HL incident on 2022-10-10 — TX

Operator
Williams Olefins Feedstock Pipelines, Llc
Cause
Equipment Failure
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$32,500
Incident datetime
2022-10-10 16:40
Report number
Location
TX
Narrative
The pump had been stopped for19 hours. When a seal fail alarm was triggered. The control center called out a tech to inspect the sight. Upon arrival, he found the seal was still releasing product into the atmosphere through the seal fail system. The tech isolated the seal fail tubing to stop the product release, isolated the pump site from the pipeline, and locked it out from further use. The seals will be pulled for inspection/rebuilt prior to the pump being placed back in service. Update 6/20/23 - pump has been repaired and is back in service. Update 2/8/24 - the update on 6/20/23 should have been indicated as a final report. This update is only to change the status to a final report.
Detailed record list
Report Received Date
2022-10-31 00:00:00
Iyear
2022
Report Number
20220247
Supplemental Number
39168
Report Type
Supplemental Final
Operator Id
Name
Williams Olefins Feedstock Pipelines, Llc
Operator Street Address
9 Greenway Plaza Suite 2800
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77046
Local Datetime
2022-10-10 16:40:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Other Hvl
Commodity Details
Ethane
Unintentional Release Bbls
0.21
Intentional Release Bbls
0
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Incident Identified Datetime
2022-10-10 16:40:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
It Was Gasket Failure
Communication State Fed Ind
No
On Site Datetime
2022-10-10 17:17:00
Confirmed Discovery Datetime
2022-10-10 17:17:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Bayou Ethane Line
Segment Name
Ge20 Calcasieu Pump
Onshore State Abbreviation
La
Onshore Postal Code
70647
Onshore City Name
Not Within A Municipality
Onshore County Name
Calcasieu
Designated Location
Survey Station No.
Designated Name
1108+7
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Pump
Pump Type
Centrifugal
Pump Service Type
Mainline
Installation Year
1999
Manufactured Year
1999
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Seal Or Packing
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
5
Est Cost Prop Damage
32500
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
0
Prpty
32505
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
1017
Mop Psig
1420
Mop Cfr Section
Four Hour Test Or Operation �195.406(A)(5)
Maop Established Date
1999-01-01 00:00:00
Maop Reversal Flow Ind
Bi-Directional
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
Yes
Cpm Conf Ind
Yes
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
For seal/gasket leaks no investigation of the controller is necessary.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Pump Or Pump-Related Equipment
Eq Failure Type
Pump Or Pump-Related Equipment
Other Pump Ind
Seal/packing Failure
Eq Additional Other Ind
Yes
Eq Additional Other Details
Impurities In Product Scored The Seal Faces.
Preparer Name
S****** M********
Preparer Title
Compliance Program Leader
Preparer Email
S****************@b**********.com
Preparer Telephone
(270) 688-6357
Prepared Date
2024-02-08 00:00:00
Authorizer Name
T*** B****
Authorizer Telephone
(270) 688-6497
Authorizer Title
Manager Compliance Services
Authorizer Email
T*********@b**********.com
Narrative
The pump had been stopped for19 hours. When a seal fail alarm was triggered. The control center called out a tech to inspect the sight. Upon arrival, he found the seal was still releasing product into the atmosphere through the seal fail system. The tech isolated the seal fail tubing to stop the product release, isolated the pump site from the pipeline, and locked it out from further use. The seals will be pulled for inspection/rebuilt prior to the pump being placed back in service. Update 6/20/23 - pump has been repaired and is back in service. Update 2/8/24 - the update on 6/20/23 should have been indicated as a final report. This update is only to change the status to a final report.
Report Received Date 2022-10-31 00:00:00
Iyear 2022
Report Number 20220247
Supplemental Number 39168
Report Type Supplemental Final
Operator Id 32614 PHMSA Enforcement
Name Williams Olefins Feedstock Pipelines, Llc
Operator Street Address 9 Greenway Plaza Suite 2800
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77046
Local Datetime 2022-10-10 16:40:00
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 30.289936 Google Maps OpenStreetMap
Location Longitude -93.038231 Google Maps OpenStreetMap
Commodity Released Type Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype Other Hvl
Commodity Details Ethane
Unintentional Release Bbls 0.21
Intentional Release Bbls 0
Recovered Bbls 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Incident Identified Datetime 2022-10-10 16:40:00
System Part Involved Onshore Pump/meter Station Equipment And Piping
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind No
Shutdown Explain It Was Gasket Failure
Communication State Fed Ind No
On Site Datetime 2022-10-10 17:17:00
Confirmed Discovery Datetime 2022-10-10 17:17:00
Nrc Rpt Num Nrc Notification Not Required NRC Report How to search
Ignite Ind No
Num Pub Evacuated 0
Pipe Fac Name Bayou Ethane Line
Segment Name Ge20 Calcasieu Pump
Onshore State Abbreviation La
Onshore Postal Code 70647
Onshore City Name Not Within A Municipality
Onshore County Name Calcasieu
Designated Location Survey Station No.
Designated Name 1108+7
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
Item Involved Pump
Pump Type Centrifugal
Pump Service Type Mainline
Installation Year 1999
Manufactured Year 1999
Material Involved Carbon Steel
Release Type Leak
Leak Type Seal Or Packing
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca No
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 5
Est Cost Prop Damage 32500
Est Cost Emergency 0
Est Cost Environmental 0
Est Cost Other 0
Prpty 32505
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 1017
Mop Psig 1420
Mop Cfr Section Four Hour Test Or Operation �195.406(A)(5) View CFR 49 §192
Maop Established Date 1999-01-01 00:00:00
Maop Reversal Flow Ind Bi-Directional
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind Yes
Cpm In Place Ind Yes
Cpm Operating Ind Yes
Cpm Functional Ind Yes
Cpm Detection Ind Yes
Cpm Conf Ind Yes
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details For seal/gasket leaks no investigation of the controller is necessary.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Pump Or Pump-Related Equipment
Eq Failure Type Pump Or Pump-Related Equipment
Other Pump Ind Seal/packing Failure
Eq Additional Other Ind Yes
Eq Additional Other Details Impurities In Product Scored The Seal Faces.
Preparer Name S****** M********
Preparer Title Compliance Program Leader
Preparer Email S****************@b**********.com
Preparer Telephone (270) 688-6357
Prepared Date 2024-02-08 00:00:00
Authorizer Name T*** B****
Authorizer Telephone (270) 688-6497
Authorizer Title Manager Compliance Services
Authorizer Email T*********@b**********.com
Narrative The pump had been stopped for19 hours. When a seal fail alarm was triggered. The control center called out a tech to inspect the sight. Upon arrival, he found the seal was still releasing product into the atmosphere through the seal fail system. The tech isolated the seal fail tubing to stop the product release, isolated the pump site from the pipeline, and locked it out from further use. The seals will be pulled for inspection/rebuilt prior to the pump being placed back in service. Update 6/20/23 - pump has been repaired and is back in service. Update 2/8/24 - the update on 6/20/23 should have been indicated as a final report. This update is only to change the status to a final report.

All rights reserved. Copyright © by ClearPHMSA