HL incident on 2022-08-25 — TX

Operator
Enbridge Energy, Limited Partnership
Cause
Corrosion Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$43,833
Incident datetime
2022-08-25 11:36
Report number
Location
TX
Narrative
On august 25, 2022 at approximately 11:36 cdt, a contractor was conducting sandblasting on the 36" tank header at an integrity dig near tank 23 at the superior terminal. Contractor noticed oil appearing on the bottom of the pipe, and notified enbridge employee. The edmonton control center was contacted and the piping was isolated. Approximately one gallon of crude oil was released into the containment tub that was under the tank piping with no impact to soil. The area of concern was temporarily plugged until further repairs could be made. It was determined at 14:10 cdt that the repair would exceed the $50,000 nrc reporting threshold. The nrc was notified at 14:54 cdt (report # 1345537). A split sleeve plidco repair clamp was installed to complete the repair and nde testing was conducted on the tank line prior to it being returned to service at 17:00 cdt. The nrc 48-hour update notification was completed on august 26, 2022 at 14:47 cdt (report# 1345633). The cause of the release has been attributed to internal corrosion. The location of the failure was on a dead leg section of piping that does not see flow, causing water to separate and pool at the bottom of the pipe resulting in a pinhole when sandblasted. This section of piping was specifically identified for the integrity dig and assessment due to these characteristics. Further inspection and planning is required to develop a path forward on a permanent repair. The actual volume released at superior terminal was 0.02 barrels of crude oil. The PHMSA portal does not recognize volumes less than 0.1 barrels therefore that is the volume entered.
Detailed record list
Report Received Date
2022-09-23 00:00:00
Iyear
2022
Report Number
20220220
Supplemental Number
37159
Report Type
Original Final
Operator Id
Name
Enbridge Energy, Limited Partnership
Operator Street Address
915 N Eldridge Parkway, Suite 1100
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77079
Local Datetime
2022-08-25 14:10:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Crude Oil
Unintentional Release Bbls
0.1
Recovered Bbls
0.1
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Contractor Working For The Operator
Incident Identified Datetime
2022-08-25 11:36:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
The Pipe Segment Was Not In Operation During The Maintenance Activity
Communication State Fed Ind
No
On Site Datetime
2022-08-25 11:36:00
Confirmed Discovery Datetime
2022-08-25 14:10:00
Nrc Rpt Datetime
2022-08-25 14:54:00
Nrc Rpt Num
Additional Nrc Report Numbers
1345633
Ignite Ind
No
Notify Qualified Indiv Ind
No
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Superior Terminal
Segment Name
Tank 23 Piping
Onshore State Abbreviation
Wi
Onshore Postal Code
54880
Onshore City Name
Superior
Onshore County Name
Douglas
Designated Location
Milepost
Designated Name
1098
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Underground
Incident Area Subtype
Exposed Due To Excavation
Depth Of Cover
60
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Pipe
Pipe Type
Pipe Body
Puddle Weld Ind
No
Pipe Diameter
36
Pipe Wall Thickness
0.281
Pipe Smys
52200
Pipe Specification
5lx-X52
Pipe Seam Type
Single Saw
Pipe Manufacturer
Unknown
Pipe Coating Type
Coal Tar
Coating Applied Ind
No
Installation Year
Unknown
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
Other Pop Ind
Yes
Other Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
0
Est Cost Prop Damage
43833
Est Cost Emergency
327
Est Cost Environmental
142128
Est Cost Other
0
Prpty
186288
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
3
Mop Psig
222
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
1971-10-31 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
Internal Corrosion
Internal External
