GD incident on 2023-07-11 — LA

Operator
Centerpoint Energy Resources Corporation
Cause
Other Incident Cause
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$1,213,000
Incident datetime
2023-07-11 00:00 UTC
Report number
Location
LA, CALCASIEU
Narrative
Reported indication of leak on friday june 9, 2023. After initial investigation and squeezing 2" main, it was determined that leak was probable on 6" steel main. More investigation revealed that we would have to bore in new pipe to replace leaking facility. It was then discovered that cost would exceed reportable criteria and a call to the nrc was placed on monday june 12, 2023 at 14:35 pm central time. Ongoing repairs and 24 hour monitoring continued until wednesday june 21, 2023 when indications revealed that leak may be getting worse and a decision was made to turn system off. System was completely purged @ 1:20 am thursday june 22, 2023. Repairs were complete and system returned to service on friday june 23, 2023.
Detailed record list
Report Received Date
2023-07-11 00:00:00
Iyear
2023.0
Report Number
20230034.0
Supplemental Number
38874.0
Report Type
Supplemental Final
Operator Id
Name
Centerpoint Energy Resources Corporation
Operator Street Address
1111 Louisiana St
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002.0
Time Zone
Central
Daylight Savings Ind
Yes
Location Street Address
Highway 108 At Bayou Dinde
Location City Name
Sulphur
Location County Name
Calcasieu
Location State Abbreviation
LA
Location Postal Code
70665.0
Location Latitude
Location Longitude
Flow Cont Key Crit Ind
Yes
Nrc Rpt Num
Commodity Released Type
Natural Gas
Unintentional Release
384.72
Intentional Release
0.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Num Pub Evacuated
0.0
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Federal
No
Location Type
Utility Right-Of-Way / Easement
Incident Area Type
Underground
Incident Area Subtype
Other
Incident Area Details
Under Waterway
Depth Of Cover
48.0
Other Underground Facilities
No
Crossing
Yes
Water Crossing Ind
Yes
Water Type
Uncased
Water Name
Bayou Dinde
Water Depth
13
Water Subtype
Below Water, Pipe Buried Below Bottom (Not In Bored/drilled Crossing)
Pipe Facility Type
Investor Owned
System Part Involved
Main
Installation Year
1982.0
Manufactured Year
1981.0
Pipe Diameter
6.0
Pipe Specification
Api 5l Grade B
Pipe Manufacturer
Jones And Laughlin
Material Involved
Steel
Steel Seam Type
Longitudinal Erw - Unknown Frequency
Wt Steel
0.28
Release Type
Leak
Leak Type
Other
Leak Type Other
Not Excavated
Class Location Type
Class 3 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
1213000.0
Est Cost Emergency
20594.0
Est Cost Other
12540.0
Est Cost Other Details
Boom Rental To Contain Area For Monitoring.
Gas Cost In Mcf
3.7
Est Cost Unintentional Release
1423.0
Est Cost Intentional Release
0.0
Prpty
1247557.0
Commercial Affected
1.0
Industrial Affected
3.0
Residences Affected
0.0
Num Persons Hosp Not Ovnght
0.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
0.0
Num Business Building Affctd
0.0
Accident Psig
430.0
Normal Psig
430.0
Mop Psig
500.0
Mop Cfr Section
192.619(A)(2)
Maop Established Date
1982-06-17 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
By-Pass
Gas Odorized Lvl Not Msrd Ind
Yes
Scada In Place Ind
No
Accident Identifier
Notification From Public
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Incident Cause
Cause Details
Unknown
Other Type
Unknown
Unknown Subtype
Investigation Complete, Cause Of Incident Unknown
Incident Unknown Comments
Replaced Main And Abandoned Steel Main In Place. Location Of Leak Is Under Water Crossing And Was Not Verified. Decision Was Made Not To Remove Pipe Due To Excessive Costs And Environmental Concerns.
Preparer Name
J**** T*** H*****
Preparer Title
Operations Specialist
Preparer Email
J***********@c****************.com
Preparer Telephone
337-256-2161
Preparer Fax
337-373-1520
Local Contact Name
D****** B******** J*
Local Contact Email
D******************@c****************.com
Local Contact Telephone
337-475-6362
Authorizer Name
D****** B******** J*
Authorizer Title
Region Operations Director
Authorizer Telephone
337-475-6362
Authorizer Email
D******************@c****************.com
Narrative
R***************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************@ 1:20 am thursday june 22, 2023. ****************************************************************************.
