes |
Oil Spill Removal Org Ind | No |
Num Pub Evacuated | 0 |
Pipe Fac Name | Nederland Terminal |
Segment Name | Marshland Manifold |
Onshore State Abbreviation | Tx |
Onshore Postal Code | 77627 |
Onshore City Name | Nederland |
Onshore County Name | Jefferson |
Designated Location | Survey Station No. |
Designated Name | 0+00 |
Federal | No |
Location Type | Totally Contained On Operator-Controlled Property |
Incident Area Type | Aboveground |
Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
Crossing | No |
Pipe Facility Type | Interstate |
Item Involved | Relief Line And Relief Equipment |
Installation Year | 2010 |
Manufactured Year | Unknown |
Material Involved | Carbon Steel |
Release Type | Leak |
Leak Type | Crack |
Wildlife Impact Ind | No |
Soil Contamination | No |
Long Term Assessment | No |
Remediation Ind | No |
Water Contam Ind | No |
Could Be Hca | Yes |
Commodity Reached Hca | Yes |
High Pop Ind | Yes |
High Pop Yes No | Yes |
Est Cost Oper Paid | 0 |
Est Cost Gas Released | 200 |
Est Cost Prop Damage | 2000 |
Est Cost Emergency | 1000 |
Est Cost Environmental | 200 |
Est Cost Other | 0 |
Prpty | 3400 |
Num Persons Hosp Not Ovnght | 0 |
Num Injured Treated By Emt | 0 |
Num Resident Building Affctd | 0 |
Num Business Building Affctd | 0 |
Accident Psig | 88 |
Mop Psig | 275 |
Mop Cfr Section | Component Design Pressure �195.406(A)(2) View CFR 49 §192 |
Maop Established Date | 2010-01-01 00:00:00 |
Maop Reversal Flow Ind | No |
Accident Pressure | Pressure Did Not Exceed Mop |
Pressure Restriction Ind | No |
Pipeline Function | > 20% Smys Regulated Transmission |
Scada In Place Ind | Yes |
Scada Operating Ind | Yes |
Scada Functional Ind | Yes |
Scada Detection Ind | No |
Scada Conf Ind | No |
Cpm In Place Ind | Yes |
Cpm Operating Ind | Yes |
Cpm Functional Ind | Yes |
Cpm Detection Ind | No |
Cpm Conf Ind | No |
Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
Investigation Status Details | A review of the accident determined that there were no control room actions that contributed to the event. |
Employee Drug Test Ind | No |
Contractor Drug Test Ind | No |
Cause | Equipment Failure |
Cause Details | Other Equipment Failure |
Eq Failure Type | Other Equipment Failure |
Failure Details | Psv-H002 Piping Cracked Above The Weld Coming Off The 30" Loading Line. |
Additional Vibration Ind | Yes |
Pwf Design Ind | Yes |
Preparer Name | T*** N**** |
Preparer Title | Director - Regulatory Compliance |
Preparer Email | T************@e*************.com |
Preparer Telephone | 713-989-7126 |
Prepared Date | 2023-06-20 00:00:00 |
Authorizer Name | T*** N******* |
Authorizer Telephone | 713-989-7126 |
Authorizer Title | Director - Regulatory Compliance |
Authorizer Email | T************@e*************.com |
Narrative | On 5/19/20 at approximately 11:30, the associated prv piping developed a crack above the weld coming off of the 30" ship loading line. Operations was notified to shut down the loading of the ship in order to stop the leak and make the necessary repairs. It was determined that approximately 2 bbls of crude oil was released as a result of this broken prv line. Vacuum trucks responded to the site along with personnel for cleanup. Once the line was slacked, loto was completed and a plug was installed in the piping. A welding model was designed and a 4" flange was welded onto the pipe to facilitate a new prv and associated prv piping. The ship loading was restarted after the piping was completed and loto removed. All prv settings and designs within each manifold are being assessed by engineers to prevent reoccurrence. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company
All rights reserved. Copyright © by ClearPHMSA