HL incident on 2022-09-28 — OK

Operator
Oneok Ngl Pipeline, Llc
Cause
Equipment Failure
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$300
Incident datetime
2022-09-28 12:55
Report number
Location
OK
Narrative
On 9/28/2022, oneok technicians were performing routine DOT inspections on the discharge transmitter located on the station piping header at the hammet booster station. The technicians heard a noise and observed a small flame originating from a 1" insulted union associated with the launcher trap's thermal piping. The flame was located approximately 50' away from the work activities. After approaching the location, oneok technicians manually closed the thermal piping isolation valves, which extinguished the fire.
Detailed record list
Report Received Date
2022-10-28 00:00:00
Iyear
2022
Report Number
20220245
Supplemental Number
37286
Report Type
Original Final
Operator Id
Name
Oneok Ngl Pipeline, Llc
Operator Street Address
100 West Fifth Street
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74103
Local Datetime
2022-09-28 12:55:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Other Hvl
Commodity Details
Ethane/propane
Unintentional Release Bbls
0.1
Intentional Release Bbls
0
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2022-09-28 12:55:00
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
Was Able To Isolate By Closing Ball Valves
Communication State Fed Ind
No
On Site Datetime
2022-09-28 12:55:00
Confirmed Discovery Datetime
2022-09-28 12:55:00
Nrc Rpt Datetime
2022-09-28 13:57:00
Nrc Rpt Num
Additional Nrc Report Numbers
1348676
Ignite Ind
Yes
Ignite Datetime
2022-09-28 12:55:00
How Extinguished
Other
How Extinguished Other Detail
Closed Ball Valves
Consumed By Fire In Barrels
0.03
Explode Ind
No
Upstream Action Taken
Valve Closure
Upstream Valve Close Datetime
2022-09-28 12:56:00
Upstream Valve Type Ind
Manual
Downstream Action Taken
Valve Closure
Downstream Vlv Close Datetime
2022-09-28 12:56:00
Downstream Valve Type Ind
Manual
Num Pub Evacuated
0
Pipe Fac Name
Sterling 2 / Hammet Pump Station
Segment Name
10182 / Site 240
Onshore State Abbreviation
Ok
Onshore Postal Code
74851
Onshore City Name
Not Within A Municipality
Onshore County Name
Lincoln
Designated Location
Survey Station No.
Designated Name
5068+05
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Scraper/pig Trap
Installation Year
1992
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Connection Failure
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
1
Est Cost Prop Damage
300
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
0
Prpty
301
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
775
Mop Psig
1440
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
1992-11-21 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Length Segment Isolated
3
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
No controller actions had taken place prior to the leak/fire.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Threaded Connection/coupling Failure
Eq Failure Type
Threaded Connection/coupling Failure
Other Stripped Ind
Mechanical Coupling
Eq Additional Other Ind
Yes
Eq Additional Other Details
Damaged Dielectric Sealing Surface Within The Thermal Piping Insulated Union
Preparer Name
B**** T*****
Preparer Title
Supervisor - Regulatory Compliance
Preparer Email
B***********@o****.com
Preparer Telephone
620-820-3047
Prepared Date
2022-10-28 00:00:00
Local Contact Name
P**** G**** R****
Local Contact Email
P***************@o****.com
Local Contact Telephone
580-747-1324
Authorizer Name
M*** G******
Authorizer Telephone
918-588-7382
Authorizer Title
Vp Natural Gas Liquids Pipelines And Terminals
Authorizer Email
M***********@o****.com
Narrative
On 9/28/2022, oneok technicians were performing routine DOT inspections on the discharge transmitter located on the station piping header at the hammet booster station. The technicians heard a noise and observed a small flame originating from a 1" insulted union associated with the launcher trap's thermal piping. The flame was located approximately 50' away from the work activities. After approaching the location, oneok technicians manually closed the thermal piping isolation valves, which extinguished the fire.
