Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2022-09-28 — OK
Operator
Oneok Ngl Pipeline, Llc
Cause
Equipment Failure
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$300
Incident datetime
2022-09-28 12:55
Report number
Location
OK
Narrative
On 9/28/2022, oneok technicians were performing routine DOT inspections on the discharge transmitter located on the station piping header at the hammet booster station. The technicians heard a noise and observed a small flame originating from a 1" insulted union associated with the launcher trap's thermal piping. The flame was located approximately 50' away from the work activities. After approaching the location, oneok technicians manually closed the thermal piping isolation valves, which extinguished the fire.
Detailed record list
Report Received Date
2022-10-28 00:00:00
Iyear
2022
Report Number
20220245
Supplemental Number
37286
Report Type
Original Final
Operator Id
32109
Name
Oneok Ngl Pipeline, Llc
Operator Street Address
100 West Fifth Street
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74103
Local Datetime
2022-09-28 12:55:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
35.55441
Location Longitude
-97.1049
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Other Hvl
Commodity Details
Ethane/propane
Unintentional Release Bbls
0.1
Intentional Release Bbls
0
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2022-09-28 12:55:00
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
Was Able To Isolate By Closing Ball Valves
Communication State Fed Ind
No
On Site Datetime
2022-09-28 12:55:00
Confirmed Discovery Datetime
2022-09-28 12:55:00
Nrc Rpt Datetime
2022-09-28 13:57:00
Nrc Rpt Num
1348524
Additional Nrc Report Numbers
1348676
Ignite Ind
Yes
Ignite Datetime
2022-09-28 12:55:00
How Extinguished
Other
How Extinguished Other Detail
Closed Ball Valves
Consumed By Fire In Barrels
0.03
Explode Ind
No
Upstream Action Taken
Valve Closure
Upstream Valve Close Datetime
2022-09-28 12:56:00
Upstream Valve Type Ind
Manual
Downstream Action Taken
Valve Closure
Downstream Vlv Close Datetime
2022-09-28 12:56:00
Downstream Valve Type Ind
Manual
Num Pub Evacuated
0
Pipe Fac Name
Sterling 2 / Hammet Pump Station
Segment Name
10182 / Site 240
Onshore State Abbreviation
Ok
Onshore Postal Code
74851
Onshore City Name
Not Within A Municipality
Onshore County Name
Lincoln
Designated Location
Survey Station No.
Designated Name
5068+05
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Scraper/pig Trap
Installation Year
1992
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Connection Failure
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
1
Est Cost Prop Damage
300
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
0
Prpty
301
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
775
Mop Psig
1440
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
1992-11-21 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Length Segment Isolated
3
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
No controller actions had taken place prior to the leak/fire.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Threaded Connection/coupling Failure
Eq Failure Type
Threaded Connection/coupling Failure
Other Stripped Ind
Mechanical Coupling
Eq Additional Other Ind
Yes
Eq Additional Other Details
Damaged Dielectric Sealing Surface Within The Thermal Piping Insulated Union
Preparer Name
B**** T*****
Preparer Title
Supervisor - Regulatory Compliance
Preparer Email
B***********@o****.com
Preparer Telephone
620-820-3047
Prepared Date
2022-10-28 00:00:00
Local Contact Name
P**** G**** R****
Local Contact Email
P***************@o****.com
Local Contact Telephone
580-747-1324
Authorizer Name
M*** G******
Authorizer Telephone
918-588-7382
Authorizer Title
Vp Natural Gas Liquids Pipelines And Terminals
Authorizer Email
M***********@o****.com
Narrative
On 9/28/2022, oneok technicians were performing routine DOT inspections on the discharge transmitter located on the station piping header at the hammet booster station. The technicians heard a noise and observed a small flame originating from a 1" insulted union associated with the launcher trap's thermal piping. The flame was located approximately 50' away from the work activities. After approaching the location, oneok technicians manually closed the thermal piping isolation valves, which extinguished the fire.
