Incident details
Operator, cause, commodity and consequences with raw source fields.
GD incident on 2023-11-15 — PA
Operator
Columbia Gas Of Pennsylvania
Cause
Other Incident Cause
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$0
Incident datetime
2023-11-15 00:00 UTC
Report number
Location
PA, BEAVER
Narrative
On october 15, 2023, columbia began receiving "no gas" calls from customers in economy, pa. Service technicians reported normal pressure but also reported evidence of air in the system. This continued throughout the morning. Columbia's systems were supplied by a local producer in close proximity to the medium pressure systems. It was concluded that a slug of air entered columbia's system from the meridian well purchase point, and therefore, for safety reasons, gas was turned off to the two medium pressure systems so the air could be purged from the systems. This affected 3,728 customers. There were two medium pressure systems affected. Part e (additional operating information) does not allow the inclusion of two systems. Below is the required information for the second system: e1. Estimated pressure at the point and time of the incident (psig) 21 e2. Normal operating pressure at the point and time of the incident (psig) 21 e3. Maximum allowable operating pressure (maop) at the point and time of the incident (psig) 40 e3a. Maop established by 49 cfr section: 192.619 (a)(4) e3b. Date maop established: 03/20/09. E4. Describe the pressure on the system relating to the incident: pressure did not exceed maop. E5. Type of odorization system for gas at point of failure: none. E6. Odorant level near the point of failure measured after failure: not measured e7. Was supervisory control data acquisition (scada)-based system in place on the pipeline or facility involved in the incident? No. E8. Was an investigation initiated into whether or not the controller(s) or control room issues were the cause of or a contributing factor to the incident? No, the facility was not monitored by a controller(s) at the time of the incident.
Detailed record list
Report Received Date
2023-11-15 00:00:00
Iyear
2023.0
Report Number
20230067.0
Supplemental Number
39889.0
Report Type
Supplemental Final
Operator Id
2600
Name
Columbia Gas Of Pennsylvania
Operator Street Address
121 Champion Way
Operator City Name
Canonsburg
Operator State Abbreviation
PA
Operator Postal Code
15317.0
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Street Address
Tevebaugh Road
Location City Name
Freedom
Location County Name
Beaver
Location State Abbreviation
PA
Location Postal Code
15042.0
Location Latitude
40.66602
Location Longitude
-80.21585
Flow Cont Meter Reg Ind
Yes
Nrc Rpt Num
1381816.0
Additional Nrc Report Numbers
1381956.0
Commodity Released Type
Natural Gas
Unintentional Release
0.0
Intentional Release
48.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Num Pub Evacuated
0.0
Communication State Fed Ind
No
Federal
No
Location Type
Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance (E.g. Value Or Regulator Station, Outdoor Meter Set)
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
District Regulator/metering Station
Installation Year
1985.0
Material Involved
Other
Material Details
No Issue With Material For This Event
Release Type
Other
Release Type Details
There Was No Release Of Gas. This Incident Was Reported As A Significant Event Because Gas Service Was Shut Off For Safety To 3,728 Customers.
Class Location Type
Class 3 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
0.0
Est Cost Emergency
2209692.0
Est Cost Other
89181.0
Est Cost Other Details
Lodging, Meals, Etc. For Responding Employees.
Gas Cost In Mcf
4.88
Est Cost Unintentional Release
0.0
Est Cost Intentional Release
234.0
Prpty
2299107.0
Commercial Affected
37.0
Industrial Affected
0.0
Residences Affected
3691.0
Num Persons Hosp Not Ovnght
0.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
3691.0
Num Business Building Affctd
37.0
Accident Psig
15.0
Normal Psig
15.0
Mop Psig
18.0
Mop Cfr Section
192.619(A)(4)
Maop Established Date
1999-06-07 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
None
Gas Odorized Lvl Not Msrd Ind
Yes
Scada In Place Ind
No
Accident Identifier
Other
Accident Details
Customer No Gas Calls
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Incident Cause
Cause Details
Miscellaneous
Other Type
Miscellaneous
Misc Details
Slug Of Air Entered Columbia's System From The Meridian Well Purchase Point.
Preparer Name
M****** M*****
Preparer Title
Operations Compliance Manager
Preparer Email
M******@n*******.com
Preparer Telephone
7248122844
Local Contact Name
M****** M*****
Local Contact Email
M******@n*******.com
Local Contact Telephone
7248122844
Authorizer Name
B**** M*****
Authorizer Title
Vice President Gas Operations
Authorizer Telephone
4129926929
Authorizer Email
B******@n*******.com
Narrative
On october 15, 2023, columbia began receiving "no gas" calls from customers in economy, pa. Service technicians reported normal pressure but also reported evidence of air in the system. This continued throughout the morning. Columbia's systems were supplied by a local producer in close proximity to the medium pressure systems. It was concluded that a slug of air entered columbia's system from the meridian well purchase point, and therefore, for safety reasons, gas was turned off to the two medium pressure systems so the air could be purged from the systems. This affected 3,728 customers. There were two medium pressure systems affected. Part e (additional operating information) does not allow the inclusion of two systems. Below is the required information for the second system: e1. Estimated pressure at the point and time of the incident (psig) 21 e2. Normal operating pressure at the point and time of the incident (psig) 21 e3. Maximum allowable operating pressure (maop) at the point and time of the incident (psig) 40 e3a. Maop established by 49 cfr section: 192.619 (a)(4) e3b. Date maop established: 03/20/09. E4. Describe the pressure on the system relating to the incident: pressure did not exceed maop. E5. Type of odorization system for gas at point of failure: none. E6. Odorant level near the point of failure measured after failure: not measured e7. Was supervisory control data acquisition (scada)-based system in place on the pipeline or facility involved in the incident? No. E8. Was an investigation initiated into whether or not the controller(s) or control room issues were the cause of or a contributing factor to the incident? No, the facility was not monitored by a controller(s) at the time of the incident.
