Incident details
Operator, cause, commodity and consequences with raw source fields.
GD incident on 2022-12-20 — MI
Operator
Consumers Energy Co
Cause
Other Outside Force Damage
Commodity
Natural Gas
Program
GD
Damage and Injuries
1 fatality
0 injuries
Property damage (nominal)
$2,147
Incident datetime
2022-12-20 08:48
Report number
Location
MI, VAN BUREN
Narrative
On tuesday, december 20, 2022, at approximately 08:48 hours, consumers energy received notification from emergency personnel of a house fire at 1014 3rd street, bangor, (van buren county) michigan. A gas service worker (gsw) was dispatched and arrived at the site at approximately 09:25 hours and confirmed the structure fire with a release at the natural gas equipment (meter/riser). The gsw advised a distribution crew would be needed to contain the blowing gas. The gsw began excavating at a remote location near the pipeline in preparation for squeezing the 5/8-inch plastic pipeline, the plastic pipeline (service) was inserted in a steel pipeline making it necessary for additional equipment utilized by gas distribution. Distribution arrived onsite at approximately 10:45 hours and squeezed the pipeline stopping gas from blowing at approximately 10:48 hours. Emergency responders were onsite and confirmed one fatality and multiple persons requiring medical attention were transported to the local hospital. Further investigation performed by the michigan state police confirmed the release at the natural gas equipment (meter/riser) was not the primary cause of the fire. The natural gas equipment was compromised by the structure fire resulting in a release at the natural gas equipment. This report is being submitted because it cannot be determined if the secondary release at the natural gas facilities contributed to the fatality.
Detailed record list
Occurred At
2022-12-20 08:48:00
Year
2022
Report Received Date
2023-01-19 00:00:00
Iyear
2022.0
Report Number
20230003.0
Supplemental Number
37594.0
Report Type
Original Final
Operator Id
2748
Name
Consumers Energy Co
Operator Street Address
One Energy Plaza
Operator City Name
Jackson
Operator State Abbreviation
MI
Operator Postal Code
49201
Local Datetime
2022-12-20 08:48:00
Time Zone
Eastern
Daylight Savings Ind
No
Location Street Address
1014 Third Street
Location City Name
Bangor
Location County Name
Van Buren
Location State Abbreviation
MI
Location Postal Code
49013
Location Latitude
42.31903
Location Longitude
-86.11671
Flow Cont Squeeze Off Ind
Yes
Nrc Rpt Datetime
2022-12-20 13:35:00
Nrc Rpt Num
1355473
Additional Nrc Report Numbers
1355602
Commodity Released Type
Natural Gas
Unintentional Release
6.6
Intentional Release
0.0
Fatality Ind
Yes
Num Emp Fatalities
0
Num Contr Fatalities
0
Num Er Fatalities
0
Num Worker Fatalities
0
Num Gp Fatalities
1
Fatal
1
Injury Ind
No
Injure
0
Ignite Ind
Yes
Ignite Datetime
2022-12-20 08:48:00
How Extinguished
Allowed To Burn Out
Gas Consumed By Fire In Mcf
6.6
Explode Ind
No
Num Pub Evacuated
0.0
Incident Identified Datetime
2022-12-20 08:48:00
On Site Datetime
2022-12-20 09:25:00
Federal
No
Location Type
Private Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance (E.g. Value Or Regulator Station, Outdoor Meter Set)
Crossing
No
Pipe Facility Type
Municipally Owned
System Part Involved
Service Riser
Installation Year
1974.0
Customer Type
Single Family Residential
Was Efv Installed Before Ind
No
Curb Valve Inst Before Inc Ind
No
Material Involved
Plastic
Plastic Type
Polyethylene (Pe)
Plastic Sdr
0.09
Material Pe Pipe Code
2708
Release Type
Leak
Leak Type
Pinhole
Class Location Type
Class 3 Location
Est Cost Oper Paid
143500.0
Est Cost Prop Damage
2147.0
Est Cost Emergency
548.0
Est Cost Other
0.0
Gas Cost In Mcf
6.17
Est Cost Unintentional Release
41.0
Est Cost Intentional Release
0.0
Prpty
146236.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
1.0
Num Persons Hosp Not Ovnght
2.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
1.0
