Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2022-08-27 — OK
Operator
Oneok Ngl Pipeline, Llc
Cause
Incorrect Operation
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$200
Incident datetime
2022-08-27 18:26
Report number
Location
OK
Narrative
On 8/27/2022 oneok and contractor personnel were performing work connecting new header piping to existing header piping at oneok mont belvieu pump station. The existing header piping had been isolated and evacuated of product in addition to a welding blanket placed in preparation for the new connection and associated welding. During the welding procedure the fire watch noticed a small, non-pressurized fire on the flange connecting the new and existing header piping. The fire was immediately extinguished and work halted. Oneok's on site investigation found that during the welding procedure the flange/spec blind connection of the new to existing header piping was not properly torqued. An isolation valve used to isolate from active piping had a small leak-by into the evacuated piping causing a release of less than 0.25 gallons of product at the improperly torqued flange/spec blind. Despite there being no vapors detected using lel monitors prior to welding and during grinding activities, the small vapor release from the flange ignited during grinding causing the small fire.
Detailed record list
Report Received Date
2022-09-26 00:00:00
Iyear
2022
Report Number
20220223
Supplemental Number
37167
Report Type
Original Final
Operator Id
32109
Name
Oneok Ngl Pipeline, Llc
Operator Street Address
100 West Fifth Street
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74103
Local Datetime
2022-08-27 18:26:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
29.8534
Location Longitude
-94.89279
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls
0.1
Intentional Release Bbls
0
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Contractor Working For The Operator
Incident Identified Datetime
2022-08-27 18:26:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Idle
Communication State Fed Ind
No
On Site Datetime
2022-08-27 18:26:00
Confirmed Discovery Datetime
2022-08-27 18:26:00
Nrc Rpt Datetime
2022-08-27 20:10:00
Nrc Rpt Num
1345723
Additional Nrc Report Numbers
1345860
Ignite Ind
Yes
Ignite Datetime
2022-08-27 18:26:00
How Extinguished
Operator/contractor
Consumed By Fire In Barrels
0.1
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Oneok Mont Belvieu Pump Station
Segment Name
460
Onshore State Abbreviation
Tx
Onshore Postal Code
77580
Onshore City Name
Mont Belvieu
Onshore County Name
Chambers
Designated Location
Survey Station No.
Designated Name
460
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Flange Assembly
Installation Year
2018
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Connection Failure
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
Commercially Nav Ind
Yes
Commercially Nav Yes No
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Other Pop Ind
Yes
Other Pop Yes No
Yes
Usa Drinking Ind
Yes
Usa Drinking Yes No
Yes
Usa Ecological Ind
Yes
Usa Ecological Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
0
Est Cost Prop Damage
200
Est Cost Emergency
800
Est Cost Environmental
0
Est Cost Other
0
Prpty
1000
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
0
Mop Psig
2160
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
2018-04-08 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Pipeline was idle at the time of release and no controller actions were required.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Incorrect Operation
Cause Details
Equipment Not Installed Properly
Operation Type
Equipment Not Installed Properly
Related Failure Follow Ind
Yes
Category Type
Construction
Operator Qualification Ind
Yes
Qualified Individuals
Yes, They Were Qualified For The Task(S)
Preparer Name
M***** C********
Preparer Title
Regulatory Compliance Specialist
Preparer Email
M***************@o****.com
Preparer Telephone
2542928911
Prepared Date
2022-09-25 00:00:00
Local Contact Name
M***** C********
Local Contact Email
M***************@o****.com
Local Contact Telephone
2542928911
Authorizer Name
M***** C********
Authorizer Telephone
2542928911
Authorizer Title
Regulatory Compliance Specialist
Authorizer Email
M***************@o****.com
Narrative
On 8/27/2022 oneok and contractor personnel were performing work connecting new header piping to existing header piping at oneok mont belvieu pump station. The existing header piping had been isolated and evacuated of product in addition to a welding blanket placed in preparation for the new connection and associated welding. During the welding procedure the fire watch noticed a small, non-pressurized fire on the flange connecting the new and existing header piping. The fire was immediately extinguished and work halted. Oneok's on site investigation found that during the welding procedure the flange/spec blind connection of the new to existing header piping was not properly torqued. An isolation valve used to isolate from active piping had a small leak-by into the evacuated piping causing a release of less than 0.25 gallons of product at the improperly torqued flange/spec blind. Despite there being no vapors detected using lel monitors prior to welding and during grinding activities, the small vapor release from the flange ignited during grinding causing the small fire.
