Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2022-09-19 — GA
Operator
Colonial Pipeline Co
Cause
Incorrect Operation
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$1,000
Incident datetime
2022-09-19 07:30
Report number
Location
GA
Narrative
While sampling product on both lines 1 and 2, an operator turned on both hydrometer wells to look at the product haze. After obtaining the samples the line 2 hydrometer was inadvertently left on. Some time after the operator left the sample house the line 2 sink drain started to back up, overflowing the sink and spilling out onto the floor. A technician going to the sample house to perform unrelated work smelled product and upon opening the door noticed ulsd on the floor and immediately notified the houston control room. While starting to clean up the product it was discovered a small amount of ulsd had gotten through the seal between the wall and floor and dripped on the rocks. Upon further investigation it was determined that 26 gallons of product was released.
Detailed record list
Report Received Date
2022-10-18 00:00:00
Iyear
2022
Report Number
20220236
Supplemental Number
37256
Report Type
Supplemental Final
Operator Id
2552
Name
Colonial Pipeline Co
Operator Street Address
1000 Lake St.
Operator City Name
Alpharetta
Operator State Abbreviation
GA
Operator Postal Code
30009
Local Datetime
2022-09-19 07:30:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
29.71901833
Location Longitude
-95.17919497
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Diesel, Fuel Oil, Kerosene, Jet Fuel
Unintentional Release Bbls
0.6
Recovered Bbls
0.6
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2022-09-19 07:30:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-09-19 07:35:00
Restart Datetime
2022-09-19 07:42:00
Communication State Fed Ind
No
On Site Datetime
2022-09-19 07:30:00
Confirmed Discovery Datetime
2022-09-19 07:30:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Qualified Indiv Notif Datetime
2022-09-19 07:30:00
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Colonial Pipeline Company - Houston Area
Segment Name
2294
Onshore State Abbreviation
Tx
Onshore Postal Code
77506
Onshore City Name
Pasadena
Onshore County Name
Harris
Designated Location
Survey Station No.
Designated Name
120
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Inside A Building
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Other
Item Involved Details
Hydrometer Well Valve (Sampling Sink)
Installation Year
1998
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Overfill Or Overflow
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
72
Est Cost Prop Damage
1000
Est Cost Emergency
5000
Est Cost Environmental
0
Est Cost Other
500
Est Cost Other Details
8.f Was The Cost For Meals
Prpty
6572
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
141
Mop Psig
275
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
1963-10-30 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
< 20% Smys Regulated Transmission
Scada In Place Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The control room had no part in the sink overflow
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Incorrect Operation
Cause Details
Valve Left Or Placed In Wrong Position, But Not Resulting In A Tank, Vessel, Or Sump/separator Overflow Or Facility Overpressure
Operation Type
Valve Left Or Placed In Wrong Position, But Not Resulting In A Tank, Vessel, Or Sump/separator Overflow Or Facility Overpressure
Related Failure Follow Ind
Yes
Category Type
Normal Operating Conditions
Operator Qualification Ind
No
Preparer Name
R***** D*****
Preparer Title
Compliance Coordinator
Preparer Email
R******@c******.com
Preparer Telephone
4097904288
Prepared Date
2022-10-21 00:00:00
Authorizer Name
Q****** F******
Authorizer Telephone
7706879672
Authorizer Title
Compliance Director
Authorizer Email
Q*******@c******.com
Narrative
While sampling product on both lines 1 and 2, an operator turned on both hydrometer wells to look at the product haze. After obtaining the samples the line 2 hydrometer was inadvertently left on. Some time after the operator left the sample house the line 2 sink drain started to back up, overflowing the sink and spilling out onto the floor. A technician going to the sample house to perform unrelated work smelled product and upon opening the door noticed ulsd on the floor and immediately notified the houston control room. While starting to clean up the product it was discovered a small amount of ulsd had gotten through the seal between the wall and floor and dripped on the rocks. Upon further investigation it was determined that 26 gallons of product was released.