Num Business Building Affctd
0.0
Accident Psig
48.0
Normal Psig
48.0
Mop Psig
60.0
Mop Cfr Section
192.619(A)(2)
Maop Established Date
1974-07-24 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Injection Pump
Gas Odorized Lvl Not Msrd Ind
Yes
Scada In Place Ind
No
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Outside Force Damage
Cause Details
Nearby Industrial, Man-Made, Or Other Fire/explosion As Primary Cause Of Incident
Outside Force Type
Nearby Industrial, Man-Made, Or Other Fire/explosion As Primary Cause Of Incident
Preparer Name
C******* Q* K***
Preparer Title
Senior Engineering Technical Analyst Ii
Preparer Email
C************@c********.com
Preparer Telephone
989-280-2963
Local Contact Name
C******* Q* K***
Local Contact Email
C************@c********.com
Local Contact Telephone
989-280-2963
Authorizer Name
J**** E* P****
Authorizer Title
Gas Compliance Manager
Authorizer Telephone
989-598-5031
Authorizer Email
J**********@c********.com
Narrative
On tuesday, december 20, 2022, at approximately 08:48 hours, consumers energy received notification from emergency personnel of a house fire at 1014 3rd street, bangor, (van buren county) michigan. A gas service worker (gsw) was dispatched and arrived at the site at approximately 09:25 hours and confirmed the structure fire with a release at the natural gas equipment (meter/riser). The gsw advised a distribution crew would be needed to contain the blowing gas. The gsw began excavating at a remote location near the pipeline in preparation for squeezing the 5/8-inch plastic pipeline, the plastic pipeline (service) was inserted in a steel pipeline making it necessary for additional equipment utilized by gas distribution. Distribution arrived onsite at approximately 10:45 hours and squeezed the pipeline stopping gas from blowing at approximately 10:48 hours. Emergency responders were onsite and confirmed one fatality and multiple persons requiring medical attention were transported to the local hospital. Further investigation performed by the michigan state police confirmed the release at the natural gas equipment (meter/riser) was not the primary cause of the fire. The natural gas equipment was compromised by the structure fire resulting in a release at the natural gas equipment. This report is being submitted because it cannot be determined if the secondary release at the natural gas facilities contributed to the fatality.
| Occurred At | 2022-12-20 08:48:00 |
|---|---|
| Year | 2022 |
| Report Received Date | 2023-01-19 00:00:00 |
| Iyear | 2022.0 |
| Report Number | 20230003.0 |
| Supplemental Number | 37594.0 |
| Report Type | Original Final |
| Operator Id | 2748 PHMSA Enforcement |
| Name | Consumers Energy Co |
| Operator Street Address | One Energy Plaza |
| Operator City Name | Jackson |
| Operator State Abbreviation | MI |
| Operator Postal Code | 49201 |
| Local Datetime | 2022-12-20 08:48:00 |
| Time Zone | Eastern |
| Daylight Savings Ind | No |
| Location Street Address | 1014 Third Street |
| Location City Name | Bangor |
| Location County Name | Van Buren |
| Location State Abbreviation | MI |
| Location Postal Code | 49013 |
| Location Latitude | 42.31903 Google Maps OpenStreetMap |
| Location Longitude | -86.11671 Google Maps OpenStreetMap |
| Flow Cont Squeeze Off Ind | Yes |
| Nrc Rpt Datetime | 2022-12-20 13:35:00 |
| Nrc Rpt Num | 1355473 NRC Report How to search |
| Additional Nrc Report Numbers | 1355602 |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 6.6 |
| Intentional Release | 0.0 |
| Fatality Ind | Yes |
| Num Emp Fatalities | 0 |
| Num Contr Fatalities | 0 |
| Num Er Fatalities | 0 |
| Num Worker Fatalities | 0 |
| Num Gp Fatalities | 1 |
| Fatal | 1 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | Yes |
| Ignite Datetime | 2022-12-20 08:48:00 |
| How Extinguished | Allowed To Burn Out |
| Gas Consumed By Fire In Mcf | 6.6 |
| Explode Ind | No |
| Num Pub Evacuated | 0.0 |
