Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2022-11-21 — TX
Operator
Dapl-Etco Operations Management, Llc
Cause
Material Failure Of Pipe Or Weld
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$30,268
Incident datetime
2022-11-21 10:21
Report number
Location
TX
Narrative
On 11/21/2022 at 10:21, operations personnel discovered a crude oil leak at the johnsons corner pump station building on the unit 3 suction piping. Station was shutdown to identify where leak was originating. Once found, unit 3 was isolated and locked out, and units 1 and 2 were restarted. Approximately 92 gallons of crude oil was released to a concrete floor inside an engine room. The released material was collected using a vacuum truck. Any residual oil left on the concrete surface was removed with absorbent pads. A visual examination determined the piping cracked just above the weld where the 2-inch drain line ties into the suction piping at the 6 oclock position. Operations performed segmented cutout and installed a 24-inch pup of pre-tested x-70 pipe. Due to initial assessment, operations went ahead and performed, like/kind, replacement of the other two systems due to susceptibility of similar events. The failed section of pipe was sent out for metallurgical analysis to determine failure mechanism. Upon receipt of laboratory report a supplemental 7000.1 report will be filed. Supplemental the results of the analysis indicate that the pipe leaked as a result of fatigue crack initiation and growth at the fillet weld of the reinforcement saddle. The fatigue crack initiated at the pipe side weld toe of the fillet weld that joined the reinforcement saddle to the suction pipe. The crack propagated through-wall, producing the leak. There was no evidence that metallurgical defects played a role in the failure. Other pump stations on the pipeline system were inspected for like and kind drain line installations and none were found.
Detailed record list
Report Received Date
2022-12-15 00:00:00
Iyear
2022
Report Number
20220285
Supplemental Number
38380
Report Type
Supplemental Final
Operator Id
39205
Name
Dapl-Etco Operations Management, Llc
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2022-11-21 10:21:00
Time Zone
Central
Daylight Savings Ind
No
Location Latitude
47.79928474
Location Longitude
-102.923979
Commodity Released Type
Crude Oil
Unintentional Release Bbls
2.19
Recovered Bbls
2.19
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2022-11-21 10:21:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-11-21 10:30:00
Restart Datetime
2022-11-21 12:00:00
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2022-11-21 14:31:00
On Site Datetime
2022-11-21 10:21:00
Confirmed Discovery Datetime
2022-11-21 10:21:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Qualified Indiv Notif Datetime
2022-11-21 10:21:00
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Johnson's Corner Pump Station
Segment Name
Pump Unit 3
Onshore State Abbreviation
Nd
Onshore Postal Code
58854
Onshore City Name
Watford City
Onshore County Name
Mckenzie
Designated Location
Survey Station No.
Designated Name
0+00
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Inside A Building
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Weld, Including Heat-Affected Zone
Weld Subtype
Fillet Weld
Installation Year
2021
Manufactured Year
2019
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Crack
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
0
Est Cost Prop Damage
30268
Est Cost Emergency
2087
Est Cost Environmental
0
Est Cost Other
0
Prpty
32355
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
820
Mop Psig
1440
Mop Cfr Section
Subpart E Pressure Test �195.406(A)(3)
Maop Established Date
2021-06-07 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
A review of the accident determined that there were no control room actions that contributed to the event.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Material Failure Of Pipe Or Weld
Cause Details
Design-, Construction-, Installation-, Or Fabrication-Related
Metallurgical Ind
Yes
Failure Type
Design-, Construction-, Installation-, Or Fabrication-Related
Fatigue Vibr Related
Yes
Failure Subtype
Mechanical Vibration
Additional Crack Ind
Yes
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
Yes
Exm Radiography Rcnt Year
2021
Exm Radiography Rcnt Ind
Yes
Preparer Name
T*** N*******
Preparer Title
Director - Regulatory Compliance
Preparer Email
T************@e*************.com
Preparer Telephone
713-989-7126
Prepared Date
2023-08-10 00:00:00
Authorizer Name
T*** N*******
Authorizer Telephone
713-989-7126
Authorizer Title
Director - Regulatory Compliance
Authorizer Email
T************@e*************.com
Narrative
On 11/21/2022 at 10:21, operations personnel discovered a crude oil leak at the johnsons corner pump station building on the unit 3 suction piping. Station was shutdown to identify where leak was originating. Once found, unit 3 was isolated and locked out, and units 1 and 2 were restarted. Approximately 92 gallons of crude oil was released to a concrete floor inside an engine room. The released material was collected using a vacuum truck. Any residual oil left on the concrete surface was removed with absorbent pads. A visual examination determined the piping cracked just above the weld where the 2-inch drain line ties into the suction piping at the 6 oclock position. Operations performed segmented cutout and installed a 24-inch pup of pre-tested x-70 pipe. Due to initial assessment, operations went ahead and performed, like/kind, replacement of the other two systems due to susceptibility of similar events. The failed section of pipe was sent out for metallurgical analysis to determine failure mechanism. Upon receipt of laboratory report a supplemental 7000.1 report will be filed. Supplemental the results of the analysis indicate that the pipe leaked as a result of fatigue crack initiation and growth at the fillet weld of the reinforcement saddle. The fatigue crack initiated at the pipe side weld toe of the fillet weld that joined the reinforcement saddle to the suction pipe. The crack propagated through-wall, producing the leak. There was no evidence that metallurgical defects played a role in the failure. Other pump stations on the pipeline system were inspected for like and kind drain line installations and none were found.
