HL incident on 2023-06-09 — TX

Operator
Targa Downstream Llc
Cause
Equipment Failure
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$0
Incident datetime
2023-06-09 00:00 UTC
Report number
Location
TX
Narrative
On 5/14/2023, at approximately 17:10, targa ngl control room received 3 gas detector alarms at the navarro pump station (ps9). Controller immediately dispatched I&e technician to location to investigate. I&e technician arrived at approximately 18:45 and identified a release from the receiver pig trap closure. Upon arrival, and quick investigation of the situation, I&e technician determined the actuator stops were out of adjustment which caused the valve not to be fully seated in the closed position. As a result, when the o-ring failed, a small amount of product leaked past the failed o-ring. Actuator stops were adjusted and product flow stopped. Trap closure o-ring was replaced and trap returned to normal operating condition. Targa operations has identified issues with this actuator and has already begun installing ancillary equipment in preparation for new actuator from a new manufacture. Due to lead time, new actuator is estimated to be installed before the end of the year.
Detailed record list
Report Received Date
2023-06-09 00:00:00
Iyear
2023
Report Number
20230123
Supplemental Number
38310
Report Type
Supplemental Final
Operator Id
Name
Targa Downstream Llc
Operator Street Address
811 Louisiana St. Suite 2100
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls
11
Intentional Release Bbls
0
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
Release Was Coming From Pig Trap Closure O-Ring.
Communication State Fed Ind
No
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Upstream Action Taken
Valve Closure
Upstream Valve Type Ind
Remotely Controlled
Downstream Action Taken
Operational Control
Downstream Oprtnl Cntrl Detail
Not Applicable To Situation Since Leak Occurred On The Trap O-Ring
Num Pub Evacuated
0
Pipe Fac Name
West Grand Prix Jct To Mont Belvieu
Segment Name
Gpx-E
Onshore State Abbreviation
Tx
Onshore Postal Code
76641
Onshore City Name
Not Within A Municipality
Onshore County Name
Navarro
Designated Location
Survey Station No.
Designated Name
Ps9
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Scraper/pig Trap
Installation Year
2019
Manufactured Year
Unknown
Material Involved
Material Other Than Carbon Steel
Material Details
Buna
Release Type
Leak
Leak Type
Other
Leak Type Other
Leak At Buna O-Ring
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
412
Est Cost Prop Damage
0
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
1200
Est Cost Other Details
Approximate Cost Of New O-Ring
Prpty
1612
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
1109
Mop Psig
1440
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
2020-01-09 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Targa did not find that an investigation of the controllers actions or control room issues was necessary due to the fact the leak occurred on the trap o-ring.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Non-Threaded Connection Failure
Eq Failure Type
Non-Threaded Connection Failure
Other Non Threaded Ind
O-Ring
Ief Addl Misalignment Ind
Yes
Eq Additional Other Ind
Yes
Eq Additional Other Details
Actuator Stops Out Of Alignment Not Allowing Valve To Close All The Way.
Preparer Name
B**** R******
Preparer Title
Pipeline Compliance Specialist
Preparer Email
B*******@t*************.com
Preparer Telephone
8179440617
Prepared Date
2023-07-24 00:00:00
Local Contact Name
B**** R******
Local Contact Email
B*******@t*************.com
Local Contact Telephone
8179440617
Authorizer Name
B**** R******
Authorizer Telephone
8179440617
Authorizer Title
Pipeline Compliance Specialist
Authorizer Email
B*******@t*************.com
Narrative
On 5/14/2023, at approximately 17:10, targa ngl control room received 3 gas detector alarms at the navarro pump station (ps9). Controller immediately dispatched I&e technician to location to investigate. I&e technician arrived at approximately 18:45 and identified a release from the receiver pig trap closure. Upon arrival, and quick investigation of the situation, I&e technician determined the actuator stops were out of adjustment which caused the valve not to be fully seated in the closed position. As a result, when the o-ring failed, a small amount of product leaked past the failed o-ring. Actuator stops were adjusted and product flow stopped. Trap closure o-ring was replaced and trap returned to normal operating condition. Targa operations has identified issues with this actuator and has already begun installing ancillary equipment in preparation for new actuator from a new manufacture. Due to lead time, new actuator is estimated to be installed before the end of the year.
