Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2022-09-16 — TX
Operator
Sunoco Pipeline L.p.
Cause
Equipment Failure
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$0
Incident datetime
2022-09-16 01:38
Report number
Location
TX
Narrative
On 9/16/22 at 00:37 am, the control center confirmed discovery regarding a pipeline high differential pressure at 00:14 and itinerant lel alarm at 00:37 the twin oaks meter station. The control center shut down the pipeline and isolated the station. On-site company personnel further isolated the filter vessel using manual valves. Station piping was routed to the maintenance flare/knockout vessel to reduce pressure on the filter and reduce the leak from a slight stream to a drip. Approximately 7.5 gallons of hvl released. Filter vessel door was identified as the point-source of the leak. The filter elements and closure o-ring were replaced. The system is equipped with dual / parallel filters. One filter is normally on line and the other can be used when needed to allow for maintenance. The line was restarted at 03:29 am with the alternate filter. Supplemental & final update: an investigation determined dust/dirt in the seal area which led to the o-ring to fail causing the accident. Operations is replacing the doors on these filter units with blind style closures that will use a gasket rather than o-rings, which are used on this style door closure to prevent recurrence.
Detailed record list
Report Received Date
2022-10-13 00:00:00
Iyear
2022
Report Number
20220232
Supplemental Number
37478
Report Type
Supplemental Final
Operator Id
18718
Name
Sunoco Pipeline L.p.
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2022-09-16 00:37:00
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Latitude
39.844873
Location Longitude
-75.418314
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Other Hvl
Commodity Details
Mixture Propane, Butane, Pentane, Hexane
Unintentional Release Bbls
0.24
Intentional Release Bbls
0
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Incident Identified Datetime
2022-09-16 01:38:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-09-16 00:14:00
Restart Datetime
2022-09-16 03:29:00
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2022-09-16 15:20:00
On Site Datetime
2022-09-16 01:14:00
Confirmed Discovery Datetime
2022-09-16 01:38:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Twin Oaks Meter Station
Segment Name
12127 20-Inch Beckersville To Twin Oaks
Onshore State Abbreviation
Pa
Onshore Postal Code
19014
Onshore City Name
Aston
Onshore County Name
Delaware
Designated Location
Milepost
Designated Name
319+16
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Filter/strainer/separator
Installation Year
2018
Manufactured Year
2016
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Connection Failure
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Usa Ecological Ind
Yes
Usa Ecological Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
10
Est Cost Prop Damage
0
Est Cost Emergency
3532
Est Cost Environmental
0
Est Cost Other
0
Prpty
3542
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
943
Mop Psig
1480
Mop Cfr Section
Subpart E Pressure Test �195.406(A)(3)
Maop Established Date
2016-01-13 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Non-Threaded Connection Failure
Eq Failure Type
Non-Threaded Connection Failure
Other Non Threaded Ind
O-Ring
Eq Additional Other Ind
Yes
Eq Additional Other Details
Dust/dirt In Sealing Area Of The O-Ring
Preparer Name
T*** N*******
Preparer Title
Director - Regulatory Compliance
Preparer Email
T************@e*************.com
Preparer Telephone
713-989-7126
Prepared Date
2022-12-15 00:00:00
Authorizer Name
T*** N*******
Authorizer Telephone
713-989-7126
Authorizer Title
Director - Regulatory Compliance
Authorizer Email
T************@e*************.com
Narrative
On 9/16/22 at 00:37 am, the control center confirmed discovery regarding a pipeline high differential pressure at 00:14 and itinerant lel alarm at 00:37 the twin oaks meter station. The control center shut down the pipeline and isolated the station. On-site company personnel further isolated the filter vessel using manual valves. Station piping was routed to the maintenance flare/knockout vessel to reduce pressure on the filter and reduce the leak from a slight stream to a drip. Approximately 7.5 gallons of hvl released. Filter vessel door was identified as the point-source of the leak. The filter elements and closure o-ring were replaced. The system is equipped with dual / parallel filters. One filter is normally on line and the other can be used when needed to allow for maintenance. The line was restarted at 03:29 am with the alternate filter. Supplemental & final update: an investigation determined dust/dirt in the seal area which led to the o-ring to fail causing the accident. Operations is replacing the doors on these filter units with blind style closures that will use a gasket rather than o-rings, which are used on this style door closure to prevent recurrence.
