Incident details
Operator, cause, commodity and consequences with raw source fields.
GTG incident on 2023-06-15 — TX
Operator
Gulf South Pipeline Company, Llc
Cause
Equipment Failure
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$1,125
Incident datetime
2023-06-15 00:00 UTC
Report number
Location
TX
Narrative
On 5/20/23 at approximately 17:41, gulf south's gas control personnel received a fire detection alarm for its harrisville compressor station followed by indications of a station emergency shutdown (esd). Operations personnel were dispatched and identified a glycol tubing leak at one turbocharger and no significant damage to the unit. It is believed that the glycol leaking on the turbocharger likely sparked and activated a fire detector that initiated the station esd. The unit was isolated, the station purged, then available horsepower was restarted. The communication with emergency responders indicated on question a17 was to notify the sheriff's office that the station purge would begin soon; it was not a notification due to a fire or assistance needed. On 5/21/23, the repair was completed by replacing the tubing. The affected unit was restarted at approximately 13:11.
Detailed record list
Report Received Date
2023-06-15 00:00:00
Iyear
2023
Report Number
20230055
Supplemental Number
38175
Report Type
Original Final
Operator Id
31728
Name
Gulf South Pipeline Company, Llc
Operator Street Address
9 Greenway Plaza Suite 2800
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77046
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
32.028425
Location Longitude
-90.142072
Nrc Rpt Num
1367813
Additional Nrc Report Numbers
1367923
Commodity Released Type
Natural Gas
Unintentional Release
3200
Intentional Release
73.81
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
Yes
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Ignite Ind
No
Num Pub Evacuated
0
On Off Shore
Onshore
Onshore State Abbreviation
Ms
Onshore Postal Code
39073
Onshore City Name
Not Within A Municipality
Onshore County Name
Simpson
Designated Location
Not Applicable
Pipe Fac Name
Harrisville Compressor Station
Segment Name
Not Applicable
Federal
No
Location Type
Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
System Part Involved
Onshore Compressor Station Equipment And Piping
Item Involved
Tubing
Tubing Material
Stainless Steel
Tubing Type
Rigid
Installation Year
2007
Manufactured Year
2007
Material Involved
Material Other Than Carbon Steel Or Plastic
Material Details
Stainless Steel
Release Type
Other
Release Type Details
Station Esd
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
1122
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
6784
Est Cost Intentional Release
156
Est Cost Prop Damage
1125
Est Cost Emergency
900
Est Cost Other
0
Gas Cost In Mcf
2.12
Prpty
8965
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
1363
Gas Flow In Pipe In Mcf
2212000
Mop Psig
1480
Mop Cfr Section
192.619(D)
Maop Established Date
2008-06-01 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Defective Or Loose Tubing Or Fitting
Eq Failure Type
Defective Or Loose Tubing Or Fitting
Additional Vibration Ind
Yes
Additional Installation Ind
Yes
Preparer Name
S****** M********
Preparer Title
Compliance Program Leader
Preparer Email
S****************@b**********.com
Preparer Telephone
270-903-5764
Authorizer Name
T*** B****
Authorizer Title
Manager Compliance Services
Authorizer Telephone
270-314-6547
Authorizer Email
T*********@b**********.com
Narrative
On 5/20/23 at approximately 17:41, gulf south's gas control personnel received a fire detection alarm for its harrisville compressor station followed by indications of a station emergency shutdown (esd). Operations personnel were dispatched and identified a glycol tubing leak at one turbocharger and no significant damage to the unit. It is believed that the glycol leaking on the turbocharger likely sparked and activated a fire detector that initiated the station esd. The unit was isolated, the station purged, then available horsepower was restarted. The communication with emergency responders indicated on question a17 was to notify the sheriff's office that the station purge would begin soon; it was not a notification due to a fire or assistance needed. On 5/21/23, the repair was completed by replacing the tubing. The affected unit was restarted at approximately 13:11.
