HL incident on 2023-06-20 — TX

Operator
Energy Transfer Nederland Terminal Llc
Cause
Equipment Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$2,000
Incident datetime
2023-06-20 00:00 UTC
Report number
Location
TX
Narrative
On 5/19/20 at approximately 11:30, the associated prv piping developed a crack above the weld coming off of the 30" ship loading line. Operations was notified to shut down the loading of the ship in order to stop the leak and make the necessary repairs. It was determined that approximately 2 bbls of crude oil was released as a result of this broken prv line. Vacuum trucks responded to the site along with personnel for cleanup. Once the line was slacked, loto was completed and a plug was installed in the piping. A welding model was designed and a 4" flange was welded onto the pipe to facilitate a new prv and associated prv piping. The ship loading was restarted after the piping was completed and loto removed. All prv settings and designs within each manifold are being assessed by engineers to prevent reoccurrence.
Detailed record list
Report Received Date
2023-06-20 00:00:00
Iyear
2023
Report Number
20230133
Supplemental Number
38190
Report Type
Original Final
Operator Id
Name
Energy Transfer Nederland Terminal Llc
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Crude Oil
Unintentional Release Bbls
2
Recovered Bbls
2
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Communication State Fed Ind
No
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Nederland Terminal
Segment Name
Marshland Manifold
Onshore State Abbreviation
Tx
Onshore Postal Code
77627
Onshore City Name
Nederland
Onshore County Name
Jefferson
Designated Location
Survey Station No.
Designated Name
0+00
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Relief Line And Relief Equipment
Installation Year
2010
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Crack
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
200
Est Cost Prop Damage
2000
Est Cost Emergency
1000
Est Cost Environmental
200
Est Cost Other
0
Prpty
3400
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
88
Mop Psig
275
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
2010-01-01 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
A review of the accident determined that there were no control room actions that contributed to the event.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Other Equipment Failure
Eq Failure Type
Other Equipment Failure
Failure Details
Psv-H002 Piping Cracked Above The Weld Coming Off The 30" Loading Line.
Additional Vibration Ind
Yes
Pwf Design Ind
Yes
Preparer Name
T*** N****
Preparer Title
Director - Regulatory Compliance
Preparer Email
T************@e*************.com
Preparer Telephone
713-989-7126
Prepared Date
2023-06-20 00:00:00
Authorizer Name
T*** N*******
Authorizer Telephone
713-989-7126
Authorizer Title
Director - Regulatory Compliance
Authorizer Email
T************@e*************.com
Narrative
On 5/19/20 at approximately 11:30, the associated prv piping developed a crack above the weld coming off of the 30" ship loading line. Operations was notified to shut down the loading of the ship in order to stop the leak and make the necessary repairs. It was determined that approximately 2 bbls of crude oil was released as a result of this broken prv line. Vacuum trucks responded to the site along with personnel for cleanup. Once the line was slacked, loto was completed and a plug was installed in the piping. A welding model was designed and a 4" flange was welded onto the pipe to facilitate a new prv and associated prv piping. The ship loading was restarted after the piping was completed and loto removed. All prv settings and designs within each manifold are being assessed by engineers to prevent reoccurrence.
Report Received Date 2023-06-20 00:00:00
Iyear 2023
Report Number 20230133
Supplemental Number 38190
Report Type Original Final
Operator Id 39706 PHMSA Enforcement
Name Energy Transfer Nederland Terminal Llc
Operator Street Address 1300 Main Street
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 30.000589 Google Maps OpenStreetMap
Location Longitude -93.992382 Google Maps OpenStreetMap
Commodity Released Type Crude Oil
Unintentional Release Bbls 2
Recovered Bbls 2
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
System Part Involved Onshore Terminal/tank Farm Equipment And Piping
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind Yes
Communication State Fed Ind No
Nrc Rpt Num Nrc Notification Not Required NRC Report How to search
Ignite Ind No
Notify Qualified Indiv Ind Yes
Oil Spill Removal Org Ind No
Num Pub Evacuated 0
Pipe Fac Name Nederland Terminal
Segment Name Marshland Manifold
Onshore State Abbreviation Tx
Onshore Postal Code 77627
Onshore City Name Nederland
Onshore County Name Jefferson
Designated Location Survey Station No.
Designated Name 0+00
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
Item Involved Relief Line And Relief Equipment
Installation Year 2010
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Leak
Leak Type Crack
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca Yes
High Pop Ind Yes
High Pop Yes No Yes
Est Cost Oper Paid 0
Est Cost Gas Released 200
Est Cost Prop Damage 2000
Est Cost Emergency 1000
Est Cost Environmental 200
Est Cost Other 0
Prpty 3400
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 88
Mop Psig 275
Mop Cfr Section Component Design Pressure �195.406(A)(2) View CFR 49 §192
Maop Established Date 2010-01-01 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind Yes
Cpm Operating Ind Yes
Cpm Functional Ind Yes
Cpm Detection Ind No
Cpm Conf Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details A review of the accident determined that there were no control room actions that contributed to the event.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Other Equipment Failure
Eq Failure Type Other Equipment Failure
Failure Details Psv-H002 Piping Cracked Above The Weld Coming Off The 30" Loading Line.
Additional Vibration Ind Yes
Pwf Design Ind Yes
Preparer Name T*** N****
Preparer Title Director - Regulatory Compliance
Preparer Email T************@e*************.com
Preparer Telephone 713-989-7126
Prepared Date 2023-06-20 00:00:00
Authorizer Name T*** N*******
Authorizer Telephone 713-989-7126
Authorizer Title Director - Regulatory Compliance
Authorizer Email T************@e*************.com
Narrative On 5/19/20 at approximately 11:30, the associated prv piping developed a crack above the weld coming off of the 30" ship loading line. Operations was notified to shut down the loading of the ship in order to stop the leak and make the necessary repairs. It was determined that approximately 2 bbls of crude oil was released as a result of this broken prv line. Vacuum trucks responded to the site along with personnel for cleanup. Once the line was slacked, loto was completed and a plug was installed in the piping. A welding model was designed and a 4" flange was welded onto the pipe to facilitate a new prv and associated prv piping. The ship loading was restarted after the piping was completed and loto removed. All prv settings and designs within each manifold are being assessed by engineers to prevent reoccurrence.

All rights reserved. Copyright © by ClearPHMSA