| Report Received Date | 2022-10-28 00:00:00 |
|---|---|
| Iyear | 2022 |
| Report Number | 20220245 |
| Supplemental Number | 37286 |
| Report Type | Original Final |
| Operator Id | 32109 PHMSA Enforcement |
| Name | Oneok Ngl Pipeline, Llc |
| Operator Street Address | 100 West Fifth Street |
| Operator City Name | Tulsa |
| Operator State Abbreviation | OK |
| Operator Postal Code | 74103 |
| Local Datetime | 2022-09-28 12:55:00 |
| Time Zone | Central |
| Daylight Savings Ind | Yes |
| Location Latitude | 35.55441 Google Maps OpenStreetMap |
| Location Longitude | -97.1049 Google Maps OpenStreetMap |
| Commodity Released Type | Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions |
| Commodity Subtype | Other Hvl |
| Commodity Details | Ethane/propane |
| Unintentional Release Bbls | 0.1 |
| Intentional Release Bbls | 0 |
| Recovered Bbls | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2022-09-28 12:55:00 |
| System Part Involved | Onshore Pipeline, Including Valve Sites |
| On Off Shore | Onshore |
| Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | Was Able To Isolate By Closing Ball Valves |
| Communication State Fed Ind | No |
| On Site Datetime | 2022-09-28 12:55:00 |
| Confirmed Discovery Datetime | 2022-09-28 12:55:00 |
| Nrc Rpt Datetime | 2022-09-28 13:57:00 |
| Nrc Rpt Num | 1348524 NRC Report How to search |
| Additional Nrc Report Numbers | 1348676 |
| Ignite Ind | Yes |
| Ignite Datetime | 2022-09-28 12:55:00 |
| How Extinguished | Other |
| How Extinguished Other Detail | Closed Ball Valves |
| Consumed By Fire In Barrels | 0.03 |
| Explode Ind | No |
| Upstream Action Taken | Valve Closure |
| Upstream Valve Close Datetime | 2022-09-28 12:56:00 |
| Upstream Valve Type Ind | Manual |
| Downstream Action Taken | Valve Closure |
| Downstream Vlv Close Datetime | 2022-09-28 12:56:00 |
| Downstream Valve Type Ind | Manual |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Sterling 2 / Hammet Pump Station |
| Segment Name | 10182 / Site 240 |
| Onshore State Abbreviation | Ok |
| Onshore Postal Code | 74851 |
| Onshore City Name | Not Within A Municipality |
| Onshore County Name | Lincoln |
| Designated Location | Survey Station No. |
| Designated Name | 5068+05 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Scraper/pig Trap |
| Installation Year | 1992 |
| Manufactured Year | Unknown |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Connection Failure |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 1 |
| Est Cost Prop Damage | 300 |
| Est Cost Emergency | 0 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 301 |
| Num Persons Hosp Not Ovnght | 0 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 0 |
| Num Business Building Affctd | 0 |
| Accident Psig | 775 |
| Mop Psig | 1440 |
| Mop Cfr Section | Component Design Pressure �195.406(A)(2) View CFR 49 §192 |
| Maop Established Date | 1992-11-21 00:00:00 |
| Maop Reversal Flow Ind | No |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Length Segment Isolated | 3 |
| Internal Inspection Ind | Yes |
| Operation Complications Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | No controller actions had taken place prior to the leak/fire. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Threaded Connection/coupling Failure |
| Eq Failure Type | Threaded Connection/coupling Failure |
| Other Stripped Ind | Mechanical Coupling |
| Eq Additional Other Ind | Yes |
| Eq Additional Other Details | Damaged Dielectric Sealing Surface Within The Thermal Piping Insulated Union |
| Preparer Name | B**** T***** |
| Preparer Title | Supervisor - Regulatory Compliance |
| Preparer Email | B***********@o****.com |
| Preparer Telephone | 620-820-3047 |
| Prepared Date | 2022-10-28 00:00:00 |
| Local Contact Name | P**** G**** R**** |
| Local Contact Email | P***************@o****.com |
| Local Contact Telephone | 580-747-1324 |
| Authorizer Name | M*** G****** |
| Authorizer Telephone | 918-588-7382 |
| Authorizer Title | Vp Natural Gas Liquids Pipelines And Terminals |
| Authorizer Email | M***********@o****.com |
| Narrative | On 9/28/2022, oneok technicians were performing routine DOT inspections on the discharge transmitter located on the station piping header at the hammet booster station. The technicians heard a noise and observed a small flame originating from a 1" insulted union associated with the launcher trap's thermal piping. The flame was located approximately 50' away from the work activities. After approaching the location, oneok technicians manually closed the thermal piping isolation valves, which extinguished the fire. |
External Resources