GTG incident on 2023-09-11 — NE

Operator
Northern Natural Gas Co
Cause
Corrosion Failure
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$865,000
Incident datetime
2023-09-11 00:00 UTC
Report number
Location
NE
Narrative
On august 16, 2023, nng gas control received alarms of low pressure and zero flow at multiple stations in the seminole subsystem, upstream of the kermit, tx, compressor station. The gas controllers contacted customers in the area confirming the pressure and flow deviations. Nng operations communications center contacted the field operations team on-call technician to investigate the alarms. Nng was notified by local authorities of blowing gas and fire near coyanosa, tx. This confirmed the incident with nng gas control. Nng operations communication center initiated an all-call to the kermit, tx, field operations team to respond to the emergency. Nng gas control completed shutting-in all receipt and delivery points. The field operations team closed block valve 3 which completed the isolation of the affected segment. First responders closed two roads in the process. The fire from the failure was reduced to burning residual gas within 75 minutes of the segment being isolated. Based on lab results, the pipeline ruptured initially in approximately the 6 o'clock position in an area, about a foot long, of severe, mostly circular, pitting and corrosion. This pitting bears all the hallmarks of microbiologically influenced corrosion (mic), a process where one or several strains of bacteria corrode steel. The material had been corroded to approximately 0.041" wall thickness at the rupture origin, approximately 12% of the original material thickness. Further examinations of the material did not locate any other failure mechanism.
Detailed record list
Report Received Date
2023-09-11 00:00:00
Iyear
2023
Report Number
20230087
Supplemental Number
38917
Report Type
Supplemental Final
Operator Id
Name
Northern Natural Gas Co
Operator Street Address
1111 South 103rd Street
Operator City Name
Omaha
Operator State Abbreviation
NE
Operator Postal Code
68124
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Nrc Rpt Num
Additional Nrc Report Numbers
1376514
Commodity Released Type
Natural Gas
Unintentional Release
87500
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
Yes
Still Shutdown Ind
Yes
Communication State Fed Ind
Yes
Party Initiated Communication
Local/state/federal Emergency Responder
Ignite Ind
Yes
How Extinguished
Allowed To Burn Out
Gas Consumed By Fire In Mcf
87500
Explode Ind
Yes
Upstream Action Taken
Valve Closure
Downstream Action Taken
Valve Closure
Num Pub Evacuated
0
On Off Shore
Onshore
Onshore State Abbreviation
Tx
Onshore Postal Code
79722
Onshore City Name
Not Within A Municipality
Onshore County Name
Reeves
Designated Location
Milepost
Designated Name
13.84
Pipe Fac Name
M855c Coyanosa Valve #1 To Kermit
Segment Name
Txm46202
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
48
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Interstate
System Part Involved
Onshore Pipeline, Including Valve Sites
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
30
Puddle Weld Ind
No
Pipe Wall Thickness
0.321
Pipe Smys
65000
Pipe Specification
Api 5lx
Pipe Seam Type
Flash Welded
Pipe Manufacturer
Ao Smith
Pipe Coating Type
Asphalt
Coating Applied Ind
Yes
Installation Year
1968
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Rupture
Rupture Orient
Longitudinal
Rupture Length
1080
Rupture Width
94.2
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
693
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
187688
Est Cost Intentional Release
0
Est Cost Prop Damage
865000
Est Cost Emergency
50000
Est Cost Other
0
Gas Cost In Mcf
2.145
Prpty
1102688
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
Yes
Terrestrial Impact Ind
Yes
Accident Psig
930
Gas Flow In Pipe In Mcf
105580
Mop Psig
1000
Mop Cfr Section
192.619(A)(2)
Maop Established Date
1968-11-01 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Upstream Valve Type Ind
Remotely Controlled
Downstream Valve Type Ind
Manual
Length Segment Isolated
75754
Internal Inspection Ind
No
Unsuitable Mainline Ind