| Report Received Date | 2022-12-15 00:00:00 |
|---|---|
| Iyear | 2022 |
| Report Number | 20220285 |
| Supplemental Number | 38380 |
| Report Type | Supplemental Final |
| Operator Id | 39205 PHMSA Enforcement |
| Name | Dapl-Etco Operations Management, Llc |
| Operator Street Address | 1300 Main Street |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77002 |
| Local Datetime | 2022-11-21 10:21:00 |
| Time Zone | Central |
| Daylight Savings Ind | No |
| Location Latitude | 47.79928474 Google Maps OpenStreetMap |
| Location Longitude | -102.923979 Google Maps OpenStreetMap |
| Commodity Released Type | Crude Oil |
| Unintentional Release Bbls | 2.19 |
| Recovered Bbls | 2.19 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2022-11-21 10:21:00 |
| System Part Involved | Onshore Pump/meter Station Equipment And Piping |
| On Off Shore | Onshore |
| Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2022-11-21 10:30:00 |
| Restart Datetime | 2022-11-21 12:00:00 |
| Communication State Fed Ind | Yes |
| Party Initiated Communication | Operator |
| Initial Responder Com Datetime | 2022-11-21 14:31:00 |
| On Site Datetime | 2022-11-21 10:21:00 |
| Confirmed Discovery Datetime | 2022-11-21 10:21:00 |
| Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
| Ignite Ind | No |
| Notify Qualified Indiv Ind | Yes |
| Qualified Indiv Notif Datetime | 2022-11-21 10:21:00 |
| Oil Spill Removal Org Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Johnson's Corner Pump Station |
| Segment Name | Pump Unit 3 |
| Onshore State Abbreviation | Nd |
| Onshore Postal Code | 58854 |
| Onshore City Name | Watford City |
| Onshore County Name | Mckenzie |
| Designated Location | Survey Station No. |
| Designated Name | 0+00 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Inside A Building |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Weld, Including Heat-Affected Zone |
| Weld Subtype | Fillet Weld |
| Installation Year | 2021 |
| Manufactured Year | 2019 |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Crack |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | No |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 0 |
| Est Cost Prop Damage | 30268 |
| Est Cost Emergency | 2087 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 32355 |
| Num Persons Hosp Not Ovnght | 0 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 0 |
| Num Business Building Affctd | 0 |
| Accident Psig | 820 |
| Mop Psig | 1440 |
| Mop Cfr Section | Subpart E Pressure Test �195.406(A)(3) View CFR 49 §192 |
| Maop Established Date | 2021-06-07 00:00:00 |
| Maop Reversal Flow Ind | No |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | A review of the accident determined that there were no control room actions that contributed to the event. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Material Failure Of Pipe Or Weld |
| Cause Details | Design-, Construction-, Installation-, Or Fabrication-Related |
| Metallurgical Ind | Yes |
| Failure Type | Design-, Construction-, Installation-, Or Fabrication-Related |
| Fatigue Vibr Related | Yes |
| Failure Subtype | Mechanical Vibration |
| Additional Crack Ind | Yes |
| Collected Data Ind | No |
| Has Hydrtst Conduc Before Ind | No |
| Direct Asmnt Conducted | No |
| Non Destructive Exam Ind | Yes |
| Exm Radiography Rcnt Year | 2021 |
| Exm Radiography Rcnt Ind | Yes |
| Preparer Name | T*** N******* |
| Preparer Title | Director - Regulatory Compliance |
| Preparer Email | T************@e*************.com |
| Preparer Telephone | 713-989-7126 |
| Prepared Date | 2023-08-10 00:00:00 |
| Authorizer Name | T*** N******* |
| Authorizer Telephone | 713-989-7126 |
| Authorizer Title | Director - Regulatory Compliance |
| Authorizer Email | T************@e*************.com |
| Narrative | On 11/21/2022 at 10:21, operations personnel discovered a crude oil leak at the johnsons corner pump station building on the unit 3 suction piping. Station was shutdown to identify where leak was originating. Once found, unit 3 was isolated and locked out, and units 1 and 2 were restarted. Approximately 92 gallons of crude oil was released to a concrete floor inside an engine room. The released material was collected using a vacuum truck. Any residual oil left on the concrete surface was removed with absorbent pads. A visual examination determined the piping cracked just above the weld where the 2-inch drain line ties into the suction piping at the 6 oclock position. Operations performed segmented cutout and installed a 24-inch pup of pre-tested x-70 pipe. Due to initial assessment, operations went ahead and performed, like/kind, replacement of the other two systems due to susceptibility of similar events. The failed section of pipe was sent out for metallurgical analysis to determine failure mechanism. Upon receipt of laboratory report a supplemental 7000.1 report will be filed. Supplemental the results of the analysis indicate that the pipe leaked as a result of fatigue crack initiation and growth at the fillet weld of the reinforcement saddle. The fatigue crack initiated at the pipe side weld toe of the fillet weld that joined the reinforcement saddle to the suction pipe. The crack propagated through-wall, producing the leak. There was no evidence that metallurgical defects played a role in the failure. Other pump stations on the pipeline system were inspected for like and kind drain line installations and none were found. |