Internal Corrosion
Int Visual Exam Results
General Corrosion
Int Water Acid Ind
Yes
Int Field Exam Basis Ind
Yes
Int Low Point Pipe Loc Ind
Yes
Int Dead Leg Loc Ind
Yes
Corrosion Inhibitors
No
Corrosion Lining
No
Cleaning Dewatering
Not Applicable - Not Mainline Pipe
Corrosion Coupons
Not Applicable - Not Mainline Pipe
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
Yes
Hydrtst Most Rcnt Year
1971
Hydrtst Most Rcnt Pressure
278
Direct Asmnt Conducted
Yes, And An Investigative Dig Was Cunducted At The Point Of The Accident
Direct Asmnt At Pnt Accdnt Yr
2022
Asmnt Ecda Rcnt Ind
Yes
Asmnt Ecda Rcnt Year
2022
Non Destructive Exam Ind
No
Preparer Name
S**** S****
Preparer Title
Sr Compliance Analyst
Preparer Email
S**********@e*******.com
Preparer Telephone
715-395-3620
Prepared Date
2022-09-23 00:00:00
Authorizer Name
L*** S**********
Authorizer Telephone
715-394-1584
Authorizer Title
Supervisor Us Regulatory Compliance
Authorizer Email
L***************@e*******.com
Narrative
On august 25, 2022 at approximately 11:36 cdt, a contractor was conducting sandblasting on the 36" tank header at an integrity dig near tank 23 at the superior terminal. Contractor noticed oil appearing on the bottom of the pipe, and notified enbridge employee. The edmonton control center was contacted and the piping was isolated. Approximately one gallon of crude oil was released into the containment tub that was under the tank piping with no impact to soil. The area of concern was temporarily plugged until further repairs could be made. It was determined at 14:10 cdt that the repair would exceed the $50,000 nrc reporting threshold. The nrc was notified at 14:54 cdt (report # 1345537). A split sleeve plidco repair clamp was installed to complete the repair and nde testing was conducted on the tank line prior to it being returned to service at 17:00 cdt. The nrc 48-hour update notification was completed on august 26, 2022 at 14:47 cdt (report# 1345633). The cause of the release has been attributed to internal corrosion. The location of the failure was on a dead leg section of piping that does not see flow, causing water to separate and pool at the bottom of the pipe resulting in a pinhole when sandblasted. This section of piping was specifically identified for the integrity dig and assessment due to these characteristics. Further inspection and planning is required to develop a path forward on a permanent repair. The actual volume released at superior terminal was 0.02 barrels of crude oil. The PHMSA portal does not recognize volumes less than 0.1 barrels therefore that is the volume entered.
Report Received Date 2022-09-23 00:00:00
Iyear 2022
Report Number 20220220
Supplemental Number 37159
Report Type Original Final
Operator Id 11169 PHMSA Enforcement
Name Enbridge Energy, Limited Partnership
Operator Street Address 915 N Eldridge Parkway, Suite 1100
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77079
Local Datetime 2022-08-25 14:10:00
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 46.683961 Google Maps OpenStreetMap
Location Longitude -92.063401 Google Maps OpenStreetMap
Commodity Released Type Crude Oil
Unintentional Release Bbls 0.1
Recovered Bbls 0.1
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Contractor Working For The Operator
Incident Identified Datetime 2022-08-25 11:36:00
System Part Involved Onshore Terminal/tank Farm Equipment And Piping
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind No
Shutdown Explain The Pipe Segment Was Not In Operation During The Maintenance Activity
Communication State Fed Ind No
On Site Datetime 2022-08-25 11:36:00
Confirmed Discovery Datetime 2022-08-25 14:10:00
Nrc Rpt Datetime 2022-08-25 14:54:00
Nrc Rpt Num 1345537 NRC Report How to search
Additional Nrc Report Numbers 1345633
Ignite Ind No
Notify Qualified Indiv Ind No
Oil Spill Removal Org Ind No
Num Pub Evacuated 0
Pipe Fac Name Superior Terminal
Segment Name Tank 23 Piping
Onshore State Abbreviation Wi
