HL incident on 2022-08-28 — OK

Operator
Explorer Pipeline Co
Cause
Equipment Failure
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$5,000
Incident datetime
2022-08-28 03:22
Report number
Location
OK
Narrative
On the morning of august 28, 2022, a vapor monitor alarm was received by the explorer control center. The pump station was not operational, but product from the pipeline was flowing through the station. The pipeline was shut down and the station was isolated from the mainline pipeline. Field personnel were dispatched to the gerald, mo pump station and discovered a 150-gallon release of gasoline that was totally contained to the property. The source of the release was confirmed to be the seal on the control valve which was submitted to a third-party for failure analysis. Any free phase product was recovered, and any petroleum impacted soil was properly managed.
Detailed record list
Report Received Date
2022-09-26 00:00:00
Iyear
2022
Report Number
20220222
Supplemental Number
37728
Report Type
Supplemental Final
Operator Id
Name
Explorer Pipeline Co
Operator Street Address
Po Box 2650
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74101
Local Datetime
2022-08-28 03:22:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Gasoline (Non-Ethanol)
Unintentional Release Bbls
3.57
Recovered Bbls
3.57
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Incident Identified Datetime
2022-08-28 03:22:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-08-28 02:44:00
Restart Datetime
2022-08-28 14:23:00
Communication State Fed Ind
Yes
Party Initiated Communication
Local/state/federal Emergency Responder
Initial Responder Com Datetime
2022-08-29 13:26:00
On Site Datetime
2022-08-28 03:22:00
Confirmed Discovery Datetime
2022-08-29 03:22:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Qualified Indiv Notif Datetime
2022-08-28 03:24:00
Oil Spill Removal Org Ind
Yes
Osro Activated Datetime
2022-08-28 04:21:00
Osro Arrived On Site Dt
8/28/2022 8:15
Num Pub Evacuated
0
Pipe Fac Name
Gerald Pump Station
Segment Name
Gerald Pump Station
Onshore State Abbreviation
Mo
Onshore Postal Code
63037
Onshore City Name
Gerald
Onshore County Name
Franklin
Designated Location
Milepost
Designated Name
316.45
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Valve
Valve Type
Auxiliary Or Other Valve
Installation Year
2016
Manufactured Year
Unknown
Material Involved
Material Other Than Carbon Steel
Material Details
Viton
Release Type
Leak
Leak Type
Seal Or Packing
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
400
Est Cost Prop Damage
5000
Est Cost Emergency
18316
Est Cost Environmental
2000
Est Cost Other
0
Prpty
25716
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
125.7
Mop Psig
1440
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
1971-12-15 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest Schedule Ind
Yes
Invest Other Ind
Yes
Invest Other Ind Details
Investigation Identified An Intermittent Vapor Monitor Alarm Delayed Isolation Of The Pump Station From The Pipeline. Vapor Monitor Alarm Will Now Latch To Prevent An Intermittent Alarm That Prompts Station Isolation, Field Verification, And Resetting Of Alarm Locally.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Non-Threaded Connection Failure
Eq Failure Type
Non-Threaded Connection Failure
Other Non Threaded Ind
Seal (Not Pump Seal) Or Packing
Additional Erosion Wear Ind
Yes
Preparer Name
K**** E* B****
Preparer Title
Manager Dot And Regulatory Compliance
Preparer Email
K*****@e***.com
Preparer Telephone
9184935104
Prepared Date
2023-02-20 00:00:00
Local Contact Name
R***** M****
Local Contact Email
R*****@e***.com
Local Contact Telephone
9185913182
Authorizer Name
L***** S******
Authorizer Telephone
9183595471
Authorizer Title
Vice President Hsse
Authorizer Email
L*******@e***.com
Narrative
On the morning of august 28, 2022, a vapor monitor alarm was received by the explorer control center. The pump station was not operational, but product from the pipeline was flowing through the station. The pipeline was shut down and the station was isolated from the mainline pipeline. Field personnel were dispatched to the gerald, mo pump station and discovered a 150-gallon release of gasoline that was totally contained to the property. The source of the release was confirmed to be the seal on the control valve which was submitted to a third-party for failure analysis. Any free phase product was recovered, and any petroleum impacted soil was properly managed.