Yes
Other Restrictions Ind
Yes
Operation Complications Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest Schedule Ind
Yes
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
External Corrosion
Internal External
External Corrosion
Visual Exam Results
Localized Pitting
Microbiological Corrosion Ind
Yes
Metallurgical Basis Ind
Yes
Underground Location
Yes
Under Cathodic Protection Ind
Yes
Cathodic Pro Start Year
1968
Shielding Evident
Yes
Cathodic Survey Type
Yes
Close Interval Survey Ind
Yes
Close Interval Survey Year
2023
Prior Damage
No
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Preparer Name
K**** G***
Preparer Title
Pipeline Safety Specialist
Preparer Email
K*********@n****.com
Preparer Telephone
15152025067
Local Contact Name
K**** G***
Local Contact Email
K*********@n****.com
Local Contact Telephone
15152025067
Authorizer Name
T** C******
Authorizer Title
Vp Of Pipeline Safety And Risk
Authorizer Telephone
4023987715
Authorizer Email
T*************@n****.com
Narrative
On august 16, 2023, nng gas control received alarms of low pressure and zero flow at multiple stations in the seminole subsystem, upstream of the kermit, tx, compressor station. The gas controllers contacted customers in the area confirming the pressure and flow deviations. Nng operations communications center contacted the field operations team on-call technician to investigate the alarms. Nng was notified by local authorities of blowing gas and fire near coyanosa, tx. This confirmed the incident with nng gas control. Nng operations communication center initiated an all-call to the kermit, tx, field operations team to respond to the emergency. Nng gas control completed shutting-in all receipt and delivery points. The field operations team closed block valve 3 which completed the isolation of the affected segment. First responders closed two roads in the process. The fire from the failure was reduced to burning residual gas within 75 minutes of the segment being isolated. Based on lab results, the pipeline ruptured initially in approximately the 6 o'clock position in an area, about a foot long, of severe, mostly circular, pitting and corrosion. This pitting bears all the hallmarks of microbiologically influenced corrosion (mic), a process where one or several strains of bacteria corrode steel. The material had been corroded to approximately 0.041" wall thickness at the rupture origin, approximately 12% of the original material thickness. Further examinations of the material did not locate any other failure mechanism.
Report Received Date 2023-09-11 00:00:00
Iyear 2023
Report Number 20230087
Supplemental Number 38917
Report Type Supplemental Final
Operator Id 13750 PHMSA Enforcement
Name Northern Natural Gas Co
Operator Street Address 1111 South 103rd Street
Operator City Name Omaha
Operator State Abbreviation NE
Operator Postal Code 68124
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 31.38328 Google Maps OpenStreetMap
Location Longitude -103.04836 Google Maps OpenStreetMap
Nrc Rpt Num 1376310 NRC Report How to search
Additional Nrc Report Numbers 1376514
Commodity Released Type Natural Gas
Unintentional Release 87500
Intentional Release 0
Accompanying Liquid 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Status When Identified Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind Yes
Still Shutdown Ind Yes
Communication State Fed Ind Yes
Party Initiated Communication Local/state/federal Emergency Responder
Ignite Ind Yes
How Extinguished Allowed To Burn Out
Gas Consumed By Fire In Mcf 87500
Explode Ind Yes
Upstream Action Taken Valve Closure
Downstream Action Taken Valve Closure
Num Pub Evacuated 0
On Off Shore Onshore
Onshore State Abbreviation Tx
Onshore Postal Code 79722
Onshore City Name Not Within A Municipality
Onshore County Name Reeves
Designated Location Milepost
Designated Name 13.84
Pipe Fac Name M855c Coyanosa Valve #1 To Kermit
Segment Name Txm46202
Federal No
Location Type Pipeline Right-Of-Way
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover 48
Other Underground Facilities No
Crossing No
Pipe Facility Type Interstate
System Part Involved Onshore Pipeline, Including Valve Sites
