HL incident on 2022-11-14 — CO

Operator
Fundare Resources Operating Company, Llc
Cause
Natural Force Damage
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$5,000
Incident datetime
2022-11-14 12:38
Report number
Location
CO
Narrative
On november 14, 2022 a three-inch valve froze and split at the seat causing the valve to fail. The leak was discovered during routine maintenance. Oil was released out of the failed valve onto the location. All the released product was contained on the location and there was no threat to surface water, groundwater, or wildlife. The total amount released was 28.19bbls (1,183.98 gallons) and the total amount recovered was 25.5bbl (1,071 gallons). Clean-up and excavation commenced immediately, and soil samples have been collected. The valve was replaced, and the site was returned to service at 16:15. The 48 hour notice was not submitted as rule 195.52 did not apply to this incident. The notice that was submitted was submitted per the previous operator's pipeline spill and emergency response plan which is currently being edited. During colder weather events the valves will be checked more frequently for freezing conditions.
Detailed record list
Report Received Date
2022-11-29 00:00:00
Iyear
2022
Report Number
20220264
Supplemental Number
37462
Report Type
Supplemental Final
Operator Id
Name
Fundare Resources Operating Company, Llc
Operator Street Address
5251 Dtc Pkwy Ste #950
Operator City Name
Greenwood Village
Operator State Abbreviation
CO
Operator Postal Code
80111
Local Datetime
2022-11-14 10:00:00
Time Zone
Mountain
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Crude Oil
Unintentional Release Bbls
28.19
Recovered Bbls
25.5
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Contractor Working For The Operator
Incident Identified Datetime
2022-11-14 12:38:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-11-14 12:42:00
Restart Datetime
2022-11-14 16:15:00
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2022-11-15 08:00:00
On Site Datetime
2022-11-14 12:55:00
Confirmed Discovery Datetime
2022-11-14 12:38:00
Nrc Rpt Datetime
2022-11-21 13:15:00
Nrc Rpt Num
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Qualified Indiv Notif Datetime
2022-11-14 06:33:00
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Redtail Gas Gathering System
Segment Name
Cr 110 East
Onshore State Abbreviation
Co
Onshore Postal Code
80742
Onshore City Name
New Raymer
Onshore County Name
Weld
Designated Location
Milepost
Designated Name
10.5
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Valve
Valve Type
Auxiliary Or Other Valve
Installation Year
2015
Manufactured Year
2014
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Connection Failure
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
245
Est Cost Prop Damage
5000
Est Cost Emergency
0
Est Cost Environmental
20000
Est Cost Other
0
Prpty
25245
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
125
Mop Psig
375
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
2015-03-08 00:00:00
Maop Reversal Flow Ind
Bi-Directional
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
< 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The cause of the release was determined to be due to a frozen valve upon discovery of the release.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Natural Force Damage
Cause Details
Temperature
Natural Force Type
Temperature
Temperature Subtype
Frozen Components
Nf Extreme Weather Ind
No
Preparer Name
S***** S****
Preparer Title
Director Ehsr
Preparer Email
S*****@f***************.com
Preparer Telephone
13039104511
Prepared Date
2022-12-13 00:00:00
Local Contact Name
S***** S****
Local Contact Email
S*****@f***************.com
Local Contact Telephone
13039104511
Authorizer Name
S***** S****
Authorizer Telephone
13039104511
Authorizer Title
Director Ehsr
Authorizer Email
S*****@f***************.com
Narrative
On november 14, 2022 a three-inch valve froze and split at the seat causing the valve to fail. The leak was discovered during routine maintenance. Oil was released out of the failed valve onto the location. All the released product was contained on the location and there was no threat to surface water, groundwater, or wildlife. The total amount released was 28.19bbls (1,183.98 gallons) and the total amount recovered was 25.5bbl (1,071 gallons). Clean-up and excavation commenced immediately, and soil samples have been collected. The valve was replaced, and the site was returned to service at 16:15. The 48 hour notice was not submitted as rule 195.52 did not apply to this incident. The notice that was submitted was submitted per the previous operator's pipeline spill and emergency response plan which is currently being edited. During colder weather events the valves will be checked more frequently for freezing conditions.