| Incident Identified Datetime | 2022-12-20 08:48:00 |
| On Site Datetime | 2022-12-20 09:25:00 |
| Federal | No |
| Location Type | Private Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance (E.g. Value Or Regulator Station, Outdoor Meter Set) |
| Crossing | No |
| Pipe Facility Type | Municipally Owned |
| System Part Involved | Service Riser |
| Installation Year | 1974.0 |
| Customer Type | Single Family Residential |
| Was Efv Installed Before Ind | No |
| Curb Valve Inst Before Inc Ind | No |
| Material Involved | Plastic |
| Plastic Type | Polyethylene (Pe) |
| Plastic Sdr | 0.09 |
| Material Pe Pipe Code | 2708 |
| Release Type | Leak |
| Leak Type | Pinhole |
| Class Location Type | Class 3 Location |
| Est Cost Oper Paid | 143500.0 |
| Est Cost Prop Damage | 2147.0 |
| Est Cost Emergency | 548.0 |
| Est Cost Other | 0.0 |
| Gas Cost In Mcf | 6.17 |
| Est Cost Unintentional Release | 41.0 |
| Est Cost Intentional Release | 0.0 |
| Prpty | 146236.0 |
| Commercial Affected | 0.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 1.0 |
| Num Persons Hosp Not Ovnght | 2.0 |
| Num Injured Treated By Emt | 0.0 |
| Num Resident Building Affctd | 1.0 |
| Num Business Building Affctd | 0.0 |
| Accident Psig | 48.0 |
| Normal Psig | 48.0 |
| Mop Psig | 60.0 |
| Mop Cfr Section | 192.619(A)(2) View CFR 49 §192 |
| Maop Established Date | 1974-07-24 00:00:00 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Gas Odorized System Type | Injection Pump |
| Gas Odorized Lvl Not Msrd Ind | Yes |
| Scada In Place Ind | No |
| Accident Identifier | Notification From Emergency Responder |
| Investigation Status | No, the facility was not monitored by a controller(s) at the time of the incident |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Other Outside Force Damage |
| Cause Details | Nearby Industrial, Man-Made, Or Other Fire/explosion As Primary Cause Of Incident |
| Outside Force Type | Nearby Industrial, Man-Made, Or Other Fire/explosion As Primary Cause Of Incident |
| Preparer Name | C******* Q* K*** |
| Preparer Title | Senior Engineering Technical Analyst Ii |
| Preparer Email | C************@c********.com |
| Preparer Telephone | 989-280-2963 |
| Local Contact Name | C******* Q* K*** |
| Local Contact Email | C************@c********.com |
| Local Contact Telephone | 989-280-2963 |
| Authorizer Name | J**** E* P**** |
| Authorizer Title | Gas Compliance Manager |
| Authorizer Telephone | 989-598-5031 |
| Authorizer Email | J**********@c********.com |
| Narrative | On tuesday, december 20, 2022, at approximately 08:48 hours, consumers energy received notification from emergency personnel of a house fire at 1014 3rd street, bangor, (van buren county) michigan. A gas service worker (gsw) was dispatched and arrived at the site at approximately 09:25 hours and confirmed the structure fire with a release at the natural gas equipment (meter/riser). The gsw advised a distribution crew would be needed to contain the blowing gas. The gsw began excavating at a remote location near the pipeline in preparation for squeezing the 5/8-inch plastic pipeline, the plastic pipeline (service) was inserted in a steel pipeline making it necessary for additional equipment utilized by gas distribution. Distribution arrived onsite at approximately 10:45 hours and squeezed the pipeline stopping gas from blowing at approximately 10:48 hours. Emergency responders were onsite and confirmed one fatality and multiple persons requiring medical attention were transported to the local hospital. Further investigation performed by the michigan state police confirmed the release at the natural gas equipment (meter/riser) was not the primary cause of the fire. The natural gas equipment was compromised by the structure fire resulting in a release at the natural gas equipment. This report is being submitted because it cannot be determined if the secondary release at the natural gas facilities contributed to the fatality. |
External Resources