Report Received Date 2023-06-09 00:00:00
Iyear 2023
Report Number 20230123
Supplemental Number 38310
Report Type Supplemental Final
Operator Id 39823 PHMSA Enforcement
Name Targa Downstream Llc
Operator Street Address 811 Louisiana St. Suite 2100
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 32.019316 Google Maps OpenStreetMap
Location Longitude -96.783384 Google Maps OpenStreetMap
Commodity Released Type Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls 11
Intentional Release Bbls 0
Recovered Bbls 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
System Part Involved Onshore Pipeline, Including Valve Sites
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind No
Shutdown Explain Release Was Coming From Pig Trap Closure O-Ring.
Communication State Fed Ind No
Nrc Rpt Num Nrc Notification Not Required NRC Report How to search
Ignite Ind No
Upstream Action Taken Valve Closure
Upstream Valve Type Ind Remotely Controlled
Downstream Action Taken Operational Control
Downstream Oprtnl Cntrl Detail Not Applicable To Situation Since Leak Occurred On The Trap O-Ring
Num Pub Evacuated 0
Pipe Fac Name West Grand Prix Jct To Mont Belvieu
Segment Name Gpx-E
Onshore State Abbreviation Tx
Onshore Postal Code 76641
Onshore City Name Not Within A Municipality
Onshore County Name Navarro
Designated Location Survey Station No.
Designated Name Ps9
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
Item Involved Scraper/pig Trap
Installation Year 2019
Manufactured Year Unknown
Material Involved Material Other Than Carbon Steel
Material Details Buna
Release Type Leak
Leak Type Other
Leak Type Other Leak At Buna O-Ring
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca No
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 412
Est Cost Prop Damage 0
Est Cost Emergency 0
Est Cost Environmental 0
Est Cost Other 1200
Est Cost Other Details Approximate Cost Of New O-Ring
Prpty 1612
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 1109
Mop Psig 1440
Mop Cfr Section Component Design Pressure �195.406(A)(2) View CFR 49 §192
Maop Established Date 2020-01-09 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Internal Inspection Ind Yes
Operation Complications Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind Yes
Cpm In Place Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details Targa did not find that an investigation of the controllers actions or control room issues was necessary due to the fact the leak occurred on the trap o-ring.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Non-Threaded Connection Failure
Eq Failure Type Non-Threaded Connection Failure
Other Non Threaded Ind O-Ring
Ief Addl Misalignment Ind Yes
Eq Additional Other Ind Yes
Eq Additional Other Details Actuator Stops Out Of Alignment Not Allowing Valve To Close All The Way.
Preparer Name B**** R******
Preparer Title Pipeline Compliance Specialist
Preparer Email B*******@t*************.com
Preparer Telephone 8179440617
Prepared Date 2023-07-24 00:00:00
Local Contact Name B**** R******
Local Contact Email B*******@t*************.com
Local Contact Telephone 8179440617
Authorizer Name B**** R******
Authorizer Telephone 8179440617
Authorizer Title Pipeline Compliance Specialist
Authorizer Email B*******@t*************.com
Narrative On 5/14/2023, at approximately 17:10, targa ngl control room received 3 gas detector alarms at the navarro pump station (ps9). Controller immediately dispatched I&e technician to location to investigate. I&e technician arrived at approximately 18:45 and identified a release from the receiver pig trap closure. Upon arrival, and quick investigation of the situation, I&e technician determined the actuator stops were out of adjustment which caused the valve not to be fully seated in the closed position. As a result, when the o-ring failed, a small amount of product leaked past the failed o-ring. Actuator stops were adjusted and product flow stopped. Trap closure o-ring was replaced and trap returned to normal operating condition. Targa operations has identified issues with this actuator and has already begun installing ancillary equipment in preparation for new actuator from a new manufacture. Due to lead time, new actuator is estimated to be installed before the end of the year.

All rights reserved. Copyright © by ClearPHMSA