Report Received Date 2022-11-29 00:00:00
Iyear 2022
Report Number 20220264
Supplemental Number 37462
Report Type Supplemental Final
Operator Id 40295 PHMSA Enforcement
Name Fundare Resources Operating Company, Llc
Operator Street Address 5251 Dtc Pkwy Ste #950
Operator City Name Greenwood Village
Operator State Abbreviation CO
Operator Postal Code 80111
Local Datetime 2022-11-14 10:00:00
Time Zone Mountain
Daylight Savings Ind Yes
Location Latitude 40.78112 Google Maps OpenStreetMap
Location Longitude -103.9448 Google Maps OpenStreetMap
Commodity Released Type Crude Oil
Unintentional Release Bbls 28.19
Recovered Bbls 25.5
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Contractor Working For The Operator
Incident Identified Datetime 2022-11-14 12:38:00
System Part Involved Onshore Pump/meter Station Equipment And Piping
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind Yes
Shutdown Datetime 2022-11-14 12:42:00
Restart Datetime 2022-11-14 16:15:00
Communication State Fed Ind Yes
Party Initiated Communication Operator
Initial Responder Com Datetime 2022-11-15 08:00:00
On Site Datetime 2022-11-14 12:55:00
Confirmed Discovery Datetime 2022-11-14 12:38:00
Nrc Rpt Datetime 2022-11-21 13:15:00
Nrc Rpt Num 1353138 NRC Report How to search
Ignite Ind No
Notify Qualified Indiv Ind Yes
Qualified Indiv Notif Datetime 2022-11-14 06:33:00
Oil Spill Removal Org Ind No
Num Pub Evacuated 0
Pipe Fac Name Redtail Gas Gathering System
Segment Name Cr 110 East
Onshore State Abbreviation Co
Onshore Postal Code 80742
Onshore City Name New Raymer
Onshore County Name Weld
Designated Location Milepost
Designated Name 10.5
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Intrastate
Item Involved Valve
Valve Type Auxiliary Or Other Valve
Installation Year 2015
Manufactured Year 2014
Material Involved Carbon Steel
Release Type Leak
Leak Type Connection Failure
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment No
Remediation Ind Yes
Soil Remed Ind Yes
Water Contam Ind No
Could Be Hca No
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 245
Est Cost Prop Damage 5000
Est Cost Emergency 0
Est Cost Environmental 20000
Est Cost Other 0
Prpty 25245
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 125
Mop Psig 375
Mop Cfr Section Component Design Pressure �195.406(A)(2) View CFR 49 §192
Maop Established Date 2015-03-08 00:00:00
Maop Reversal Flow Ind Bi-Directional
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function < 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind Yes
Cpm Operating Ind Yes
Cpm Functional Ind Yes
Cpm Detection Ind No
Cpm Conf Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details The cause of the release was determined to be due to a frozen valve upon discovery of the release.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Natural Force Damage
Cause Details Temperature
Natural Force Type Temperature
Temperature Subtype Frozen Components
Nf Extreme Weather Ind No
Preparer Name S***** S****
Preparer Title Director Ehsr
Preparer Email S*****@f***************.com
Preparer Telephone 13039104511
Prepared Date 2022-12-13 00:00:00
Local Contact Name S***** S****
Local Contact Email S*****@f***************.com
Local Contact Telephone 13039104511
Authorizer Name S***** S****
Authorizer Telephone 13039104511
Authorizer Title Director Ehsr
Authorizer Email S*****@f***************.com
Narrative On november 14, 2022 a three-inch valve froze and split at the seat causing the valve to fail. The leak was discovered during routine maintenance. Oil was released out of the failed valve onto the location. All the released product was contained on the location and there was no threat to surface water, groundwater, or wildlife. The total amount released was 28.19bbls (1,183.98 gallons) and the total amount recovered was 25.5bbl (1,071 gallons). Clean-up and excavation commenced immediately, and soil samples have been collected. The valve was replaced, and the site was returned to service at 16:15. The 48 hour notice was not submitted as rule 195.52 did not apply to this incident. The notice that was submitted was submitted per the previous operator's pipeline spill and emergency response plan which is currently being edited. During colder weather events the valves will be checked more frequently for freezing conditions.

All rights reserved. Copyright © by ClearPHMSA