Report Received Date 2022-10-28 00:00:00
Iyear 2022
Report Number 20220245
Supplemental Number 37286
Report Type Original Final
Operator Id 32109 PHMSA Enforcement
Name Oneok Ngl Pipeline, Llc
Operator Street Address 100 West Fifth Street
Operator City Name Tulsa
Operator State Abbreviation OK
Operator Postal Code 74103
Local Datetime 2022-09-28 12:55:00
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 35.55441 Google Maps OpenStreetMap
Location Longitude -97.1049 Google Maps OpenStreetMap
Commodity Released Type Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype Other Hvl
Commodity Details Ethane/propane
Unintentional Release Bbls 0.1
Intentional Release Bbls 0
Recovered Bbls 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Incident Identified Datetime 2022-09-28 12:55:00
System Part Involved Onshore Pipeline, Including Valve Sites
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind No
Shutdown Explain Was Able To Isolate By Closing Ball Valves
Communication State Fed Ind No
On Site Datetime 2022-09-28 12:55:00
Confirmed Discovery Datetime 2022-09-28 12:55:00
Nrc Rpt Datetime 2022-09-28 13:57:00
Nrc Rpt Num 1348524 NRC Report How to search
Additional Nrc Report Numbers 1348676
Ignite Ind Yes
Ignite Datetime 2022-09-28 12:55:00
How Extinguished Other
How Extinguished Other Detail Closed Ball Valves
Consumed By Fire In Barrels 0.03
Explode Ind No
Upstream Action Taken Valve Closure
Upstream Valve Close Datetime 2022-09-28 12:56:00
Upstream Valve Type Ind Manual
Downstream Action Taken Valve Closure
Downstream Vlv Close Datetime 2022-09-28 12:56:00
Downstream Valve Type Ind Manual
Num Pub Evacuated 0
Pipe Fac Name Sterling 2 / Hammet Pump Station
Segment Name 10182 / Site 240
Onshore State Abbreviation Ok
Onshore Postal Code 74851
Onshore City Name Not Within A Municipality
Onshore County Name Lincoln
Designated Location Survey Station No.
Designated Name 5068+05
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
Item Involved Scraper/pig Trap
Installation Year 1992
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Leak
Leak Type Connection Failure
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 1
Est Cost Prop Damage 300
Est Cost Emergency 0
Est Cost Environmental 0
Est Cost Other 0
Prpty 301
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 775
Mop Psig 1440
Mop Cfr Section Component Design Pressure �195.406(A)(2) View CFR 49 §192
Maop Established Date 1992-11-21 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Length Segment Isolated 3
Internal Inspection Ind Yes
Operation Complications Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind Yes
Cpm Operating Ind Yes
Cpm Functional Ind Yes
Cpm Detection Ind No
Cpm Conf Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details No controller actions had taken place prior to the leak/fire.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Threaded Connection/coupling Failure
Eq Failure Type Threaded Connection/coupling Failure
Other Stripped Ind Mechanical Coupling
Eq Additional Other Ind Yes
Eq Additional Other Details Damaged Dielectric Sealing Surface Within The Thermal Piping Insulated Union
Preparer Name B**** T*****
Preparer Title Supervisor - Regulatory Compliance
Preparer Email B***********@o****.com
Preparer Telephone 620-820-3047
Prepared Date 2022-10-28 00:00:00
Local Contact Name P**** G**** R****
Local Contact Email P***************@o****.com
Local Contact Telephone 580-747-1324
Authorizer Name M*** G******
Authorizer Telephone 918-588-7382
Authorizer Title Vp Natural Gas Liquids Pipelines And Terminals
Authorizer Email M***********@o****.com
Narrative On 9/28/2022, oneok technicians were performing routine DOT inspections on the discharge transmitter located on the station piping header at the hammet booster station. The technicians heard a noise and observed a small flame originating from a 1" insulted union associated with the launcher trap's thermal piping. The flame was located approximately 50' away from the work activities. After approaching the location, oneok technicians manually closed the thermal piping isolation valves, which extinguished the fire.

All rights reserved. Copyright © by ClearPHMSA