Onshore Postal Code 54880
Onshore City Name Superior
Onshore County Name Douglas
Designated Location Milepost
Designated Name 1098
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Underground
Incident Area Subtype Exposed Due To Excavation
Depth Of Cover 60
Crossing No
Pipe Facility Type Interstate
Item Involved Pipe
Pipe Type Pipe Body
Puddle Weld Ind No
Pipe Diameter 36
Pipe Wall Thickness 0.281
Pipe Smys 52200
Pipe Specification 5lx-X52
Pipe Seam Type Single Saw
Pipe Manufacturer Unknown
Pipe Coating Type Coal Tar
Coating Applied Ind No
Installation Year Unknown
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Leak
Leak Type Pinhole
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca Yes
Other Pop Ind Yes
Other Pop Yes No Yes
Est Cost Oper Paid 0
Est Cost Gas Released 0
Est Cost Prop Damage 43833
Est Cost Emergency 327
Est Cost Environmental 142128
Est Cost Other 0
Prpty 186288
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 3
Mop Psig 222
Mop Cfr Section Component Design Pressure �195.406(A)(2) View CFR 49 §192
Maop Established Date 1971-10-31 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind No
Investigation Status Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind Yes
Invest No Controller Ind Yes
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Corrosion Failure
Cause Details Internal Corrosion
Internal External Internal Corrosion
Int Visual Exam Results General Corrosion
Int Water Acid Ind Yes
Int Field Exam Basis Ind Yes
Int Low Point Pipe Loc Ind Yes
Int Dead Leg Loc Ind Yes
Corrosion Inhibitors No
Corrosion Lining No
Cleaning Dewatering Not Applicable - Not Mainline Pipe
Corrosion Coupons Not Applicable - Not Mainline Pipe
Collected Data Ind No
Has Hydrtst Conduc Before Ind Yes
Hydrtst Most Rcnt Year 1971
Hydrtst Most Rcnt Pressure 278
Direct Asmnt Conducted Yes, And An Investigative Dig Was Cunducted At The Point Of The Accident
Direct Asmnt At Pnt Accdnt Yr 2022
Asmnt Ecda Rcnt Ind Yes
Asmnt Ecda Rcnt Year 2022
Non Destructive Exam Ind No
Preparer Name S**** S****
Preparer Title Sr Compliance Analyst
Preparer Email S**********@e*******.com
Preparer Telephone 715-395-3620
Prepared Date 2022-09-23 00:00:00
Authorizer Name L*** S**********
Authorizer Telephone 715-394-1584
Authorizer Title Supervisor Us Regulatory Compliance
Authorizer Email L***************@e*******.com
Narrative On august 25, 2022 at approximately 11:36 cdt, a contractor was conducting sandblasting on the 36" tank header at an integrity dig near tank 23 at the superior terminal. Contractor noticed oil appearing on the bottom of the pipe, and notified enbridge employee. The edmonton control center was contacted and the piping was isolated. Approximately one gallon of crude oil was released into the containment tub that was under the tank piping with no impact to soil. The area of concern was temporarily plugged until further repairs could be made. It was determined at 14:10 cdt that the repair would exceed the $50,000 nrc reporting threshold. The nrc was notified at 14:54 cdt (report # 1345537). A split sleeve plidco repair clamp was installed to complete the repair and nde testing was conducted on the tank line prior to it being returned to service at 17:00 cdt. The nrc 48-hour update notification was completed on august 26, 2022 at 14:47 cdt (report# 1345633). The cause of the release has been attributed to internal corrosion. The location of the failure was on a dead leg section of piping that does not see flow, causing water to separate and pool at the bottom of the pipe resulting in a pinhole when sandblasted. This section of piping was specifically identified for the integrity dig and assessment due to these characteristics. Further inspection and planning is required to develop a path forward on a permanent repair. The actual volume released at superior terminal was 0.02 barrels of crude oil. The PHMSA portal does not recognize volumes less than 0.1 barrels therefore that is the volume entered.