| Report Received Date | 2022-10-18 00:00:00 |
|---|---|
| Iyear | 2022 |
| Report Number | 20220236 |
| Supplemental Number | 37256 |
| Report Type | Supplemental Final |
| Operator Id | 2552 PHMSA Enforcement |
| Name | Colonial Pipeline Co |
| Operator Street Address | 1000 Lake St. |
| Operator City Name | Alpharetta |
| Operator State Abbreviation | GA |
| Operator Postal Code | 30009 |
| Local Datetime | 2022-09-19 07:30:00 |
| Time Zone | Central |
| Daylight Savings Ind | Yes |
| Location Latitude | 29.71901833 Google Maps OpenStreetMap |
| Location Longitude | -95.17919497 Google Maps OpenStreetMap |
| Commodity Released Type | Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions |
| Commodity Subtype | Diesel, Fuel Oil, Kerosene, Jet Fuel |
| Unintentional Release Bbls | 0.6 |
| Recovered Bbls | 0.6 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2022-09-19 07:30:00 |
| System Part Involved | Onshore Terminal/tank Farm Equipment And Piping |
| On Off Shore | Onshore |
| Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2022-09-19 07:35:00 |
| Restart Datetime | 2022-09-19 07:42:00 |
| Communication State Fed Ind | No |
| On Site Datetime | 2022-09-19 07:30:00 |
| Confirmed Discovery Datetime | 2022-09-19 07:30:00 |
| Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
| Ignite Ind | No |
| Notify Qualified Indiv Ind | Yes |
| Qualified Indiv Notif Datetime | 2022-09-19 07:30:00 |
| Oil Spill Removal Org Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Colonial Pipeline Company - Houston Area |
| Segment Name | 2294 |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 77506 |
| Onshore City Name | Pasadena |
| Onshore County Name | Harris |
| Designated Location | Survey Station No. |
| Designated Name | 120 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Inside A Building |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Other |
| Item Involved Details | Hydrometer Well Valve (Sampling Sink) |
| Installation Year | 1998 |
| Manufactured Year | Unknown |
| Material Involved | Carbon Steel |
| Release Type | Overfill Or Overflow |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 72 |
| Est Cost Prop Damage | 1000 |
| Est Cost Emergency | 5000 |
| Est Cost Environmental | 0 |
| Est Cost Other | 500 |
| Est Cost Other Details | 8.f Was The Cost For Meals |
| Prpty | 6572 |
| Num Persons Hosp Not Ovnght | 0 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 0 |
| Num Business Building Affctd | 0 |
| Accident Psig | 141 |
| Mop Psig | 275 |
| Mop Cfr Section | Component Design Pressure �195.406(A)(2) View CFR 49 §192 |
| Maop Established Date | 1963-10-30 00:00:00 |
| Maop Reversal Flow Ind | No |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | < 20% Smys Regulated Transmission |
| Scada In Place Ind | No |
| Cpm In Place Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | The control room had no part in the sink overflow |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Incorrect Operation |
| Cause Details | Valve Left Or Placed In Wrong Position, But Not Resulting In A Tank, Vessel, Or Sump/separator Overflow Or Facility Overpressure |
| Operation Type | Valve Left Or Placed In Wrong Position, But Not Resulting In A Tank, Vessel, Or Sump/separator Overflow Or Facility Overpressure |
| Related Failure Follow Ind | Yes |
| Category Type | Normal Operating Conditions |
| Operator Qualification Ind | No |
| Preparer Name | R***** D***** |
| Preparer Title | Compliance Coordinator |
| Preparer Email | R******@c******.com |
| Preparer Telephone | 4097904288 |
| Prepared Date | 2022-10-21 00:00:00 |
| Authorizer Name | Q****** F****** |
| Authorizer Telephone | 7706879672 |
| Authorizer Title | Compliance Director |
| Authorizer Email | Q*******@c******.com |
| Narrative | While sampling product on both lines 1 and 2, an operator turned on both hydrometer wells to look at the product haze. After obtaining the samples the line 2 hydrometer was inadvertently left on. Some time after the operator left the sample house the line 2 sink drain started to back up, overflowing the sink and spilling out onto the floor. A technician going to the sample house to perform unrelated work smelled product and upon opening the door noticed ulsd on the floor and immediately notified the houston control room. While starting to clean up the product it was discovered a small amount of ulsd had gotten through the seal between the wall and floor and dripped on the rocks. Upon further investigation it was determined that 26 gallons of product was released. |