GTG incident on 2023-02-17 — NC

Operator
Piedmont Natural Gas Co Inc
Cause
Other Outside Force Damage
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$200,000
Incident datetime
2023-02-17 00:00 UTC
Report number
Location
NC
Narrative
Piedmont natural gas responded to a report of a vehicle damaging a mainline valve. Upon arrival operator observed visual damage of the blowdown stack and detected a small gas leak from a grease fitting on the mainline valve. Field operations monitored a minor gas reading well below lel, enabling field operations to safely hand dig to expose the below ground piping to investigate the extent of the damage without any isolation of this segment. Gas flowed normally during the impacted segment of line 272 containing 272-mlv-3 site during the entirety of the repair response. Unable to determine gas volume.
Detailed record list
Report Received Date
2023-02-17 00:00:00
Iyear
2023
Report Number
20230018
Supplemental Number
37765
Report Type
Supplemental Final
Operator Id
Name
Piedmont Natural Gas Co Inc
Operator Street Address
525 South Tryon Street
Operator City Name
Charlotte
Operator State Abbreviation
NC
Operator Postal Code
28202
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Nrc Rpt Num
Additional Nrc Report Numbers
1358492
Commodity Released Type
Natural Gas
Unintentional Release
0.01
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
Replacement Was On Normally Closed Bypass Piping Around Open Mainline Valve.
Ignite Ind
No
Upstream Action Taken
Operational Control
Upstream Oprtnl Cntrl Detail
Flow Upstream Was Monitored By Field Operations.
Downstream Action Taken
Operational Control
Downstream Oprtnl Cntrl Detail
Flow Downstream Was Monitored By Field Operations.
Num Pub Evacuated
0
On Off Shore
Onshore
Onshore State Abbreviation
Nc
Onshore Postal Code
28146
Onshore City Name
Salisbury
Onshore County Name
Rowan
Designated Location
Not Applicable
Pipe Fac Name
Line 272-Mlv-3
Segment Name
Line 272
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
System Part Involved
Onshore Pipeline, Including Valve Sites
Item Involved
Valve
Valve Type
Mainline
Valve Mainline Type
Ball
Valve Manufacturer
Rockwell
Installation Year
1998
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Seal Or Packing
Class Location Type
Class 2 Location
Could Be Hca
No
Pir Radius
137
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
0
Est Cost Intentional Release
0
Est Cost Prop Damage
200000
Est Cost Emergency
5000
Est Cost Other
0
Gas Cost In Mcf
0.1
Prpty
205000
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
658
Gas Flow In Pipe In Mcf
3300
Mop Psig
900
Mop Cfr Section
192.619(A)(2)
Maop Established Date
1998-11-16 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
Yes
Gas Odorized Ind
Yes
Length Segment Isolated
3700
Internal Inspection Ind
No
Diameter Change Ind
Yes
Unsuitable Mainline Ind
Yes
Tight Mitered Ind
Yes
Other Restrictions Ind
Yes
Operation Complications Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The incident was too small to register on the scada system.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Outside Force Damage
Cause Details
Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation
Outside Force Type
Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation
Vehicle Subtype
Third Party
Driver Issued Citation Ind
Unknown
Driver In Control Ind
Unknown
Estimated Speed Unknown Ind
Yes
Vehicle Type
Passenger Car
Vehicle Travel From
Off-Road
Vehicle Travel Distance Ft
50
Protections Installed Ind
Yes
Protection Bollards Post Ind
Yes
Protection Barricades Ind
Yes
Preparer Name
C********** R******
Preparer Title
Gas Regulatory Compliance Analyst
Preparer Email
C******************@d**********.com
Preparer Telephone
704-731-4680
Authorizer Name
F***** B****
Authorizer Title
Manager- Pipeline Safety
Authorizer Telephone
704-731-4618
Authorizer Email
F***********@d**********.com
Narrative
Piedmont natural gas responded to a report of a vehicle damaging a mainline valve. Upon arrival operator observed visual damage of the blowdown stack and detected a small gas leak from a grease fitting on the mainline valve. Field operations monitored a minor gas reading well below lel, enabling field operations to safely hand dig to expose the below ground piping to investigate the extent of the damage without any isolation of this segment. Gas flowed normally during the impacted segment of line 272 containing 272-mlv-3 site during the entirety of the repair response. Unable to determine gas volume.