Item Involved Pipe
Pipe Type Pipe Body
Pipe Diameter 30
Puddle Weld Ind No
Pipe Wall Thickness 0.321
Pipe Smys 65000
Pipe Specification Api 5lx
Pipe Seam Type Flash Welded
Pipe Manufacturer Ao Smith
Pipe Coating Type Asphalt
Coating Applied Ind Yes
Installation Year 1968
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Rupture
Rupture Orient Longitudinal
Rupture Length 1080
Rupture Width 94.2
Class Location Type Class 1 Location
Could Be Hca No
Pir Radius 693
Heat Damage Ind No
Non Heat Damage Ind No
Did Occur In Mca Ind No
Est Cost Oper Paid 0
Est Cost Unintentional Release 187688
Est Cost Intentional Release 0
Est Cost Prop Damage 865000
Est Cost Emergency 50000
Est Cost Other 0
Gas Cost In Mcf 2.145
Prpty 1102688
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Wildlife Impact Ind Yes
Terrestrial Impact Ind Yes
Accident Psig 930
Gas Flow In Pipe In Mcf 105580
Mop Psig 1000
Mop Cfr Section 192.619(A)(2) View CFR 49 §192
Maop Established Date 1968-11-01 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Maop
Pressure Restriction Ind No
Gas Required Odorized Ind No
Upstream Valve Type Ind Remotely Controlled
Downstream Valve Type Ind Manual
Length Segment Isolated 75754
Internal Inspection Ind No
Unsuitable Mainline Ind Yes
Other Restrictions Ind Yes
Operation Complications Ind No
Pipeline Function Transmission System
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind Yes
Accident Identifier Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status Yes, specify investigation result(s): (select all that apply)
Invest Schedule Ind Yes
Invest No Control Room Ind Yes
Invest No Controller Ind Yes
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Corrosion Failure
Cause Details External Corrosion
Internal External External Corrosion
Visual Exam Results Localized Pitting
Microbiological Corrosion Ind Yes
Metallurgical Basis Ind Yes
Underground Location Yes
Under Cathodic Protection Ind Yes
Cathodic Pro Start Year 1968
Shielding Evident Yes
Cathodic Survey Type Yes
Close Interval Survey Ind Yes
Close Interval Survey Year 2023
Prior Damage No
Collected Data Ind No
Has Hydrtst Conduc Before Ind No
Direct Asmnt Conducted No
Non Destructive Exam Ind No
Preparer Name K**** G***
Preparer Title Pipeline Safety Specialist
Preparer Email K*********@n****.com
Preparer Telephone 15152025067
Local Contact Name K**** G***
Local Contact Email K*********@n****.com
Local Contact Telephone 15152025067
Authorizer Name T** C******
Authorizer Title Vp Of Pipeline Safety And Risk
Authorizer Telephone 4023987715
Authorizer Email T*************@n****.com
Narrative On august 16, 2023, nng gas control received alarms of low pressure and zero flow at multiple stations in the seminole subsystem, upstream of the kermit, tx, compressor station. The gas controllers contacted customers in the area confirming the pressure and flow deviations. Nng operations communications center contacted the field operations team on-call technician to investigate the alarms. Nng was notified by local authorities of blowing gas and fire near coyanosa, tx. This confirmed the incident with nng gas control. Nng operations communication center initiated an all-call to the kermit, tx, field operations team to respond to the emergency. Nng gas control completed shutting-in all receipt and delivery points. The field operations team closed block valve 3 which completed the isolation of the affected segment. First responders closed two roads in the process. The fire from the failure was reduced to burning residual gas within 75 minutes of the segment being isolated. Based on lab results, the pipeline ruptured initially in approximately the 6 o'clock position in an area, about a foot long, of severe, mostly circular, pitting and corrosion. This pitting bears all the hallmarks of microbiologically influenced corrosion (mic), a process where one or several strains of bacteria corrode steel. The material had been corroded to approximately 0.041" wall thickness at the rupture origin, approximately 12% of the original material thickness. Further examinations of the material did not locate any other failure mechanism.