GTG incident on 2023-06-15 — TX

Operator
Gulf South Pipeline Company, Llc
Cause
Equipment Failure
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$1,125
Incident datetime
2023-06-15 00:00 UTC
Report number
Location
TX
Narrative
On 5/20/23 at approximately 17:41, gulf south's gas control personnel received a fire detection alarm for its harrisville compressor station followed by indications of a station emergency shutdown (esd). Operations personnel were dispatched and identified a glycol tubing leak at one turbocharger and no significant damage to the unit. It is believed that the glycol leaking on the turbocharger likely sparked and activated a fire detector that initiated the station esd. The unit was isolated, the station purged, then available horsepower was restarted. The communication with emergency responders indicated on question a17 was to notify the sheriff's office that the station purge would begin soon; it was not a notification due to a fire or assistance needed. On 5/21/23, the repair was completed by replacing the tubing. The affected unit was restarted at approximately 13:11.
Detailed record list
Report Received Date
2023-06-15 00:00:00
Iyear
2023
Report Number
20230055
Supplemental Number
38175
Report Type
Original Final
Operator Id
Name
Gulf South Pipeline Company, Llc
Operator Street Address
9 Greenway Plaza Suite 2800
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77046
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Nrc Rpt Num
Additional Nrc Report Numbers
1367923
Commodity Released Type
Natural Gas
Unintentional Release
3200
Intentional Release
73.81
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
Yes
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Ignite Ind
No
Num Pub Evacuated
0
On Off Shore
Onshore
Onshore State Abbreviation
Ms
Onshore Postal Code
39073
Onshore City Name
Not Within A Municipality
Onshore County Name
Simpson
Designated Location
Not Applicable
Pipe Fac Name
Harrisville Compressor Station
Segment Name
Not Applicable
Federal
No
Location Type
Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
System Part Involved
Onshore Compressor Station Equipment And Piping
Item Involved
Tubing
Tubing Material
Stainless Steel
Tubing Type
Rigid
Installation Year
2007
Manufactured Year
2007
Material Involved
Material Other Than Carbon Steel Or Plastic
Material Details
Stainless Steel
Release Type
Other
Release Type Details
Station Esd
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
1122
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
6784
Est Cost Intentional Release
156
Est Cost Prop Damage
1125
Est Cost Emergency
900
Est Cost Other
0
Gas Cost In Mcf
2.12
Prpty
8965
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
1363
Gas Flow In Pipe In Mcf
2212000
Mop Psig
1480
Mop Cfr Section
Maop Established Date
2008-06-01 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Defective Or Loose Tubing Or Fitting
Eq Failure Type
Defective Or Loose Tubing Or Fitting
Additional Vibration Ind
Yes
Additional Installation Ind
Yes
Preparer Name
S****** M********
Preparer Title
Compliance Program Leader
Preparer Email
S****************@b**********.com
Preparer Telephone
270-903-5764
Authorizer Name
T*** B****
Authorizer Title
Manager Compliance Services
Authorizer Telephone
270-314-6547
Authorizer Email
T*********@b**********.com
Narrative
On 5/20/23 at approximately 17:41, gulf south's gas control personnel received a fire detection alarm for its harrisville compressor station followed by indications of a station emergency shutdown (esd). Operations personnel were dispatched and identified a glycol tubing leak at one turbocharger and no significant damage to the unit. It is believed that the glycol leaking on the turbocharger likely sparked and activated a fire detector that initiated the station esd. The unit was isolated, the station purged, then available horsepower was restarted. The communication with emergency responders indicated on question a17 was to notify the sheriff's office that the station purge would begin soon; it was not a notification due to a fire or assistance needed. On 5/21/23, the repair was completed by replacing the tubing. The affected unit was restarted at approximately 13:11.
Report Received Date 2023-06-15 00:00:00
Iyear 2023
Report Number 20230055
Supplemental Number 38175
Report Type Original Final
Operator Id 31728 PHMSA Enforcement
Name Gulf South Pipeline Company, Llc
Operator Street Address 9 Greenway Plaza Suite 2800
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77046
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 32.028425 Google Maps OpenStreetMap
Location Longitude -90.142072 Google Maps OpenStreetMap
Nrc Rpt Num 1367813 NRC Report How to search
Additional Nrc Report Numbers 1367923
Commodity Released Type Natural Gas
Unintentional Release 3200
Intentional Release 73.81
Accompanying Liquid 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Status When Identified Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind Yes
Communication State Fed Ind Yes
Party Initiated Communication Operator
Ignite Ind No
Num Pub Evacuated 0
On Off Shore Onshore
Onshore State Abbreviation Ms
Onshore Postal Code 39073
Onshore City Name Not Within A Municipality
Onshore County Name Simpson
Designated Location Not Applicable
Pipe Fac Name Harrisville Compressor Station
Segment Name Not Applicable
Federal No
Location Type Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
System Part Involved Onshore Compressor Station Equipment And Piping
Item Involved Tubing
Tubing Material Stainless Steel
Tubing Type Rigid
Installation Year 2007
Manufactured Year 2007
Material Involved Material Other Than Carbon Steel Or Plastic
Material Details Stainless Steel
Release Type Other
Release Type Details Station Esd
Class Location Type Class 1 Location
Could Be Hca No
Pir Radius 1122
Heat Damage Ind No
Non Heat Damage Ind No
Did Occur In Mca Ind No
Est Cost Oper Paid 0
Est Cost Unintentional Release 6784
Est Cost Intentional Release 156
Est Cost Prop Damage 1125
Est Cost Emergency 900
Est Cost Other 0
Gas Cost In Mcf 2.12
Prpty 8965
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Wildlife Impact Ind No
Accident Psig 1363
Gas Flow In Pipe In Mcf 2212000
Mop Psig 1480
Mop Cfr Section 192.619(D) View CFR 49 §192
Maop Established Date 2008-06-01 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Maop
Pressure Restriction Ind No
Gas Required Odorized Ind No
Pipeline Function Transmission System
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind Yes
Accident Identifier Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind Yes
Invest No Controller Ind Yes
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Defective Or Loose Tubing Or Fitting
Eq Failure Type Defective Or Loose Tubing Or Fitting
Additional Vibration Ind Yes
Additional Installation Ind Yes
Preparer Name S****** M********
Preparer Title Compliance Program Leader
Preparer Email S****************@b**********.com
Preparer Telephone 270-903-5764
Authorizer Name T*** B****
Authorizer Title Manager Compliance Services
Authorizer Telephone 270-314-6547
Authorizer Email T*********@b**********.com
Narrative On 5/20/23 at approximately 17:41, gulf south's gas control personnel received a fire detection alarm for its harrisville compressor station followed by indications of a station emergency shutdown (esd). Operations personnel were dispatched and identified a glycol tubing leak at one turbocharger and no significant damage to the unit. It is believed that the glycol leaking on the turbocharger likely sparked and activated a fire detector that initiated the station esd. The unit was isolated, the station purged, then available horsepower was restarted. The communication with emergency responders indicated on question a17 was to notify the sheriff's office that the station purge would begin soon; it was not a notification due to a fire or assistance needed. On 5/21/23, the repair was completed by replacing the tubing. The affected unit was restarted at approximately 13:11.