Report Received Date 2023-02-17 00:00:00
Iyear 2023
Report Number 20230018
Supplemental Number 37765
Report Type Supplemental Final
Operator Id 15518 PHMSA Enforcement
Name Piedmont Natural Gas Co Inc
Operator Street Address 525 South Tryon Street
Operator City Name Charlotte
Operator State Abbreviation NC
Operator Postal Code 28202
Time Zone Eastern
Daylight Savings Ind Yes
Location Latitude 35.61886 Google Maps OpenStreetMap
Location Longitude -80.3958 Google Maps OpenStreetMap
Nrc Rpt Num 1358400 NRC Report How to search
Additional Nrc Report Numbers 1358492
Commodity Released Type Natural Gas
Unintentional Release 0.01
Intentional Release 0
Accompanying Liquid 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Status When Identified Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind No
Shutdown Explain Replacement Was On Normally Closed Bypass Piping Around Open Mainline Valve.
Ignite Ind No
Upstream Action Taken Operational Control
Upstream Oprtnl Cntrl Detail Flow Upstream Was Monitored By Field Operations.
Downstream Action Taken Operational Control
Downstream Oprtnl Cntrl Detail Flow Downstream Was Monitored By Field Operations.
Num Pub Evacuated 0
On Off Shore Onshore
Onshore State Abbreviation Nc
Onshore Postal Code 28146
Onshore City Name Salisbury
Onshore County Name Rowan
Designated Location Not Applicable
Pipe Fac Name Line 272-Mlv-3
Segment Name Line 272
Federal No
Location Type Pipeline Right-Of-Way
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Intrastate
System Part Involved Onshore Pipeline, Including Valve Sites
Item Involved Valve
Valve Type Mainline
Valve Mainline Type Ball
Valve Manufacturer Rockwell
Installation Year 1998
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Leak
Leak Type Seal Or Packing
Class Location Type Class 2 Location
Could Be Hca No
Pir Radius 137
Heat Damage Ind No
Non Heat Damage Ind No
Did Occur In Mca Ind No
Est Cost Oper Paid 0
Est Cost Unintentional Release 0
Est Cost Intentional Release 0
Est Cost Prop Damage 200000
Est Cost Emergency 5000
Est Cost Other 0
Gas Cost In Mcf 0.1
Prpty 205000
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Wildlife Impact Ind No
Accident Psig 658
Gas Flow In Pipe In Mcf 3300
Mop Psig 900
Mop Cfr Section 192.619(A)(2) View CFR 49 §192
Maop Established Date 1998-11-16 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Maop
Pressure Restriction Ind No
Gas Required Odorized Ind Yes
Gas Odorized Ind Yes
Length Segment Isolated 3700
Internal Inspection Ind No
Diameter Change Ind Yes
Unsuitable Mainline Ind Yes
Tight Mitered Ind Yes
Other Restrictions Ind Yes
Operation Complications Ind No
Pipeline Function Transmission System
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Accident Identifier Notification From Emergency Responder
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details The incident was too small to register on the scada system.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Other Outside Force Damage
Cause Details Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation
Outside Force Type Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation
Vehicle Subtype Third Party
Driver Issued Citation Ind Unknown
Driver In Control Ind Unknown
Estimated Speed Unknown Ind Yes
Vehicle Type Passenger Car
Vehicle Travel From Off-Road
Vehicle Travel Distance Ft 50
Protections Installed Ind Yes
Protection Bollards Post Ind Yes
Protection Barricades Ind Yes
Preparer Name C********** R******
Preparer Title Gas Regulatory Compliance Analyst
Preparer Email C******************@d**********.com
Preparer Telephone 704-731-4680
Authorizer Name F***** B****
Authorizer Title Manager- Pipeline Safety
Authorizer Telephone 704-731-4618
Authorizer Email F***********@d**********.com
Narrative Piedmont natural gas responded to a report of a vehicle damaging a mainline valve. Upon arrival operator observed visual damage of the blowdown stack and detected a small gas leak from a grease fitting on the mainline valve. Field operations monitored a minor gas reading well below lel, enabling field operations to safely hand dig to expose the below ground piping to investigate the extent of the damage without any isolation of this segment. Gas flowed normally during the impacted segment of line 272 containing 272-mlv-3 site during the entirety of the repair response. Unable to determine gas volume.

All rights reserved. Copyright © by ClearPHMSA