| Report Received Date | 2022-09-26 00:00:00 |
|---|---|
| Iyear | 2022 |
| Report Number | 20220223 |
| Supplemental Number | 37167 |
| Report Type | Original Final |
| Operator Id | 32109 PHMSA Enforcement |
| Name | Oneok Ngl Pipeline, Llc |
| Operator Street Address | 100 West Fifth Street |
| Operator City Name | Tulsa |
| Operator State Abbreviation | OK |
| Operator Postal Code | 74103 |
| Local Datetime | 2022-08-27 18:26:00 |
| Time Zone | Central |
| Daylight Savings Ind | Yes |
| Location Latitude | 29.8534 Google Maps OpenStreetMap |
| Location Longitude | -94.89279 Google Maps OpenStreetMap |
| Commodity Released Type | Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions |
| Commodity Subtype | Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid) |
| Unintentional Release Bbls | 0.1 |
| Intentional Release Bbls | 0 |
| Recovered Bbls | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Contractor Working For The Operator |
| Incident Identified Datetime | 2022-08-27 18:26:00 |
| System Part Involved | Onshore Pump/meter Station Equipment And Piping |
| On Off Shore | Onshore |
| Status When Identified | Idle |
| Communication State Fed Ind | No |
| On Site Datetime | 2022-08-27 18:26:00 |
| Confirmed Discovery Datetime | 2022-08-27 18:26:00 |
| Nrc Rpt Datetime | 2022-08-27 20:10:00 |
| Nrc Rpt Num | 1345723 NRC Report How to search |
| Additional Nrc Report Numbers | 1345860 |
| Ignite Ind | Yes |
| Ignite Datetime | 2022-08-27 18:26:00 |
| How Extinguished | Operator/contractor |
| Consumed By Fire In Barrels | 0.1 |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Oneok Mont Belvieu Pump Station |
| Segment Name | 460 |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 77580 |
| Onshore City Name | Mont Belvieu |
| Onshore County Name | Chambers |
| Designated Location | Survey Station No. |
| Designated Name | 460 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Intrastate |
| Item Involved | Flange Assembly |
| Installation Year | 2018 |
| Manufactured Year | Unknown |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Connection Failure |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | Yes |
| Commercially Nav Ind | Yes |
| Commercially Nav Yes No | Yes |
| High Pop Ind | Yes |
| High Pop Yes No | Yes |
| Other Pop Ind | Yes |
| Other Pop Yes No | Yes |
| Usa Drinking Ind | Yes |
| Usa Drinking Yes No | Yes |
| Usa Ecological Ind | Yes |
| Usa Ecological Yes No | Yes |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 0 |
| Est Cost Prop Damage | 200 |
| Est Cost Emergency | 800 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 1000 |
| Num Persons Hosp Not Ovnght | 0 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 0 |
| Num Business Building Affctd | 0 |
| Accident Psig | 0 |
| Mop Psig | 2160 |
| Mop Cfr Section | Component Design Pressure �195.406(A)(2) View CFR 49 §192 |
| Maop Established Date | 2018-04-08 00:00:00 |
| Maop Reversal Flow Ind | No |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | No |
| Cpm In Place Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Pipeline was idle at the time of release and no controller actions were required. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Incorrect Operation |
| Cause Details | Equipment Not Installed Properly |
| Operation Type | Equipment Not Installed Properly |
| Related Failure Follow Ind | Yes |
| Category Type | Construction |
| Operator Qualification Ind | Yes |
| Qualified Individuals | Yes, They Were Qualified For The Task(S) |
| Preparer Name | M***** C******** |
| Preparer Title | Regulatory Compliance Specialist |
| Preparer Email | M***************@o****.com |
| Preparer Telephone | 2542928911 |
| Prepared Date | 2022-09-25 00:00:00 |
| Local Contact Name | M***** C******** |
| Local Contact Email | M***************@o****.com |
| Local Contact Telephone | 2542928911 |
| Authorizer Name | M***** C******** |
| Authorizer Telephone | 2542928911 |
| Authorizer Title | Regulatory Compliance Specialist |
| Authorizer Email | M***************@o****.com |
| Narrative | On 8/27/2022 oneok and contractor personnel were performing work connecting new header piping to existing header piping at oneok mont belvieu pump station. The existing header piping had been isolated and evacuated of product in addition to a welding blanket placed in preparation for the new connection and associated welding. During the welding procedure the fire watch noticed a small, non-pressurized fire on the flange connecting the new and existing header piping. The fire was immediately extinguished and work halted. Oneok's on site investigation found that during the welding procedure the flange/spec blind connection of the new to existing header piping was not properly torqued. An isolation valve used to isolate from active piping had a small leak-by into the evacuated piping causing a release of less than 0.25 gallons of product at the improperly torqued flange/spec blind. Despite there being no vapors detected using lel monitors prior to welding and during grinding activities, the small vapor release from the flange ignited during grinding causing the small fire. |