Report Received Date | 2023-11-15 00:00:00 |
---|---|
Iyear | 2023.0 |
Report Number | 20230067.0 |
Supplemental Number | 39889.0 |
Report Type | Supplemental Final |
Operator Id | 2600 PHMSA Enforcement |
Name | Columbia Gas Of Pennsylvania |
Operator Street Address | 121 Champion Way |
Operator City Name | Canonsburg |
Operator State Abbreviation | PA |
Operator Postal Code | 15317.0 |
Time Zone | Eastern |
Daylight Savings Ind | Yes |
Location Street Address | Tevebaugh Road |
Location City Name | Freedom |
Location County Name | Beaver |
Location State Abbreviation | PA |
Location Postal Code | 15042.0 |
Location Latitude | 40.66602 Google Maps OpenStreetMap |
Location Longitude | -80.21585 Google Maps OpenStreetMap |
Flow Cont Meter Reg Ind | Yes |
Nrc Rpt Num | 1381816.0 NRC Report How to search |
Additional Nrc Report Numbers | 1381956.0 |
Commodity Released Type | Natural Gas |
Unintentional Release | 0.0 |
Intentional Release | 48.0 |
Fatality Ind | No |
Fatal | 0 |
Injury Ind | No |
Injure | 0 |
Ignite Ind | No |
Num Pub Evacuated | 0.0 |
Communication State Fed Ind | No |
Federal | No |
Location Type | Operator-Controlled Property |
Incident Area Type | Aboveground |
Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance (E.g. Value Or Regulator Station, Outdoor Meter Set) |
Crossing | No |
Pipe Facility Type | Investor Owned |
System Part Involved | District Regulator/metering Station |
Installation Year | 1985.0 |
Material Involved | Other |
Material Details | No Issue With Material For This Event |
Release Type | Other |
Release Type Details | There Was No Release Of Gas. This Incident Was Reported As A Significant Event Because Gas Service Was Shut Off For Safety To 3,728 Customers. |
Class Location Type | Class 3 Location |
Est Cost Oper Paid | 0.0 |
Est Cost Prop Damage | 0.0 |
Est Cost Emergency | 2209692.0 |
Est Cost Other | 89181.0 |
Est Cost Other Details | Lodging, Meals, Etc. For Responding Employees. |
Gas Cost In Mcf | 4.88 |
Est Cost Unintentional Release | 0.0 |
Est Cost Intentional Release | 234.0 |
Prpty | 2299107.0 |
Commercial Affected | 37.0 |
Industrial Affected | 0.0 |
Residences Affected | 3691.0 |
Num Persons Hosp Not Ovnght | 0.0 |
Num Injured Treated By Emt | 0.0 |
Num Resident Building Affctd | 3691.0 |
Num Business Building Affctd | 37.0 |
Accident Psig | 15.0 |
Normal Psig | 15.0 |
Mop Psig | 18.0 |
Mop Cfr Section | 192.619(A)(4) View CFR 49 §192 |
Maop Established Date | 1999-06-07 00:00:00 |
Accident Pressure | Pressure Did Not Exceed Maop |
Gas Odorized System Type | None |
Gas Odorized Lvl Not Msrd Ind | Yes |
Scada In Place Ind | No |
Accident Identifier | Other |
Accident Details | Customer No Gas Calls |
Investigation Status | No, the facility was not monitored by a controller(s) at the time of the incident |
Employee Drug Test Ind | No |
Contractor Drug Test Ind | No |
Cause | Other Incident Cause |
Cause Details | Miscellaneous |
Other Type | Miscellaneous |
Misc Details | Slug Of Air Entered Columbia's System From The Meridian Well Purchase Point. |
Preparer Name | M****** M***** |
Preparer Title | Operations Compliance Manager |
Preparer Email | M******@n*******.com |
Preparer Telephone | 7248122844 |
Local Contact Name | M****** M***** |
Local Contact Email | M******@n*******.com |
Local Contact Telephone | 7248122844 |
Authorizer Name | B**** M***** |
Authorizer Title | Vice President Gas Operations |
Authorizer Telephone | 4129926929 |
Authorizer Email | B******@n*******.com |
Narrative | On october 15, 2023, columbia began receiving "no gas" calls from customers in economy, pa. Service technicians reported normal pressure but also reported evidence of air in the system. This continued throughout the morning. Columbia's systems were supplied by a local producer in close proximity to the medium pressure systems. It was concluded that a slug of air entered columbia's system from the meridian well purchase point, and therefore, for safety reasons, gas was turned off to the two medium pressure systems so the air could be purged from the systems. This affected 3,728 customers. There were two medium pressure systems affected. Part e (additional operating information) does not allow the inclusion of two systems. Below is the required information for the second system: e1. Estimated pressure at the point and time of the incident (psig) 21 e2. Normal operating pressure at the point and time of the incident (psig) 21 e3. Maximum allowable operating pressure (maop) at the point and time of the incident (psig) 40 e3a. Maop established by 49 cfr section: 192.619 (a)(4) e3b. Date maop established: 03/20/09. E4. Describe the pressure on the system relating to the incident: pressure did not exceed maop. E5. Type of odorization system for gas at point of failure: none. E6. Odorant level near the point of failure measured after failure: not measured e7. Was supervisory control data acquisition (scada)-based system in place on the pipeline or facility involved in the incident? No. E8. Was an investigation initiated into whether or not the controller(s) or control room issues were the cause of or a contributing factor to the incident? No, the facility was not monitored by a controller(s) at the time of the incident. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company
All rights reserved. Copyright © by ClearPHMSA