HL incident on 2022-11-12 — TX
Operator
Express Holdings (Usa), Llc
Cause
Equipment Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$12,760
Incident datetime
2022-11-12 03:29
Report number
Location
TX
Narrative
On november 12, 2022 at 2:59 am cst, the edmonton control center received a seal fail alarm on unit 3 at moorefield station and the unit was locked out. At 3:29 am cst the edmonton control center received a sump alert and the moorefield station was shut down and isolated. An on-call technician was called out to investigate the alarm. At 4:30 am cst technician arrived at moorefield station and discovered approximately 10 gallons of crude oil had been released in the pump building. The source of the release was identified as a seal on the unit 3 pump. Additional resources arrived on site for cleanup and repairs. The majority of product was contained within the pump building on the concrete floor with a small amount that migrated out of the building and onto the gravel. All product was cleaned up and less than one cubic yard of contaminated soil was removed and properly disposed of. The investigation determined the cause of the release was due to normal wear and tear of the seal from years of service. The seal was replaced and unit 3 was returned to service.
Detailed record list
Report Received Date
2022-12-09 00:00:00
Iyear
2022
Report Number
20220279
Supplemental Number
37450
Report Type
Original Final
Operator Id
31720
Name
Express Holdings (Usa), Llc
Operator Street Address
915 N Eldridge Parkway, Suite 1100
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77079
Local Datetime
2022-11-12 02:59:00
Time Zone
Central
Daylight Savings Ind
No
Location Latitude
40.686133
Location Longitude
-100.407531
Commodity Released Type
Crude Oil
Unintentional Release Bbls
0.24
Recovered Bbls
0.24
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Incident Identified Datetime
2022-11-12 03:29:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-11-12 03:29:00
Restart Datetime
2022-11-12 17:05:00
Communication State Fed Ind
No
On Site Datetime
2022-11-12 04:30:00
Confirmed Discovery Datetime
2022-11-12 04:30:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Notify Qualified Indiv Ind
No
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Moorefield Station
Segment Name
Unit 3 Pump
Onshore State Abbreviation
Ne
Onshore Postal Code
69039
Onshore City Name
Moorefield
Onshore County Name
Frontier
Designated Location
Milepost
Designated Name
1263
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Inside A Building
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Pump
Pump Type
Centrifugal
Pump Service Type
Mainline
Installation Year
1997
Manufactured Year
1997
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Seal Or Packing
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
16
Est Cost Prop Damage
12760
Est Cost Emergency
4450
Est Cost Environmental
1000
Est Cost Other
0
Prpty
18226
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
607
Mop Psig
1000
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
1996-11-26 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Pump Or Pump-Related Equipment
Eq Failure Type
Pump Or Pump-Related Equipment
Other Pump Ind
Seal/packing Failure
Eq Additional Other Ind
Yes
Eq Additional Other Details
Wear And Tear From Years Of Service
Preparer Name
S**** S****
Preparer Title
Sr Compliance Analyst
Preparer Email
S**********@e*******.com
Preparer Telephone
715-395-3620
Prepared Date
2022-12-09 00:00:00
Authorizer Name
L*** S**********
Authorizer Telephone
715-394-1584
Authorizer Title
Supervisor Us Regulatory Compliance
Authorizer Email
L***************@e*******.com
Narrative
On november 12, 2022 at 2:59 am cst, the edmonton control center received a seal fail alarm on unit 3 at moorefield station and the unit was locked out. At 3:29 am cst the edmonton control center received a sump alert and the moorefield station was shut down and isolated. An on-call technician was called out to investigate the alarm. At 4:30 am cst technician arrived at moorefield station and discovered approximately 10 gallons of crude oil had been released in the pump building. The source of the release was identified as a seal on the unit 3 pump. Additional resources arrived on site for cleanup and repairs. The majority of product was contained within the pump building on the concrete floor with a small amount that migrated out of the building and onto the gravel. All product was cleaned up and less than one cubic yard of contaminated soil was removed and properly disposed of. The investigation determined the cause of the release was due to normal wear and tear of the seal from years of service. The seal was replaced and unit 3 was returned to service.