Report Received Date 2022-09-26 00:00:00
Iyear 2022
Report Number 20220222
Supplemental Number 37728
Report Type Supplemental Final
Operator Id 4805 PHMSA Enforcement
Name Explorer Pipeline Co
Operator Street Address Po Box 2650
Operator City Name Tulsa
Operator State Abbreviation OK
Operator Postal Code 74101
Local Datetime 2022-08-28 03:22:00
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 38.352573 Google Maps OpenStreetMap
Location Longitude -91.323912 Google Maps OpenStreetMap
Commodity Released Type Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype Gasoline (Non-Ethanol)
Unintentional Release Bbls 3.57
Recovered Bbls 3.57
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Incident Identified Datetime 2022-08-28 03:22:00
System Part Involved Onshore Pump/meter Station Equipment And Piping
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind Yes
Shutdown Datetime 2022-08-28 02:44:00
Restart Datetime 2022-08-28 14:23:00
Communication State Fed Ind Yes
Party Initiated Communication Local/state/federal Emergency Responder
Initial Responder Com Datetime 2022-08-29 13:26:00
On Site Datetime 2022-08-28 03:22:00
Confirmed Discovery Datetime 2022-08-29 03:22:00
Nrc Rpt Num Nrc Notification Not Required NRC Report How to search
Ignite Ind No
Notify Qualified Indiv Ind Yes
Qualified Indiv Notif Datetime 2022-08-28 03:24:00
Oil Spill Removal Org Ind Yes
Osro Activated Datetime 2022-08-28 04:21:00
Osro Arrived On Site Dt 8/28/2022 8:15
Num Pub Evacuated 0
Pipe Fac Name Gerald Pump Station
Segment Name Gerald Pump Station
Onshore State Abbreviation Mo
Onshore Postal Code 63037
Onshore City Name Gerald
Onshore County Name Franklin
Designated Location Milepost
Designated Name 316.45
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
Item Involved Valve
Valve Type Auxiliary Or Other Valve
Installation Year 2016
Manufactured Year Unknown
Material Involved Material Other Than Carbon Steel
Material Details Viton
Release Type Leak
Leak Type Seal Or Packing
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 400
Est Cost Prop Damage 5000
Est Cost Emergency 18316
Est Cost Environmental 2000
Est Cost Other 0
Prpty 25716
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 125.7
Mop Psig 1440
Mop Cfr Section Component Design Pressure �195.406(A)(2) View CFR 49 §192
Maop Established Date 1971-12-15 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind No
Cpm In Place Ind Yes
Cpm Operating Ind Yes
Cpm Functional Ind Yes
Cpm Detection Ind No
Cpm Conf Ind No
Investigation Status Yes, specify investigation result(s): (select all that apply)
Invest Schedule Ind Yes
Invest Other Ind Yes
Invest Other Ind Details Investigation Identified An Intermittent Vapor Monitor Alarm Delayed Isolation Of The Pump Station From The Pipeline. Vapor Monitor Alarm Will Now Latch To Prevent An Intermittent Alarm That Prompts Station Isolation, Field Verification, And Resetting Of Alarm Locally.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Non-Threaded Connection Failure
Eq Failure Type Non-Threaded Connection Failure
Other Non Threaded Ind Seal (Not Pump Seal) Or Packing
Additional Erosion Wear Ind Yes
Preparer Name K**** E* B****
Preparer Title Manager Dot And Regulatory Compliance
Preparer Email K*****@e***.com
Preparer Telephone 9184935104
Prepared Date 2023-02-20 00:00:00
Local Contact Name R***** M****
Local Contact Email R*****@e***.com
Local Contact Telephone 9185913182
Authorizer Name L***** S******
Authorizer Telephone 9183595471
Authorizer Title Vice President Hsse
Authorizer Email L*******@e***.com
Narrative On the morning of august 28, 2022, a vapor monitor alarm was received by the explorer control center. The pump station was not operational, but product from the pipeline was flowing through the station. The pipeline was shut down and the station was isolated from the mainline pipeline. Field personnel were dispatched to the gerald, mo pump station and discovered a 150-gallon release of gasoline that was totally contained to the property. The source of the release was confirmed to be the seal on the control valve which was submitted to a third-party for failure analysis. Any free phase product was recovered, and any petroleum impacted soil was properly managed.