Report Received Date 2023-07-11 00:00:00
Iyear 2023.0
Report Number 20230034.0
Supplemental Number 38874.0
Report Type Supplemental Final
Operator Id 4499 PHMSA Enforcement
Name Centerpoint Energy Resources Corporation
Operator Street Address 1111 Louisiana St
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002.0
Time Zone Central
Daylight Savings Ind Yes
Location Street Address Highway 108 At Bayou Dinde
Location City Name Sulphur
Location County Name Calcasieu
Location State Abbreviation LA
Location Postal Code 70665.0
Location Latitude 30.203065 Google Maps OpenStreetMap
Location Longitude -93.32526 Google Maps OpenStreetMap
Flow Cont Key Crit Ind Yes
Nrc Rpt Num 1369874.0 NRC Report How to search
Commodity Released Type Natural Gas
Unintentional Release 384.72
Intentional Release 0.0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Ignite Ind No
Num Pub Evacuated 0.0
Communication State Fed Ind Yes
Party Initiated Communication Operator
Federal No
Location Type Utility Right-Of-Way / Easement
Incident Area Type Underground
Incident Area Subtype Other
Incident Area Details Under Waterway
Depth Of Cover 48.0
Other Underground Facilities No
Crossing Yes
Water Crossing Ind Yes
Water Type Uncased
Water Name Bayou Dinde
Water Depth 13
Water Subtype Below Water, Pipe Buried Below Bottom (Not In Bored/drilled Crossing)
Pipe Facility Type Investor Owned
System Part Involved Main
Installation Year 1982.0
Manufactured Year 1981.0
Pipe Diameter 6.0
Pipe Specification Api 5l Grade B
Pipe Manufacturer Jones And Laughlin
Material Involved Steel
Steel Seam Type Longitudinal Erw - Unknown Frequency
Wt Steel 0.28
Release Type Leak
Leak Type Other
Leak Type Other Not Excavated
Class Location Type Class 3 Location
Est Cost Oper Paid 0.0
Est Cost Prop Damage 1213000.0
Est Cost Emergency 20594.0
Est Cost Other 12540.0
Est Cost Other Details Boom Rental To Contain Area For Monitoring.
Gas Cost In Mcf 3.7
Est Cost Unintentional Release 1423.0
Est Cost Intentional Release 0.0
Prpty 1247557.0
Commercial Affected 1.0
Industrial Affected 3.0
Residences Affected 0.0
Num Persons Hosp Not Ovnght 0.0
Num Injured Treated By Emt 0.0
Num Resident Building Affctd 0.0
Num Business Building Affctd 0.0
Accident Psig 430.0
Normal Psig 430.0
Mop Psig 500.0
Mop Cfr Section 192.619(A)(2) View CFR 49 §192
Maop Established Date 1982-06-17 00:00:00
Accident Pressure Pressure Did Not Exceed Maop
Gas Odorized System Type By-Pass
Gas Odorized Lvl Not Msrd Ind Yes
Scada In Place Ind No
Accident Identifier Notification From Public
Investigation Status No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Other Incident Cause
Cause Details Unknown
Other Type Unknown
Unknown Subtype Investigation Complete, Cause Of Incident Unknown
Incident Unknown Comments Replaced Main And Abandoned Steel Main In Place. Location Of Leak Is Under Water Crossing And Was Not Verified. Decision Was Made Not To Remove Pipe Due To Excessive Costs And Environmental Concerns.
Preparer Name J**** T*** H*****
Preparer Title Operations Specialist
Preparer Email J***********@c****************.com
Preparer Telephone 337-256-2161
Preparer Fax 337-373-1520
Local Contact Name D****** B******** J*
Local Contact Email D******************@c****************.com
Local Contact Telephone 337-475-6362
Authorizer Name D****** B******** J*
Authorizer Title Region Operations Director
Authorizer Telephone 337-475-6362
Authorizer Email D******************@c****************.com
Narrative R***************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************@ 1:20 am thursday june 22, 2023. ****************************************************************************.

All rights reserved. Copyright © by ClearPHMSA