| Report Received Date | 2022-12-09 00:00:00 |
|---|---|
| Iyear | 2022 |
| Report Number | 20220279 |
| Supplemental Number | 37450 |
| Report Type | Original Final |
| Operator Id | 31720 PHMSA Enforcement |
| Name | Express Holdings (Usa), Llc |
| Operator Street Address | 915 N Eldridge Parkway, Suite 1100 |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77079 |
| Local Datetime | 2022-11-12 02:59:00 |
| Time Zone | Central |
| Daylight Savings Ind | No |
| Location Latitude | 40.686133 Google Maps OpenStreetMap |
| Location Longitude | -100.407531 Google Maps OpenStreetMap |
| Commodity Released Type | Crude Oil |
| Unintentional Release Bbls | 0.24 |
| Recovered Bbls | 0.24 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations) |
| Incident Identified Datetime | 2022-11-12 03:29:00 |
| System Part Involved | Onshore Pump/meter Station Equipment And Piping |
| On Off Shore | Onshore |
| Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2022-11-12 03:29:00 |
| Restart Datetime | 2022-11-12 17:05:00 |
| Communication State Fed Ind | No |
| On Site Datetime | 2022-11-12 04:30:00 |
| Confirmed Discovery Datetime | 2022-11-12 04:30:00 |
| Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
| Ignite Ind | No |
| Notify Qualified Indiv Ind | No |
| Oil Spill Removal Org Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Moorefield Station |
| Segment Name | Unit 3 Pump |
| Onshore State Abbreviation | Ne |
| Onshore Postal Code | 69039 |
| Onshore City Name | Moorefield |
| Onshore County Name | Frontier |
| Designated Location | Milepost |
| Designated Name | 1263 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Inside A Building |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Pump |
| Pump Type | Centrifugal |
| Pump Service Type | Mainline |
| Installation Year | 1997 |
| Manufactured Year | 1997 |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Seal Or Packing |
| Wildlife Impact Ind | No |
| Soil Contamination | Yes |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 16 |
| Est Cost Prop Damage | 12760 |
| Est Cost Emergency | 4450 |
| Est Cost Environmental | 1000 |
| Est Cost Other | 0 |
| Prpty | 18226 |
| Num Persons Hosp Not Ovnght | 0 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 0 |
| Num Business Building Affctd | 0 |
| Accident Psig | 607 |
| Mop Psig | 1000 |
| Mop Cfr Section | Component Design Pressure �195.406(A)(2) View CFR 49 §192 |
| Maop Established Date | 1996-11-26 00:00:00 |
| Maop Reversal Flow Ind | No |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | Yes |
| Scada Conf Ind | Yes |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | Yes, specify investigation result(s): (select all that apply) |
| Invest No Control Room Ind | Yes |
| Invest No Controller Ind | Yes |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Pump Or Pump-Related Equipment |
| Eq Failure Type | Pump Or Pump-Related Equipment |
| Other Pump Ind | Seal/packing Failure |
| Eq Additional Other Ind | Yes |
| Eq Additional Other Details | Wear And Tear From Years Of Service |
| Preparer Name | S**** S**** |
| Preparer Title | Sr Compliance Analyst |
| Preparer Email | S**********@e*******.com |
| Preparer Telephone | 715-395-3620 |
| Prepared Date | 2022-12-09 00:00:00 |
| Authorizer Name | L*** S********** |
| Authorizer Telephone | 715-394-1584 |
| Authorizer Title | Supervisor Us Regulatory Compliance |
| Authorizer Email | L***************@e*******.com |
| Narrative | On november 12, 2022 at 2:59 am cst, the edmonton control center received a seal fail alarm on unit 3 at moorefield station and the unit was locked out. At 3:29 am cst the edmonton control center received a sump alert and the moorefield station was shut down and isolated. An on-call technician was called out to investigate the alarm. At 4:30 am cst technician arrived at moorefield station and discovered approximately 10 gallons of crude oil had been released in the pump building. The source of the release was identified as a seal on the unit 3 pump. Additional resources arrived on site for cleanup and repairs. The majority of product was contained within the pump building on the concrete floor with a small amount that migrated out of the building and onto the gravel. All product was cleaned up and less than one cubic yard of contaminated soil was removed and properly disposed of. The investigation determined the cause of the release was due to normal wear and tear of the seal from years of service. The seal was replaced and unit 3 was returned to service. |