| Report Received Date | 2022-10-13 00:00:00 |
|---|---|
| Iyear | 2022 |
| Report Number | 20220232 |
| Supplemental Number | 37478 |
| Report Type | Supplemental Final |
| Operator Id | 18718 PHMSA Enforcement |
| Name | Sunoco Pipeline L.p. |
| Operator Street Address | 1300 Main Street |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77002 |
| Local Datetime | 2022-09-16 00:37:00 |
| Time Zone | Eastern |
| Daylight Savings Ind | Yes |
| Location Latitude | 39.844873 Google Maps OpenStreetMap |
| Location Longitude | -75.418314 Google Maps OpenStreetMap |
| Commodity Released Type | Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions |
| Commodity Subtype | Other Hvl |
| Commodity Details | Mixture Propane, Butane, Pentane, Hexane |
| Unintentional Release Bbls | 0.24 |
| Intentional Release Bbls | 0 |
| Recovered Bbls | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations) |
| Incident Identified Datetime | 2022-09-16 01:38:00 |
| System Part Involved | Onshore Pump/meter Station Equipment And Piping |
| On Off Shore | Onshore |
| Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2022-09-16 00:14:00 |
| Restart Datetime | 2022-09-16 03:29:00 |
| Communication State Fed Ind | Yes |
| Party Initiated Communication | Operator |
| Initial Responder Com Datetime | 2022-09-16 15:20:00 |
| On Site Datetime | 2022-09-16 01:14:00 |
| Confirmed Discovery Datetime | 2022-09-16 01:38:00 |
| Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
| Ignite Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Twin Oaks Meter Station |
| Segment Name | 12127 20-Inch Beckersville To Twin Oaks |
| Onshore State Abbreviation | Pa |
| Onshore Postal Code | 19014 |
| Onshore City Name | Aston |
| Onshore County Name | Delaware |
| Designated Location | Milepost |
| Designated Name | 319+16 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Filter/strainer/separator |
| Installation Year | 2018 |
| Manufactured Year | 2016 |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Connection Failure |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | Yes |
| High Pop Ind | Yes |
| High Pop Yes No | Yes |
| Usa Ecological Ind | Yes |
| Usa Ecological Yes No | Yes |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 10 |
| Est Cost Prop Damage | 0 |
| Est Cost Emergency | 3532 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 3542 |
| Num Persons Hosp Not Ovnght | 0 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 0 |
| Num Business Building Affctd | 0 |
| Accident Psig | 943 |
| Mop Psig | 1480 |
| Mop Cfr Section | Subpart E Pressure Test �195.406(A)(3) View CFR 49 §192 |
| Maop Established Date | 2016-01-13 00:00:00 |
| Maop Reversal Flow Ind | No |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | Yes |
| Scada Conf Ind | Yes |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | Yes, specify investigation result(s): (select all that apply) |
| Invest No Control Room Ind | Yes |
| Invest No Controller Ind | Yes |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Non-Threaded Connection Failure |
| Eq Failure Type | Non-Threaded Connection Failure |
| Other Non Threaded Ind | O-Ring |
| Eq Additional Other Ind | Yes |
| Eq Additional Other Details | Dust/dirt In Sealing Area Of The O-Ring |
| Preparer Name | T*** N******* |
| Preparer Title | Director - Regulatory Compliance |
| Preparer Email | T************@e*************.com |
| Preparer Telephone | 713-989-7126 |
| Prepared Date | 2022-12-15 00:00:00 |
| Authorizer Name | T*** N******* |
| Authorizer Telephone | 713-989-7126 |
| Authorizer Title | Director - Regulatory Compliance |
| Authorizer Email | T************@e*************.com |
| Narrative | On 9/16/22 at 00:37 am, the control center confirmed discovery regarding a pipeline high differential pressure at 00:14 and itinerant lel alarm at 00:37 the twin oaks meter station. The control center shut down the pipeline and isolated the station. On-site company personnel further isolated the filter vessel using manual valves. Station piping was routed to the maintenance flare/knockout vessel to reduce pressure on the filter and reduce the leak from a slight stream to a drip. Approximately 7.5 gallons of hvl released. Filter vessel door was identified as the point-source of the leak. The filter elements and closure o-ring were replaced. The system is equipped with dual / parallel filters. One filter is normally on line and the other can be used when needed to allow for maintenance. The line was restarted at 03:29 am with the alternate filter. Supplemental & final update: an investigation determined dust/dirt in the seal area which led to the o-ring to fail causing the accident. Operations is replacing the doors on these filter units with blind style closures that will use a gasket rather than o-rings, which are used on this style door closure to prevent recurrence. |