Report Received Date | 2023-06-15 00:00:00 |
---|---|
Iyear | 2023 |
Report Number | 20230055 |
Supplemental Number | 38175 |
Report Type | Original Final |
Operator Id | 31728 PHMSA Enforcement |
Name | Gulf South Pipeline Company, Llc |
Operator Street Address | 9 Greenway Plaza Suite 2800 |
Operator City Name | Houston |
Operator State Abbreviation | TX |
Operator Postal Code | 77046 |
Time Zone | Central |
Daylight Savings Ind | Yes |
Location Latitude | 32.028425 Google Maps OpenStreetMap |
Location Longitude | -90.142072 Google Maps OpenStreetMap |
Nrc Rpt Num | 1367813 NRC Report How to search |
Additional Nrc Report Numbers | 1367923 |
Commodity Released Type | Natural Gas |
Unintentional Release | 3200 |
Intentional Release | 73.81 |
Accompanying Liquid | 0 |
Fatality Ind | No |
Fatal | 0 |
Injury Ind | No |
Injure | 0 |
Status When Identified | Normal Operation, Includes Pauses During Maintenance |
Shutdown Due Accident Ind | Yes |
Communication State Fed Ind | Yes |
Party Initiated Communication | Operator |
Ignite Ind | No |
Num Pub Evacuated | 0 |
On Off Shore | Onshore |
Onshore State Abbreviation | Ms |
Onshore Postal Code | 39073 |
Onshore City Name | Not Within A Municipality |
Onshore County Name | Simpson |
Designated Location | Not Applicable |
Pipe Fac Name | Harrisville Compressor Station |
Segment Name | Not Applicable |
Federal | No |
Location Type | Operator-Controlled Property |
Incident Area Type | Aboveground |
Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
Crossing | No |
Pipe Facility Type | Interstate |
System Part Involved | Onshore Compressor Station Equipment And Piping |
Item Involved | Tubing |
Tubing Material | Stainless Steel |
Tubing Type | Rigid |
Installation Year | 2007 |
Manufactured Year | 2007 |
Material Involved | Material Other Than Carbon Steel Or Plastic |
Material Details | Stainless Steel |
Release Type | Other |
Release Type Details | Station Esd |
Class Location Type | Class 1 Location |
Could Be Hca | No |
Pir Radius | 1122 |
Heat Damage Ind | No |
Non Heat Damage Ind | No |
Did Occur In Mca Ind | No |
Est Cost Oper Paid | 0 |
Est Cost Unintentional Release | 6784 |
Est Cost Intentional Release | 156 |
Est Cost Prop Damage | 1125 |
Est Cost Emergency | 900 |
Est Cost Other | 0 |
Gas Cost In Mcf | 2.12 |
Prpty | 8965 |
Num Persons Hosp Not Ovnght | 0 |
Num Injured Treated By Emt | 0 |
Num Resident Building Affctd | 0 |
Num Business Building Affctd | 0 |
Wildlife Impact Ind | No |
Accident Psig | 1363 |
Gas Flow In Pipe In Mcf | 2212000 |
Mop Psig | 1480 |
Mop Cfr Section | 192.619(D) View CFR 49 §192 |
Maop Established Date | 2008-06-01 00:00:00 |
Maop Reversal Flow Ind | No |
Accident Pressure | Pressure Did Not Exceed Maop |
Pressure Restriction Ind | No |
Gas Required Odorized Ind | No |
Pipeline Function | Transmission System |
Scada In Place Ind | Yes |
Scada Operating Ind | Yes |
Scada Functional Ind | Yes |
Scada Detection Ind | Yes |
Scada Conf Ind | Yes |
Accident Identifier | Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations) |
Investigation Status | Yes, specify investigation result(s): (select all that apply) |
Invest No Control Room Ind | Yes |
Invest No Controller Ind | Yes |
Employee Drug Test Ind | No |
Contractor Drug Test Ind | No |
Cause | Equipment Failure |
Cause Details | Defective Or Loose Tubing Or Fitting |
Eq Failure Type | Defective Or Loose Tubing Or Fitting |
Additional Vibration Ind | Yes |
Additional Installation Ind | Yes |
Preparer Name | S****** M******** |
Preparer Title | Compliance Program Leader |
Preparer Email | S****************@b**********.com |
Preparer Telephone | 270-903-5764 |
Authorizer Name | T*** B**** |
Authorizer Title | Manager Compliance Services |
Authorizer Telephone | 270-314-6547 |
Authorizer Email | T*********@b**********.com |
Narrative | On 5/20/23 at approximately 17:41, gulf south's gas control personnel received a fire detection alarm for its harrisville compressor station followed by indications of a station emergency shutdown (esd). Operations personnel were dispatched and identified a glycol tubing leak at one turbocharger and no significant damage to the unit. It is believed that the glycol leaking on the turbocharger likely sparked and activated a fire detector that initiated the station esd. The unit was isolated, the station purged, then available horsepower was restarted. The communication with emergency responders indicated on question a17 was to notify the sheriff's office that the station purge would begin soon; it was not a notification due to a fire or assistance needed. On 5/21/23, the repair was completed by replacing the tubing. The affected unit was restarted at approximately 13:11. |